Grounded Wye-Delta Transformer Bank Backfeed Short-Circuit Currents W. H. Kersting & Wayne Carr Milsoft Utility Solutions
Introduction Wye-Delta Transformer Bank – Serving a three-phase load A three-phase transformer Or three single-phase transformers – Serving single-phase and three-phase loads One centered tapped lighting transformer Two power transformers Question: To ground or not to ground the Wye connection.
Wye-Delta Transformer Connection
Ungrounded Wye-Delta Transformer Bank
Grounded Wye-Delta Transformer Bank
So What? Ungrounded Y-D – No backfeed short circuit current – Lose one phase and bank becomes single-phase Grounded Y-D – Backfeed current possible – Lose one phase and have open Y-D bank – Need to compute all short circuit currents for A-G fault
Test System Used to Compute Backfeed SC Currents for Grounded Y-D Bank
Overhead Lines
Overhead Line Phase Impedances
Methods of Analysis Symmetrical Components – Old fashion way to demonstrate backfeed Basic circuit and transformer analysis – Analysis of total three-phase circuit Reduced 8x8 matrix analysis – Reduce total analysis to just what is needed
Symmetrical Component Method
Overhead Line Sequence Impedances
Sequence Networks Connection Phase a-g Fault at Node 12
The Minus 3 Error Doc. Crosno (NMSU) was a stickler for accurate calculations when I was a student When he found an error it was an automatic -3 error (red rubber stamp) out of 10 points on the problem When I was preparing for this presentation I found a -3 error on the symmetrical component analysis. I used transformer impedance referred to secondary rather than primary side. Please ignore the results in the paper
Correct Sequence Network Analysis Results
Now What? The symmetrical component method has demonstrated – There is a backfeed current of amps/phase – This method assumes a balanced three-phase system (ignored the off diagonal terms of the sequence impedance matrix) Need to evaluate the short circuit currents with a total unbalanced three-phase system
Unbalanced Three-Phase System
Observations to Note
A-G Fault at Node 12
A-G Fault at Node 12 Results
Reduced Three-Phase Circuit Analysis Primary concern – Currents in the fault – Currents from the source – Backfeed currents from the transformer bank Recognize the three backfeed currents are equal Apply basic algebra to reduce to 8 equations and 8 unknowns
Reduced Analysis 8x8 Matrix
8x8 Matrix for A-G Fault at Node 12
8x8 Matrix Results
Comparisons of Results
WindMil Results Using Loop Flow Method
Ungrounded Wye-Delta Connection Analysis methods – 7x7 matrix – Set Zg = Results
Short Circuit Current vs. Rated Current Transformer Rated Currents – 100 kVA: 13.8 amps – 50 kVA: 6.9 amps With Zg = 5 ohms backfeed = 91.7 amps – 100 kVA: 564% over rated current – 50 kVA: 1,229% over rated current With Zg = 50 ohms backfeed = 19.3 amps – 100 kVA: 39.9% over rated current – 50 kVA: 79.9 % over rated current
Short Circuit Protection
Substation Transformer Primary Fuses Primary responsibility is to open on transformer faults Backup responsibility to open if low side breaker fails to open for downstream fault Transformer fuse must lie between inrush current and maximum melt curves
Primary A-G Short Circuit Current
Substation Transformer Fuses
Primary Fuse Curves Referred to Secondary for LG Fault
Primary Curves Referred to Secondary For LG Fault
Recloser and Xfm Fuses
Total Protection
Three Downstream Transformers 8x8 equivalent matrix method of analysis doesn’t work Symmetrical component model developed and analysis run WindMil using the loop flow method was developed and analysis run Symmetrical components and loop flow methods match very closely
Three Downstream Transformers WindMil Solution
Summary Grounded Wye-Delta Short Circuit Analysis – Symmetrical Components – Exact Circuit Analysis – Reduced Circuit Analysis Ungrounded Wye-Delta Short Circuit Analysis Short Circuit Protection – Primary Fuses – Recloser – Distribution Transformer Fuses
Conclusions Grounded wye-delta transformer banks provide backfeed currents for upstream faults involving ground Ungrounded wye-delta does not provide backfeed currents Backfeed currents can blow transformer fuses for upstream ground faults