TAN DELTA TEST FOR POWER TRANSFORMERS

Slides:



Advertisements
Similar presentations
An Electronic Device, and also a Action Hero…
Advertisements

EZCT TURNS RATIO TEST The EZCT’s use the “Voltage Method” to determine the CT Turns ratio The ideal connection is shown in this illustration.
Advanced Power Protection Lecture No.2
Which type of circuit has more than one path for electricity to flow?
Department of Electrical and Computer Engineering EE18B.
TRANSFORMERS. TRANSFORMER PARAMETERS Turns Ratio (n) It is defined as the ratio of the number of turns in the secondary winding (N sec ) to the number.
Parallel Circuit electricity has more than one path to follow total amps are equal to the sum of the individual amps total watts are equal to the sum of.
Transformer Construction
Unit 27 Three-Phase Circuits
NEW TOOLS FOR DIAGNOSTIC MEASUREMENTS ON ELECTICAL ROTATING MACHINES
Chapter 2 Transformers.
FOWLER CHAPTER 9 LECTURE 9 POWER IN AC CIRCUITS. POWER IN RESISTIVE CIRCUITS, CHAP 9 WITH A RESISTIVE LOAD, CURRENT AND VOLTAGE ARE IN PHASE. F.9.1 THIS.
1.6 Real Single-Phase Transformer.
Transformer.
Four identical resistors, P, Q, R and S are connected as shown. In which of the resistors is the current the same? 1.P and Q only 2.R and S only 3.P, R.
34.11 Electric Power Electric power is equal to the product of current and voltage.
Transformer Taking the ratio of the two equations
ON LINE TRANSFORMER OIL REGENERATION PROCESS OF GT-8
Power and Power Measurement ENGR 10 – Intro to Engineering College of Engineering San Jose State University (Ping Hsu and Ken Youssefi) 1 Introduction.
4.2.3B Electrical Power What About Watts?. Power Law Moving electrons (current) requires ENERGY How much energy gets used depends on: Strength of push.
DIAGNOSIS AND FAULT FINDING ON POWER TRANSFORMERS
EXAMPLE A pole mounted 100kVA distribution transformer has the following characteristics R 1 = 1.56  R 2 =  X 1 = 4.66  X 2 =  Volts Ratio.
Transformer Protection Over-current protection in the form of fuses may be the only protection provided to a small 100 kVA, 11 kV/440 V distribution transformer.
Transformer condition assessment with an integrated test van
Electronic Report Pigi. HV-LV-ADC status Sometimes “repaired boards” are not working properly and so I would like to propose you to: – Test and qualify.
General power system. objective Review general energy and power system Application of fundamental knowledge of principal machines, transformer and other.
Current flow versus Electron flow Conventional current flows this way. Electrons flow this way.
Transformer Current & Voltage Practice
Per-Unit System.
EE 740 Professor Ali Keyhani Lecture #6 Load-Tap-Change Transformer (LTC)
Series Circuit Measurements Be Accurate, Be Safe By David Rainey Navaid Lighting Associates, Inc.
Instrument Transformer Electrical Measuring Instruments & Instrumentation 3rd SEMESTER ELECTRICAL ENGG.
D.C. Machine & Transformer Topic: Instrument Transformer Electrical:-1 presented by: Jill Chauhan ( ) Chirag Agarawal ( )
IDAX 300 Insulation Diagnostic Analyzer Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy.
Gandhinagar Institute of Technology
Advanced Meter School August 18-20, 2015 INSTRUMENT TRANSFORMER SIZING 2015 David L. Johnson.
Outage of Generator Transformer due to High DGA. BRIEF HISTORY 200 MVA 400 kV GT erected at site. After satisfactory pre-commissioning checks GT was successfully.
Current Transformer Testing
ET 332b Ac Motors, Generators and Power Systems 1 Lesson 11_et332b.pptx.
ELECTROTECHNIC. LARGE RANGE OF ROTARY MACHINES AND ACCESSORIES Educational equipment & solutions for technical training institutes & Universities 90W.
Electronics Technology Fundamentals Chapter 10 Inductors.
TESTING AND MAINTENANCE OF POWER TRANSFORMER
Doble Power Factor Bushing Test
Series Circuit Measurements Be Accurate, Be Safe
PS 1 – Transformer Protection, Monitoring & Control
Chapter 11 AC Power Analysis
WELCOME.
Testing of Transformers
The Step by Step Charging Techniques
DC MACHINE AND tRANSFORMER
MANUFACTURING PROCESS OF TRANSFORMERS
CIGRE SC B5 COLLOQUIUM CALGARY
Per-Unit System.
Induction motor control
A presentation on Measurement of Winding Resistance and Insulation Resistance of 3 Phase 11 kV/ 433 V, 16KVA Oil cooled type Transformer PRESENTED BY:
Open circuit Test and Short circuit Test
ELE 2103 Dept . of E & E, MIT Manipal
المحولات Transformers
Φ 3. Transformer Models. Turns ratio 7200:240 (30 : 1)
EZCT TURNS RATIO TEST The EZCT’s use the “Voltage Method” to determine the CT Turns ratio The ideal connection is shown in this illustration.
CONSTRUCTION of TRANSFORMERS
Transformer Impedance
Basic Electrical Calculations
CHAPTER 3 INSULATION TEST OF POWER SYSTEM EQUIPMENT
COMPLEX POWER The units of apparent and reactive power are Volt-Ampere
Wye/Wye 277/480 4 wire Transformer Bank
Notes 7.3 : Calculating Electric Power + Electrical Energy
C H A P T E R 20 Harmonics. C H A P T E R 20 Harmonics.
Electrical components and systems
E E 2415 Lecture 9 Phasor Circuit Analysis, Effective Value and Complex Power: Watts, VAR’s and Volt-Amperes.
Presentation transcript:

TAN DELTA TEST FOR POWER TRANSFORMERS

TAN DELTA(INSULATION DISSIPATION FACTOR) Tan delta is the insulation power factor & is equal to the ratio of power dissipated in the insulation in watts to the product of effective voltage & current in volt ampere when tested under sinusoidal voltage.

PROCEDURE All windings immersed in insulating liquid. All windings shortcircuited using bare braided jumper such that jumper shall not be allowed to sag. All bushings in place. Temperature of winding & insulation liquid near to the reference temperature(27 degree). All bushings cleaned properly. Transformer earthed properly.

Neutral,star point of 3 phase winding connected to other bushing of that winding by means of short jumper. Tan delta is then tested between below combinations, a. HV to EARTH b. LV to EARTH c. HV to LV.

TEST SETUP TRANSFORMER SPECIFICATONS RATING-100 MVA VOLTAGE CLASS-33KV/220KV Yyn-0 COOLING-OFAF INSTRUMENT MAKE-OMICRON APPLIED VOLTAGE-10KV

LV TO EARTH TESTING

HV TO EARTH TESTING

LV-HV TESTING

TAN-DELTA TEST RESULTS WINDING TAN-DELTA LV TO EARTH 0.4702 HV TO EARTH 0.4983 LV TO HV 0.2616