POWER QUALITY AND NETWORK DISTURBANCES in CERN’s electrical network K. KAHLE, TS-EL Diploma students R. Sternberger, M. Neubert 1 st TS Workshop Archamps,

Slides:



Advertisements
Similar presentations
SWITCH-MODE POWER SUPPLIES AND SYSTEMS Silesian University of Technology Faculty of Automatic Control, Electronics and Computer Sciences Ryszard Siurek.
Advertisements

04/ Benefits of Using a Power Analyzer: Easily Identify Power Quality Issues Generate Detailed Reports Outlining Power Problems Utilize Smart Power.
QUALITY AND TECHNOLOGY
Modeling of Reconnection of Decentralized Power Energy Sources Using EMTP ATP Ing. Dušan MEDVEĎ, PhD. Železná Ruda-Špičák, 25. May 2010 TECHNICAL UNIVERSITY.
EMC in Electrical Power Systems Frithiof Jensen Power System Engineer November 12, 2013.
Preparing for Power Outages Like any other part of the infrastructure, electrical power to the campus can fail, either as an isolated incident (e.g., tripped.
Uninterruptible Power Supply (UPS)
Increasing the Efficiency of UPS Systems – And Proving It!
Reliability Software1 Reliability Software Minimum requirements & Best practices Frank Macedo - FERC Technical Conference July 14, 2004.
Introduction to ATS Scott Kolek – ATS Global Product Manager 2006 Annual Power Quality Meeting.
Computer Maintenance Power Quality and Protection Copyright © Texas Education Agency, All rights reserved. 1.
LHC UPS Systems and Configurations: Changes during the LS1 V. Chareyre / EN-EL LHC Beam Operation Committee 11 February 2014 EDMS No /02/2014.
Electrical Distribution: How to Ensure Safe Powering and High Availability for LHC Machine Protection Systems? V. Chareyre / EN-EL Machine Protection Panel.
Delta Confidential DES UPS introduction UPS training June 2006 Markus Schwab.
Electrical Systems Electrical Engineering in Railways –Rolling Stock –Communications & Control –Signalling –LV Installations in Stations and Buildings.
Power Converters and Power Quality Karsten KAHLE, CERN CAS Power Converters 2014, Baden (CH) 2.
Electrical power distribution in experiments W.Iwanski.
GE Critical Power © 2010 General Electric Company. All Rights Reserved. This material may not be copied or distributed in whole or in part, without prior.
The HiLumi LHC Design Study is included in the High Luminosity LHC project and is partly funded by the European Commission within the Framework Programme.
1 Power Quality Mary Santori, P.E. Senior Engineer September 12, 2013.
2. Terms and definitions1 # Terms and Definitions # Voltage Sags and Interruptions.
17.March Connection to the CERN Power System of the TT2 mercury target project by Karsten KAHLE (TS-EL)
UPS network perturbations in SX2 Vincent Chareyre EN-EL-SN ALICE Technical Coordination Meeting 7 May 2010.
EN-EL and LS2 Gerard CUMER, EN-EL february Presentation outline 2 Part 1 : Overview of CERN’s electrical network Part 2 : Power Quality _ Statistics.
Frankfurt (Germany), 6-9 June 2011 GONZALEZ–CH–RIFS4–0182 OPERATIONAL STABILITY OF SHUNT CIRCUIT-BREAKER SYSTEMS IN UNGROUNDED MV NETWORKS WITH DISTRIBUTED.
Review of the Project for the Consolidation and Upgrade of the CERN Electrical Distribution System October 24-26, 2012 THE HIGH-VOLTAGE NETWORK OF CERN.
Frankfurt (Germany), 6-9 June 2011 ISSOURIBEHERE – Argentina – RIF Session 2 – 0513 PERTURBATION MEASUREMENTS ON OVERHEAD NETWORKS USING ELECTRIC FIELD.
Chamonix Risks due to UPS malfunctioning Impact on the Superconducting Circuit Protection System Hugues Thiesen Acknowledgments:K. Dahlerup-Petersen,
1 POWER QUALITY -- Bhanu Bhushan -- April, Simple examples around us : Ceiling fan regulators Tube lights Lap-tops & peripherals Domestic inverters.
PowerSouth Lowman AC/DC Essential Voltage System.
Electromagnetic Compatibility Test for CMS Experiment. Authors C. Rivetta– Fermilab F. Arteche, F. Szoncso, - CERN.
Consolidation and Upgrade of the SPS Electrical Networks Current Status JP. Sferruzza, on behalf of EN/EL.
1 Power Quality EKT 451 CHAPTER 8. 2 Introduction Utilities transmit electricity over power lines into home as an alternating current (AC) wave. This.
Control, monitoring and safety aspects of electrical distribution in the Atlas experiment W.Iwanski PH/ESE-BE.
Introduction  Utilities transmit electricity over power lines into home as an alternating current (AC) wave.  This is how power travels through wiring.
Power Quality Karsten KAHLE Electric Power Converter Group (TE-EPC) High Power Converter Section Review of CERN’s Electrical Power Network October.
A common 400 Hz AC Power Supply Distribution System for CMS FEE. Authors C. Rivetta– Fermilab. F. Arteche, F. Szoncso, - CERN.
ATC/ABOC Days, 22 January 2007 The safety electrical networks at CERN Anne Funken, TS-EL.
Overview of the main events related to TS equipment during 2007 Definition Number and category of the events Events and measures taken for each machine.
ABOC/ATC days Electrical Network: Selectivity and Protection Plan José Carlos GASCON TS–EL Group 22 January 2007.
THE NEW STATIC VAR COMPENSATOR FOR SPS – COMMISSIONING RESULTS based on the CIRED2003 conference paper from K. Kahle, J. Pedersen (CERN) and T. Larsson,
LARSSON SE Session 2 – Block 2 Barcelona May The new 150 Mvar, 18 kV SVC at CERN – background, design and commissioning K. Kahle, J Pedersen,
Power Quality Product Overview
A second Thyristor Controlled Static Var Compensator for SPS
TE/MPE/MI MPE-TM30 th June 2011 FMCM sensitivity to mains perturbations 0v1 M. Zerlauth.
Conclusions on UPS powering test and procedure I. Romera Acknowledgements: V. Chareyre, M. Zerlauth 86 th MPP meeting –
Uninterruptible Power Supply Improves Reliability at The Australian Synchrotron Sean Murphy – ARW 2013 Melbourne.
A DSP based on on-line UPS R.Padamaja G.Mamatha Reddy EEE EEE S.V.C.E S.V.C.E BY.
J.PRAKASH.  The term power quality means different things to different people.  Power quality is the interaction of electronic equipment within the.
1 March 2001 EPCOS FK PM PFC Basics of Power Factor Correction BASICS OF POWER FACTOR CORRECTION.
Supply and Distribution of Electrical Energy
YETS & LS2 Works EN-EL / Power distribution
Uninterruptible Power Supply (UPS)
Situation of the Static Var Compensators at CERN.
Technical Services: Unavailability Root Causes, Strategy and Limitations Data and presentation in collaboration with Ronan LEDRU and Luigi SERIO.
IG BASED WINDFARMS USING STATCOM
YETS & LS2 Works EN-El on LHC / Power distribution
CERN Data Centre ‘Building 513 on the Meyrin Site’
Ensuring Security of Supply in Estonian Transmission Grid
LV Safe Powering from UPS to Clients
WELCOME TO ALL.
the CERN Electrical network protection system
YETS & LS2 Works EN-EL / Power distribution
Business opportunities related to CERN electrical network
FREQUENCY CONTROL-THE UNEXPLOITED GOLD
LHC FMCM Project 1.
PSS0 Design & Concept of Operations
Biosco: MV/LV prefabricated substations IEC Presentation of the standard Safety is a choice.
ILO Industrial Opportunities Days, 6-7 June 2019
Presentation transcript:

POWER QUALITY AND NETWORK DISTURBANCES in CERN’s electrical network K. KAHLE, TS-EL Diploma students R. Sternberger, M. Neubert 1 st TS Workshop Archamps, 4 – 6 May Definition of Power Quality and Network Disturbances 2. How to measure network disturbances ? 3. Statistics Computer simulations 5. Reliability of CERN’s distribution network 6. Conclusions

Power Quality = Quality of electrical energy supplied Definition Measurem.StatisticsSimulationReliabilityConclusions

Types of network disturbances Definition Measurem.StatisticsSimulationReliabilityConclusions DIPSWELL

Types of network disturbances Definition Measurem.StatisticsSimulationReliabilityConclusions DIPSWELL MAINS FAILURES Causes: - thunder-storms -short-circuit inside CERN - Emergency Stop operation Consequences: - accelerator stop

Types of network disturbances Definition Measurem.StatisticsSimulationReliabilityConclusions MAINS FAILURES Causes: - thunder-storms - short-circuit inside CERN - Emergency Stop operation Consequences: - accelerator stop Causes: - sudden change of load, inrush - short-circuits inside & outside CERN - thunder-storms VOLTAGE DIP / SWELL Consequences: - sometimes accelerator stop

Types of network disturbances Definition Measurem.StatisticsSimulationReliabilityConclusions MAINS FAILURES Causes: - thunder-storms - short-circuit inside CERN - Emergency Stop operation Consequences: - accelerator stop Causes: - sudden change of load, inrush - short-circuits inside & outside CERN - thunder-storms VOLTAGE DIP / SWELL Consequences: - sometimes accelerator stop TRANSIENTS Consequences: - failure of electronics Causes: - switching compensators ON - power converters (thyristors) - thunder-storms

Types of network disturbances Definition Measurem.StatisticsSimulationReliabilityConclusions MAINS FAILURES Causes: - thunder-storms - short-circuit inside CERN - Emergency Stop operation Consequences: - accelerator stop Causes: - sudden change of load, inrush - short-circuits inside & outside CERN - thunder-storms VOLTAGE DIP / SWELL Consequences: - sometimes accelerator stop TRANSIENTS Consequences: - failure of electronics Causes: - switching compensators ON - power converters (thyristors) - thunder-storms HARMONICS Causes: - non-linear loads (office PC’s, power converters etc.) Consequences: - malfunctioning of electronics

Measurement of disturbances at CERN Measurem. DefinitionStatisticsSimulationReliabilityConclusions HV: 400kV, 66kV, 18kV LV: 400V - plug-in 230V socket - 20 channels operating OSCILLOSTORE FLUKE devices channels operating - online 365 days / year - central data analysis - low cost

Statistics 2003: 400kV network Statistics DefinitionMeasurem.SimulationReliabilityConclusions 100% = nominal voltage red colour: major events (accelerator stop)

Statistics 2003: 18kV network Statistics DefinitionMeasurem.SimulationReliabilityConclusions 100% = nominal voltage red colour: major events (accelerator stop)

Statistics 2003: 400V network Statistics DefinitionMeasurem.SimulationReliabilityConclusions 100% = nominal voltage red colour: major events (accelerator stop) yellow: Blackout Italy ( )

Statistics: Harmonics 400V network Statistics DefinitionMeasurem.SimulationReliabilityConclusions Limit acc. to IEC , class 2

Statistics DefinitionMeasurem.SimulationReliabilityConclusions Statistics 2003: Causes of disturbances 400V Transients: 5% thunder-storms and short-circuits 20% power converters (commutation) 5% Compensator switching ON Voltage swell:10% thunder-storms and short-circuits, no-load Voltage dips: 50% sudden change of load (inrush, switching ON) 5% short-circuits inside and outside CERN 4% thunder-storms Mains failures:0.3% extern: thunder-storms 0.1% intern: Emergency Stop, short-circuit 100% Total consequences increase

Statistics: network disturbances The MAJORITY of network disturbances is caused WITHIN CERN. The MAJORITY of network disturbances has no consequences. Statistics DefinitionMeasurem.SimulationReliabilityConclusions

Simulation DefinitionMeasurem.StatisticsReliabilityConclusions Simulation: Thunder-storm ( :14:32)

Simulation DefinitionMeasurem.StatisticsReliabilityConclusions Simulation: Thunder-storm ( :14:32) Recording Simulation 400kV

Simulation DefinitionMeasurem.StatisticsReliabilityConclusions Simulation: Thunder-storm ( :14:32) 400kV Recording Simulation 18kV

Simulation DefinitionMeasurem.StatisticsReliabilityConclusions Simulation: Thunder-storm ( :14:32) Simulation Recording 400 V

For SPS, LHC and experiments: - 400kV overhead line to GENISSIAT power station, H.-SAVOIE - 400kV line from CHAMOSSON hydro station, VALAIS CERN Automatic Source Transfer System (AUTOTRANSFER, 20 sec) Power limited to 60MVA Back-up supply for LHC general services: - 130kV line to VERBOIS, GE Reliability DefinitionMeasurem.StatisticsSimulationConclusions Reliability: Mains failures 130kV / 400kV

Reliability DefinitionMeasurem.StatisticsSimulationConclusions Reliability of CERN’s 400V networks Normal supply network (switchboards EBDxx/xx): - supplied by 400kV grid - load sees all perturbations typical for industrial networks Assured supply network (switchboards EADxx/xx): - as Normal Supply, but with diesel generator back-up, 45sec - switched off by Emergency Stop Uninterrupted supply network (switchboards EODxx/xx): - supplied by UPS systems - load does not see any disturbances Secured supply network (switchboards ESDxx/xx): - as Assured Supply - not switched off by Emergency Stop Reliability increases

We have now comprehensive recording equipment operational. We possess detailed statistics on Power Quality at CERN. We are able to simulate major disturbances and assess their effects on accelerator operation. Power Quality at CERN is better than the IEC requirements. Our know-how: Conclusions DefinitionMeasurem.StatisticsReliabilitySimulation Conclusions 1/3

Effort is made to limit the effect of mains failures: - Autotransfer 20sec - Diesel generators 45sec - manual back-up EDF 20kV, 1h For critical loads (safety) : - UPS systems (LHC cryo. control and Computer Center B.513) - sometimes two redundant UPS in parallel Mains failures: Conclusions DefinitionMeasurem.StatisticsReliabilitySimulation Conclusions 2/3

* Not possible to eliminate transient disturbances - causes out of our control (e.g. lightning strikes, inrush etc.) * To assure the functioning of equipment through disturbances, definition of tolerance levels for user’s equipment: LHC Engineering Spec. EDMS ( ) “Main Parameters of the LHC 400/230V Distribution System” * All equipment should preferably be in conformity with this Engineering Specification. Transient events: Conclusions DefinitionMeasurem.StatisticsReliabilitySimulation Conclusions 3/3

Conclusions DefinitionMeasurem.StatisticsReliabilitySimulation Questions ? Thank you.