15 Water Supply. 15 Objectives (1 of 2) Discuss rural water supplies. Describe how portable tanks are used to supply water for firefighting. Describe.

Slides:



Advertisements
Similar presentations
Chapter 12 Lesson Goal After completing this lesson, the student shall be able to make hydrant connections and draft from a static water source according.
Advertisements

Fire Apparatus Pump Theory
Chapter 12 Lesson Goal After completing this lesson, the student shall be able to make hydrant connections and draft from a static water source according.
Operation of the FW-720 Unit 1. Side 1 2 Inlet Hand Crank.
Chapter 13 Lesson Goal After completing this lesson, the student shall be able to use various hose appliances and tools, prepare a test site for service.
© Blue Graphics Concept Sauer-Danfoss START-UP PROCEDURE PROPEL PUMP Instruction Sauer-Danfoss Belgium – T. Van Mossevelde.
Potential Pathways for Coliform Contamination. Fixing Positive Coliform Results.
CAFS On-Line Orientation
BS9990 : 2015 Updates and/or Changes
Water supply and drafting. Objectives Understand and be able to demonstrate the different hydrant lays and hook ups Explain/demonstrate how to operate.
Pumping Apparatus Driver/Operator
Chapter 12 Systems and Equipment for Fire Protection.
LoneStar Fire Specialties
CVFD Training – Water Supply SFFMA Training Objectives: –
Fire Streams SFFMA Training Objectives: –
AUTOMATIC SPRINKLERS.
FIREFIGHTER I LESSON 15. SPRINKLER SYSTEM DESIGN AND OPERATION Series of sprinklers arranged to automatically distribute enough water to extinguish or.
WATER SUPPLY Copyright© Delmar is a division of Thomson Learning.
Purpose of Standpipe and Hose Systems
Water Supply.
Chapter 9 Water Supply.
CE HYDRAULICS ENGINEERING
1402 Hybrid Firefighter I 6 th Edition Chapter 14 Water Supply.
Chapter 9 Water Supply.
Pumping Apparatus Driver/Operator
Water Supply 1. Water Supply Components
Intermediate SFFMA Objectives: – Hrs received.
Series Operational Training. 2 Water Tank Water Pump Multiple Discharges 2000 Series Line Strainer Foam Tank Electronic Direct Injection Proportioner.
Module C Sprinkler systems (4-20)
Fire Hoses, Nozzles, Portable lighting, appliances, and ladders.
Learning Objective 1 Explain the ways water supply system components are used by firefighters.
Water Supply.
1. 2 Introduction We continue to develop new methods and materials for extinguishing fires Water still remains the primary extinguishing agent because.
FIREFIGHTER II LESSON 12. TYPES OF VALVES Ball — Ball — Controls nozzle flow and pump discharge rates Gate — Gate — Controls hydrant flow Butterfly.
1 CTC 450 Review Water Quality Water Quality. 2 CTC 450 Water Distribution Systems Water Distribution Systems.
3 Water. 3 Knowledge Objectives Describe the properties of water. Describe the three sources of water. Describe water’s role in extinguishing a fire.
CHAPTER 9 Copyright © 2007 Thomson Delmar Learning 9.1 Water Supply.
Water Supply Skill Drills.
Water Supply Firefighter II.
Fire Service Pump Operator - 10 Water Supply.
FVCC Fire Rescue Water Supply.
15 Water Supply. 2 Objectives Describe the sources of water for a municipal water supply system. Explain the purpose of a water treatment facility. Describe.
TANKER OPERATIONS Long Laneway – 1 st arriving pumper P-1 FIRE BLDG House?= 38mm x2 + 65mm backup line Barn? = consider 2- 65mm right away Lay a Hi-Vol.
Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.
Firefighter III Module B Water Supply (4-19) (4-19)
Achieving Maximum Flows The Water Triangle.... The FIRE Tetrahedron.
Tanker Operations In Water Supply Michael Crawford July 2002.
Water supply definitions Water supply definitions Four Basic components of a water supply system Four Basic components of a water supply system Methods.
Video: Fire Hydrant Time: 1:01 Chap 14-1
How do we harvest rainwater and why should we.. Why Harvest Rainwater? Decrease the volume of potable water used for irrigation. Recharge the groundwater.
CHAPTER 16 Water Supply. Fire Fighter I Objectives Describe the equipment and procedures that are used to access static sources of water. Describe the.
Fire Fighter Safety SCBA CHANGE/REFILL
 All fire pumps are rated by drafting through 20 ft. of hose with 10 ft. of Lift  Theoretical Lift = 14.7 psi x 2.3 ft/psi = 33.8 ft.  Maximum practical.
Water Shuttle Operations
Snohomish County Training Officers 2013Q3. Drafting Need for drafting operations Set up and resource considerations Shuttle operations Jet Siphon Operations.
Relay Pumping Operations Sugar Land Fire Department Driver/Operator-Pumper Academy Spring 2003.
Vertical Pump Motor Manifold Upgrade. VPMM Replaces Existing Pumps, Motors, Relief Valves, Check Valves, Discharge Filters, Pump Running Pressure Gauges,
2010 Union County Water Movement Training Review Leesburg Twp. September 18, 2010.
Fire Service Pump Operator - 03 Water.
Automotive Heating And Air Conditioning
Dual Pumping Definition: An operation where a strong hydrant is used to supply two Engines by connecting the Engines intake-to-intake. The second Engine.
Water Supply (Fire Fighter I)
14 Refrigerant Recovery, Recycling, and Recharging.
2013Q1.
CTC 450 Review Water Processes.
RESIDENTIAL PLUMBING SYSTEMS (WATER SUPPLY)
AUTOMATIC SPRINKLERS.
WATER SUPPLY FOR NON-HYDRANT AREAS
State of Georgia BASIC FIRE FIGHTER TRAINING COURSE
Bella Vista Fire Department Procedures on Sprinkled Buildings
Presentation transcript:

15 Water Supply

15 Objectives (1 of 2) Discuss rural water supplies. Describe how portable tanks are used to supply water for firefighting. Describe the sources of water for a municipal water supply system.

15 Objectives (2 of 2) Describe the major features of a municipal water distribution system. Describe dry-barrel fire hydrants and wet- barrel fire hydrants. Discuss maintaining a fire hydrant. Define static pressure, residual pressure, and flow pressure.

15 Introduction (1 of 2) An uninterrupted water supply is: –The primary weapon for extinguishment –Essential for fire fighter safety Ensuring a dependable water supply is a critical fire-ground operation and must be accomplished as soon as possible.

15 Introduction (2 of 2) Water sources include: –Municipal and private water systems –Static water sources

15 Rural Water Supplies Residents of rural areas usually depend on wells or cisterns to provide water. No hydrants in these areas, so water must be obtained from other sources

15 Static Water Sources (1 of 3) Static sources include: –Rivers or streams –Lakes, ponds, oceans –Canals or reservoirs –Swimming pools –Cisterns

15 Static Water Sources (2 of 3) Must be accessible to a fire engine or portable pump –Is there a road or hard surface within 20‘ of the source? May have a dry hydrant permanently installed for speed and reliability

15 Static Water Sources (3 of 3)

15 Mobile Water Supply Apparatus Tankers or water tenders Designed to carry large volumes of water to the fire Generally carry 1000– 3500 gallons May be used to pump water directly into attack engine

15 Portable Tanks (1 of 2) Carried on fire apparatus to be quickly set up at the fire scene Typically hold 600– 5000 gallons of water Tankers are used to fill the portable tanks.

15 Portable Tanks (2 of 2) The pump operator drafts from the tanks. Dump valves on the tankers allow them to off-load up to 3000 gallons per minute.

15 Tanker Shuttles Used to deliver a large volume of water over a long period of time Number required depends on –Distance between fill site and fire scene –Time it takes to dump and to refill –Flow rate required at the fire scene Fill site should be designed to refill tankers without delays

15 Municipal Water Systems Provide clean water for public use. Provide water for fire protection. Most are owned and operated by a local government agency. Systems includes water sources, water treatment facilities, and a water distribution system.

15 Water Sources Sources include: –Wells –Rivers or streams –Lakes –Reservoirs Many systems draw water from several sources.

15 Water Distribution Systems (1 of 5) Water mains deliver water from treatment facilities to the end user. Include pumps, storage tanks, and reservoirs

15 Water Distribution Systems (2 of 5) Water pressure –Generally 20–80 psi –Hydrant pressure should not drop below 20 psi. –Usually produced by pumps (directly or indirectly)

15 Water Distribution Systems (3 of 5) Water pressure may also be produced by gravity. –Gravity-feed system –Elevated water storage towers

15 Water Distribution Systems (4 of 5) Water mains typically follow a grid system. May have dead-end mains –Water enters from only one direction. –Limited available water supply

15 Water Distribution Systems (5 of 5) Water main valves –Control valves: Located throughout system to shut down sections –Shut-off valves: Used to shut off water flow to individual customers or to hydrants

15 Fire Hydrants Provide water for firefighting purposes Installed on both public and private water systems Consist of an upright steel casing attached to the underground distribution system

15 Dry-Barrel Hydrants Used in cold climates Hydrant valve is located at the base of the barrel. Water flows into the hydrant only when it is needed.

15 Fire Hydrants Locations Located according to local standards and nationally recommended practices –Every 900' in residential areas; every 300' in high-value areas in Medina County. –Every intersection; mid-block when over set distances –Based on occupancy, construction, and size of the buildings

15 Fire Hydrant Operation Turning on a hydrant. Individual fire departments may have their own variations on this procedure. –Removed needed caps –Connect Hydrant Valve to 2 ½” discharge –Flush hydrant –Connect hose –Open hydrant completely

15 Inspecting Fire Hydrants (1 of 3) Check for visibility and access. Check for exterior damage. Ensure barrel is dry and free of debris. Ensure all caps in good working order. Open valve for water flow until clear. Shut down and ensure proper draining. Replace cap.

15 Inspecting Fire Hydrants (2 of 3)

15 Inspecting Fire Hydrants (3 of 3) To clean threads, use a steel brush. Replace cracked, broke, or missing cap gaskets. Lubricate as recommended by manufacturer.

15 Flow and Pressure (2 of 3) Static pressure: Pressure when no water is moving –Measured by placing a gauge on a port with no water in the system moving

15 Flow and Pressure (3 of 3) Residual pressure: Amount of pressure that remains in the system when water is flowing

15 Summary Rural water supply utilizes fill sites, tankers, and portable tanks. Municipal system has three components. Hydrants may be wet-barrel or dry-barrel. Inspection of hydrants is needed annually. Testing is done to determine maximum flow availability.