© Fraunhofer ISE Simplified method for the calculation of the seasonal performance factor of heat pumps VDI 4650 Marek Miara Fraunhofer-Institut für Solare Energiesysteme ISE Annex 39 Workshop 12.11.2013, Tokyo
2
© Fraunhofer ISE COP SCOP EER SEER SPF HSPF η, (eta) APF JAZ SPF JAZ Coefficients of efficiency CSPF Different questions – proper coefficients
3
© Fraunhofer ISE VDI Verein Deutscher Ingenieure Organisation with more than 150 years history Promotion and representation of engineers Publisher of VDI guidelines „VDI Richtlinien” More than 2000 active guidelines
4
© Fraunhofer ISE VDI 4650 Part 1 Simplified method for the calculation of the seasonal performance factor of heat pumps SCOP Input for the calculation: COP values and correction factors
5
© Fraunhofer ISE Calculation method of SCOP Ground source heat pumps COP B0/W35 3 correction factors (operation conditions) SCOP H COP B0/W35 3 correction factors (operation conditions) SCOP W % factor α (coverage of HP in mono- energetic operation) SCOP seasonal (annual) coefficient of performance
6
© Fraunhofer ISE Correction factors......decide about accurateness of the results
7
© Fraunhofer ISE
9
Criticism / weaknesses of VDI 4650 Main points: Unclear source for the correction factors Lack of calculation method for inverter heat pumps Inflated results for calculation of high temperature heat pumps Inflated results for calculation of domestic hot water
10
© Fraunhofer ISE Amendment 2014 Main points: Well documented method of determination of correction factors Inclusion of calculation method for inverter heat pumps Correction of the factors for calculation of high temperature heat pumps Correction of the factors for calculation of domestic hot water
11
© Fraunhofer ISE Example New factors for DHW Comparison between VDI 4650 and DIN EN 16147: Heat pump, thermal power 6 kW by B0 / W35 and COP_N von 4,9 Buffer storage (DHW Storage), volume of 175 litres and power demand of heat pump in standby modus 35 W “Zapfprofil” XL: 2,85 efficiency according to DIN EN 16147 3,26 efficiency according to DIN EN 16147 corrected with standby – loses 3,60 efficiency according to “new” VDI factors 4,39 efficiency according to VDI 4650 Part 1: 2009
12
© Fraunhofer ISE Comparison VDI 4650 vs. „WP Effizienz” Project (Monitoring) measurement VDI 4650 difference air to water heat pumps brine to water heat pumps water to water heat pumps
13
© Fraunhofer ISE Comparison between different methods VDI 4650 vs. other methods A/W heat pump with 8,3 kW capacity at A2/W35 and T b =-8°C, Source: Annex 39 Workshop SCOP/SPF
14
© Fraunhofer ISE What is not VDI 4650 Summary “Ultra”-accurate simulation program taking into account all possible margin conditions “crystal ball” good enough for foresighting changed operation conditions and “non-standard” users behaviours The only and the best available tool
15
© Fraunhofer ISE What is VDI 4650 Summary “possible easy and sufficiently accurate” tool for calculating of SCOP values (aimed accuracy not less than 10%) Chosen tool for the HP incentive program in Germany (BAFA) Good basis for calculating ecological and financial benefits resulting from using of heat pumps
16
© Fraunhofer ISE Thank you Marek.Miara@ise.fraunhofer.de