Elbow Sound Attenuator (UPC-26C) Outlet (UPC-56B) Plenum Supply Tubing (UPC-25) Blower Modules (2430,3642, 4860) Heating Module (MH2430, MH3660) Cooling Modules (MC2430, MC3642, MC4860) Return Air Adapter (UPC- 59-xxxx) Sound Attenuator (UPC-26C) Secondary Drain Pan Return Air Duct (UPC-04-xxxx) Return Air Box (UPC-01-xxxx)
Unico vs. Conventional Ducted Systems Roughly half the CFM ( vs. 400) High Static Pressure (Avg. 1.5” w.c.) Refrigeration Coil vs. A/C Coil Greater Temp. Drop in AC 1000 to 2000 fpm velocity Aspiration vs. Diffusion and Throw and Return
THREE BIG DIFFERENCES 1. Airflow 2. Aspiration 3. Static Regain
Unico vs. Conventional Roughly half the CFM ( vs. 400) Refrigeration Coil vs. A/C Coil Greater Temp. Drop in AC Warmer Temperatures in Heat Pump
Lower Airflow & 6 Row Coil Removes 30% More Moisture
Higher Discharge Temperature No Need for Electric Heat to Feel Warm 122°F (50°C) Discharge Air Temp At 47° Rating Point Eliminates Cold Blow Complaints
Unico vs. Conventional High Static Pressure (1.5” w.c.)* High Velocity ( fpm) *NOT consider high static pressure by ASHRAE Ratings
Much Higher Discharge Velocity
Aspiration Diffusion, Throw, Return
Small Space Savings
Smaller Supply Outlets
Any Condensing Unit
SDHV classification
Ratings AHRI Ratings In AHRI Directory Under “SDHV”
Energy Efficiency Differences SDHVConventional Thermal losses4%8% Duct leakage<5%15-20% Duct efficiency*>80%50% System efficiency, Btuh/W (SEER x duct efficiency) * Based on ASHRAE Standard 152