Life Safety Compliance: Most Common Surveyor Findings Presented by Brad Keyes, CHSP Jamie Crouch, BSBM, MHA.

Slides:



Advertisements
Similar presentations
NFPA-101, LIFE SAFETY CODE, 2003 EDITION Chapter 15 Existing Schools
Advertisements

WAYNE DALTON OF SYRACUSE PRESENTS:
Annual Fire Door Inspection
2009 Edition – NFPA 101 Steve Hornyak, DAHC, CDT, FDAI
Biggest Pitfalls and Best Practices: Life Safety
Safety in Hospitals A Computer – Based Learning Program for Students.
Facilities Management and Design Chapter 4 Safety and Security systems.
Electronic Locking and Exemption Request Form Training
Safety Training Safety First. EXITS All exit doors shall be maintained in operable condition. Exit doors shall not be locked, chained, bolted, barred,
NFPA 72 and NFPA 101 Supervised Automatic Sprinkler System Overview
“TI” Ohhhh….. (TIO) (No TIO is not a person!) What is it all about?
 Please mute your line to reduce background noise  Do not put us on hold if you have background music on your hold line.  At the end of the presentation.
Michigan Department of Licensing and Regulatory Affairs Bureau of Construction Codes.
Emergency Lighting Code Review Presented by Iota Engineering LLC.
The Life Safety Surveyor Facility Tour
January 16, 2014 Brad Keyes, CHSP Changes to the 2014 Acute Care & Critical Access Hospital Manuals on Life Safety Compliance.
Cancer Center Training 2012 Cancer Center Training 2012 “Defend in Place” Strategy for Fire Alarm Activations Cancer Center Building #7559.
Zone Valves.
Texas Department of Insurance State Fire Marshall’s Office Sixth Report on State University Fire Safety January 2002.
Indiana Federation of Ambulatory Surgical Centers September 27, 2013 To promote and provide essential public health services.
Smoke Control Fire-Rated Stairwells Fireproofing of Structural Components Egress Lighting Fire-Resistive Construction Elements Fire and Smoke Dampers Emergency.
Inspection and Testing of Fire Alarm Systems (ITFAS)
2012 International Fire Code Adopted as the minimum fire safety standard by the State of Wyoming City of Sheridan must adopt the minimum standard to retain.
FALAR Part 3 – Post Construction  Compilation of  Maintenance records of fire protection/life safety equipment  Test records of fire protection/life.
Ted “Smitty” Smith  This slide show contains multiple timed questions. All questions can be answered using the International Fire Code, The National.
Emergency Action Plans
Unit 8: Portable Fire Extinguishers & Smoke Control Management Systems
EGRESS AND FIRE PROTECTION
Health Facilities Planning Seminar Plan Review Division Irvin J. Poke, AIA, Chief Todd Y. Cordill, NCARB, Assistant Chief Providing for Michigan’s Safety.
June 30, 2015 Brad Keyes, CHSP Engineering Advisor
The Second Survey Point of Vulnerability How Should I Prepare for the Facility Tour? Healthcare Engineering Consultants.

The Physical Environment Tracers How Should I Prepare for the Physical Environment Tracers? Healthcare Engineering Consultants  Will limit.
© 2008 Delmar, Cengage Learning Property Security, Emergency Response, and Fire Protection Systems Chapter 13.
International Fire Door Inspector Association Presents New Annual Fire Door Inspections NFPA 80 – 2007, 2010, 2013 Standard for Fire Doors and Other Opening.
Means of Egress Chapter 4.
C A & Courtemanche & Associates HEALTHCARE SYNERGISTS.
Fire Safety By Alicia Civile and Alexandra Fernandez.
© 2015 American Society for Healthcare Engineering, a personal membership group of the American Hospital Association 155 N. Wacker Drive, Suite 400 | Chicago,
MINNESOTA CHAPTER AUTOMATIC FIRE ALARM ASSOCIATION Requirements of the 2003 Minnesota State Fire Code relating to Group R Occupancies September 14, 2006.
Code Officials and the Code Process.  To design the interior of the building in conjunction with codes, standards and federal regulations required in.
ID 308 Construction + Materials IV: Construction Documents Prof. Brody Endicott College Systems Coordination.
Tennessee Department of Health Bureau of Health Licensure and Regulations Division of Health Care Facilities.
MONTGOMERY COUNTY FIRE & RESCUE FAMILY CHILD CARE FIRE SAFETY NOTEBOOK Written By: M/FF Matt Kelleher 2008.
Exit Routes and Fire Protection
Courtesy: Jeff Anderson, RCDD Associate / Systems Project Manager Communications, Security & Technology Division October 14, 2015 Locking the Means of.
Maine State Fire Marshals Office1 Laws and Codes Relating to Existing Apartment occupancies in the State of Maine Mark Stevens CFI-II, CFPS, CFPE Inspections.
Part 5: Meeting the Challenge of the “EC Tracers” Healthcare Engineering Consultants How Should I Prepare for the “EC Tracer” Part of the Survey?
Work Area Method Level 3 Alterations – Chapter 9 prescribes requirements. 50% of Building Area Rule.
Presented by John Lewandowski and Mike Larabel Inspection, Testing, and Maintenance of Kitchen Hood Systems Michigan Fire Inspectors Society Winter Educational.
Exercise #2 (part 2) Based on what you read in Chapter 4, determine if the corridors and exit doors meet the requirements for egress width, according to.
Transfer Station Safety OR WORKER AND PUBLIC RISK.
Safety Rule #1 Open flames are not allowed without first obtaining a permit. The exception to this rule is during a period of closely supervised instructions,
Fire Protection Systems for Facility Managers Michael Salazar NICET Level 2.
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection.
CIHQ - All Rights Reserved 2017
ARCHITECTURAL SAFETY FEATURES –Exit Separations –Continuation of Exit Stairs from lower to upper floors –Discharge from Exits FIRE PROTECTION FEATURES.
Emergency Evacuations: Multi-Level Apartments
Brad Keyes, CHSP HFAP Engineering Advisor Jamie Crouch, BSBM, MHA
Physical Environment: Most Common Surveyor Findings
Fire Door Inspections Qualified Training
29 CFR NFPA Life Safety Code
Brad Keyes, CHSP HFAP Engineering Advisor Jamie Crouch, BSBM, MHA
How to Submit Waivers and Equivalencies October 18, 2016
Locking the Means of Egress in Health Care Facilities
Fire Alarm Tech Practice Test # 16 NICET
Head Office Emergency Evacuation Plan
Fire Alarm Practice Drill # 11 Denver Fire Department Journeyman Installer License Test © Ted Smith 2017.
Denver Fire Depart. License Fire Alarm Practice Test # 12
Fire Protection Documentation
Presentation transcript:

Life Safety Compliance: Most Common Surveyor Findings Presented by Brad Keyes, CHSP Jamie Crouch, BSBM, MHA

2 Topics… Today, we will cover the following topics: 1.Top Ten Findings by Life Safety Surveyors 2.Frequent Issues with the Document Review Session 3.Questions you may have…

Top 10 Life Safety Findings The following are the top-ten findings cited by HFAP LS surveyors during regular triennial surveys during 2015.

Top 10 Life Safety Findings Number 1: Fire Alarm System – Installation –The installation of the fire alarm system components were observed to have problems…

Top 10 Life Safety Findings Smoke detectors must be mounted at least 36 inches away from HVAC air diffusers; supply and return.

Top 10 Life Safety Findings Smoke detectors must be mounted at least 12 inches below the ceiling or deck.

Top 10 Life Safety Findings Access to the manual pull stations is obstructed.

Top 10 Life Safety Findings Number 2: Signage –This primarily involves ‘Exit’ signs and there are multiple issues that were observed…

Top 10 Life Safety Findings There must be an inventory of every ‘Exit’ sign and they must be inspected monthly with a ‘Pass’ or ‘Fail’ notation (signature required).

Top 10 Life Safety Findings ‘No Exit’ signs are required to have the word ‘No’ 2 inches tall, and the word ‘Exit’ 1 inch tall. Not Acceptable Acceptable

Top 10 Life Safety Findings Number 3: Utility Systems –Deficiencies observed with the utility systems will lead to findings. The most common findings involve the electrical system.

Top 10 Life Safety Findings Surveyors will look above the ceiling at your fire barrier and smoke barrier location… They will cite any junction-box without a cover.

Top 10 Life Safety Findings Make sure access to all electrical equipment and panels is free and clear for 36 inches.

Top 10 Life Safety Findings Number 4: Facility Demographic Report –Common problems with the FDR involve unanswered questions, or answers that do not contain basic NFPA nomenclature

Top 10 Life Safety Findings The construction type is not listed in NFPA 220 nomenclature, such as: Occupancy classification is not listed in NFPA nomenclature, such as: –Healthcare occupancy –Business occupancy –Ambulatory healthcare occupancy Type I (443)Type I (332)Type II (222)Type II (111)Type II (000) Type III (211)Type III (200)Type IV (2HH)Type V (111)Type V (000)

Top 10 Life Safety Findings It appears that un-qualified people are completing the FDR… This is a document that should be completed by an engineer, architect, or someone with adequate knowledge of the NFPA codes and standards, and your facility. HFAP does not accept IBC nomenclature in lieu of NFPA nomenclature.

Top 10 Life Safety Findings Number 5: Fire Alarm System - Testing –HFAP requires testing of the fire alarm system to comply with the NFPA standard. This means all devices are tested in accordance with Table in NFPA

Top 10 Life Safety Findings Interface relays are often overlooked and not accounted for by the fire alarm testing contractor. They are usually mounted above the ceiling and are out of sight and therefore, out of mind. Their purpose is to connect other systems to the fire alarm system.

Top 10 Life Safety Findings Every device on the fire alarm system (and any other feature of life safety) must be inventoried as to their location and whether or not the ‘Passed’ or ‘Failed’ their test. The report must be signed by the service technician and must identify the NFPA standard and edition used during the test (hint: NFPA )

Top 10 Life Safety Findings Number 6: Fire Rated Door Assemblies –Issues with doors that are required to be fire rated, do not qualify as such.

Top 10 Life Safety Findings The labels on fire-rated doors cannot be covered by paint, hinges, or other means.

Top 10 Life Safety Findings Either the door or the frame is not labeled in a fire- rated barrier.

Top 10 Life Safety Findings Number 7: Generator Inspection –The NFPA , requirement is weekly inspections of the generator will be conducted. Surveyors are finding that either the hospitals are not doing this weekly inspection, or they are not doing it correctly.

Top 10 Life Safety Findings Hospitals are not recording the electrolyte levels (specific gravity) on generator batteries. Refractometer Hydrometer

Top 10 Life Safety Findings Sealed lead acid batteries: We have reports that some state agencies surveying on behalf of CMS do not permit them, but HFAP will, provided a conductive test is performed in lieu of recording the electrolyte levels.

Top 10 Life Safety Findings Number 8: Doors –Doors are required to function properly. Surveyors are finding multiple issues with doors, concerning their ability to latch, fully open, and obstructions created by the door swing.

Top 10 Life Safety Findings Surveyors often find corridor doors that do not latch, due to staff disabling the latching mechanism

Top 10 Life Safety Findings Often times, doors will be observed that do not open fully (at least 90 degrees)

Top 10 Life Safety Findings Surveyors will cite a door that obstructs more than ½ the width of the corridor / aisle / stairwell landing while the door is being opened.

Top 10 Life Safety Findings Number 9: Life Safety Drawings –Drawings of your rated wall system are critical to proper maintenance. They are imperative to properly assessing your facility for compliance with the Life Safety Code. –If you provide the surveyor with incorrect or poor drawings, it will affect the outcome of your survey.

Top 10 Life Safety Findings Surveyors often find that the Life Safety drawings do not include all of the required features: –Rated walls and barriers; –Smoke compartment boundaries and total area; –Travel distances to smoke barriers and to exits; –Suite boundaries and total area; –Exits, exit enclosures, horizontal exits, exit discharges; –Hazardous rooms; –Smoke partitions, such as non-rated corridor walls and hazardous areas.

32 Life Safety drawings (such as this sample) need to include all of these requirements….

Top 10 Life Safety Findings Number 10: Door Locks –Doors in the path of egress are not permitted to be locked, with the following exceptions: Clinical needs locks Delayed egress locks Access-control locks –Surveyors will cite the organization if they do not comply with these exceptions

Top 10 Life Safety Findings Doors in the path of egress may be locked where the clinical needs of the patients require specialized security measures for their safety. This is interpreted for behavioral health units, such as psychiatric units and Alzheimer’s units. These types of locks are not permitted for infant security, or any other purpose.

Top 10 Life Safety Findings Delayed egress locks are permitted, but only in buildings fully protected with sprinklers or fully protected with smoke detectors. Common deficiencies cited by the surveyors are for delayed egress locks in buildings that are neither fully smoke detected or sprinklered.

Top 10 Life Safety Findings Another frequent citing is a delayed egress lock without the proper signage with 1 inch tall lettering that says: “PUSH UNTIL ALARM SOUNDS DOOR CAN BE OPENED IN 15 SECONDS”

Top 10 Life Safety Findings Access-control locks are a misnomer… they are not locks in the path of egress. They are required to have a motion sensor on the egress side that detects a person approaching and automatically unlocks the door.

Top 10 Life Safety Findings They are also required to have a “Push to Exit” button mounted on the wall of the egress side, within 5 feet of the door, that unlocks the door when depressed. Frequent findings by surveyors identify hospitals that do not have one or the other, or neither.

Top 10 Life Safety Findings So… it’s important to understand that doors in the path of egress cannot be locked, unless they meet the prior exceptions. If cited, it will be an automatic Condition Level Deficiency (aka known as a CoP out), and if the door is an actual exit (i.e. a door to the exterior or a door to a stairwell) it will likely be an Immediate Jeopardy decision.

Top 10 Life Safety Findings There is a CMS categorical waiver (see S&C memo 13-58) that allows hospitals to use section of the 2012 Life Safety Code, for special locking arrangements to lock doors for infant security (and ICU and ER doors as well) provided they meet the requirements: –Building must be fully sprinklered –The locked area must be fully smoke detected –Staff must be able to unlock the doors at all times.

Transition… So those are the top-ten findings by surveyors for Life Safety. Now let’s transition to the common problems found during the document review session….

The Most Common Problems With the Document Review Session The most common problems with the fire alarm test report, are: Not all of the required testing is performed, most often the interface devices and occupant notification devices The testing company does not provide a list of locations for all items tested, and whether or not they passed or failed their test The hospital frequently does not read the test report and therefore does not act on deficiencies identified in the report

The Most Common Problems With the Document Review Session The most common problems with the fire pump test report, are: The weekly fire pump tests are not always conducted each week The annual waterflow test is not always conducted at peak capacity (150% of nameplate capacity) The annual waterflow test is not always conducted under emergency power at peak capacity (electric pumps only)

The Most Common Problems With the Document Review Session The most common problems with the sprinkler test and inspection report, are: Not all sprinklers and associated piping are inspected on an annual basis, or the documentation is not clear Not all sprinklers are cleaned when dust and dirt accumulate on them Main drain tests are not conducted at the system risers Check valves are not inspected internally (5-Year) Pressure gauges are not calibrated or replaced (5-Year)

The Most Common Problems With the Document Review Session The most common problems with the fire extinguisher test and inspection report, are: Not all fire extinguishers are inspected monthly Not all fire extinguishers have their annual maintenance within the + 30 day window Fire extinguishers are required to be mounted, or placed in cabinets, at least 4 inches above the floor and no more than 60 inches above the floor

The Most Common Problems With the Document Review Session The most common problems with the Alternative Life Safety Measures (ALSM) policy, are: The policy is based on old standards and is not kept up to date The policy does not contain written criteria for evaluating when and to what extent the hospital follows special measures to compensate for increased risk to life safety

The Most Common Problems With the Document Review Session The most common problems with the fire damper test reports, are: The report does not adequately identify the location of each fire damper The organization fails to implement ALSMs for deficient fire dampers The organization fails to meet the 6-Year window for testing

The Most Common Problems With the Document Review Session A comment about fire dampers: You are required to test all dampers, regardless if they are accessible or inaccessible. If they are inaccessible, then they must be made accessible and retested. There is no NFPA code or standard that allows inaccessible dampers to remain inaccessible and not be tested.

The Most Common Problems With the Document Review Session The most common problems with the overhead rolling fire door test reports, are: The report does not identify the location of each overhead rolling fire door The organization fails to act on deficiencies identified in the report, including ALSMs

The Most Common Problems With the Document Review Session The most common problems with the emergency power generator test reports, are: The generators are not load tested within the 20 – 40 day window each month (still required by HFAP and CMS) The monthly load test does not meet the 30% nameplate rating capacity The annual and 3-Year load tests are not conducted at the appropriate load capacities and within the time required

The Most Common Problems With the Document Review Session The most common problems with battery powered emergency light testing, are: The emergency lights are not tested for 30 seconds every month The emergency lights are not tested for 90 minutes once per year

The Most Common Problems With the Document Review Session The most common problems with medical gas test reports, are: The medical gas alarm panel is not tested according to the hospital’s policy on frequency The purity of the medical gas is not tested after modifications have been made to the system

QUESTIONS 53 |

Want to ask Questions later? Contact Brad Keyes at: Or, please submit questions to:

Certificate of Attendance ___________________________ Awarded 1.0 contact hours Life Safety Compliance: Most Common Surveyor Findings A 60 minute audio-conference April 28, 2016 _________________ Brad Keyes, Presenter HFAP Engineering Advisor