BASIC ELECTRICITY AND MAGNETISM

Slides:



Advertisements
Similar presentations
Electricity in the Home
Advertisements

Schematics On or off Batteries Series or Parallel Volts and Amps FJ
E1 – Electrical Fundamentals
Thermostats, Pressure Switches, and Other Electric Control Devices
Thermostats. I would recommend that as you proceed through this power point presentation that you refer to your textbook, Unit 14, for some great visuals.
HVAC Commercial Ref.
Air-Conditioning Control Systems
Contactor, Relays and Overloads
Section 4: Electric Motors
Reading Electrical Schematics
TEST METER OPERATION. Electrical Test Instruments Analog Or Digital Voltmeters – Measuring Potential Difference Ammeters – Measuring Current Flow – Clamp.
Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams
SECTION 4 ELECTRIC MOTORS UNIT 19 MOTOR CONTROLS.
Electrical Measurements: Meters
Section 4: Electric Motors
E2 Motors and Motor Starting
Electrical Electricity Fuses Relays Solenoids Electrical Testing
1 HVAC214 – Electrical for Oil Fan Centers. 2 Designed to provide low voltage control of blower motors and auxiliary circuits. Provide a good junction.
1 HVAC 214 Electricity For Oil Heat Fan Center Relays.
Troubleshooting Electric Control Devices
7.2.4 Student Book © 2005 Propane Education & Research CouncilPage Identifying Procedures for Measuring Current Between Two Given Points in an.
 Four Components of a circuit  Power supply  Conductor  Load device  Controlling device  Power Supply  Generator  Line source (wall outlet)  Transformer.
Electric Circuits A circuit is a path where a current can flow If the flow is to be continuous, the can be no gaps in the path Introduce gaps in the form.
Electrical Power Systems
7.1.3 Student Book © 2005 Propane Education & Research CouncilPage Applying a Systems Approach to Gas Appliance Troubleshooting Troubleshooting.
Air Handler Terminology
Physics I Honors 1 Current and Circuits Circuits Schematics Use of Meters.
Electricity & Magnetism Chapter 19 and 20 Review for Test April 19, 2005.
Operation Sabbath Mode - SELECT PROGRAM - Lights, alarms and fans Normal Sabbath Overview.
Charge and Current: More Practice. A Review of Circuits: Student Learning Goal The student will be able to construct and then compare and contrast.
1 Basic Electrical Series and Parallel Circuits. 2 Introduction So far we have looked at circuits that have one path for electricity to go as well as.
G1 Supplemental Questions
E1 – Electrical Fundamentals
Concepts of Engineering and Technology Basic Electricity and Electronics: DC Circuits Copyright © Texas Education Agency, All rights reserved. 1.
Control Systems: Circuitry Electricity for Refrigeration, Heating and Air Conditioning 7th Edition Chapter 16 Control Systems: Circuitry and Troubleshooting.
Electricity. TYPES OF CIRCUITS Individual electrical circuits normally combine one or more resistance or load devices. The design of the automotive electrical.
AIR CONDITIONING (COOLING)
AIR CONDITIONING (COOLING)
TROUBLESHOOTING ELECTRIC MOTORS
Push Button Station and Relay
E3 HVACR Controls and Devices
E1 – Electrical Fundamentals
“Electrical Fundamentals”
E1 – Electrical Fundamentals
Section 6: Air-Conditioning (Heating And Humidification)
© 2004 Refrigeration Training Services - Refrigeration Categories v1.1
E2 Motors and Motor Starting
Aim: How is a Series Circuit different from a Parallel Circuit?
E3 HVACR Controls and Devices
E2 Motors and Motor Starting
E2 Motors and Motor Starting
Workbook Section.
SERIES AND PARALLEL CIRCUITS
TROUBLESHOOTING ELECTRIC MOTORS
Series and parallel circuits
8.2 Electric Current.
Current Electricity and Electric Circuits
HVAC Schematic Symbols
LOAD CONTROLLERS & LOADS.
Presentation transcript:

BASIC ELECTRICITY AND MAGNETISM SECTION 3 BASIC ELECTRICITY AND MAGNETISM UNIT 15: TROUBLESHOOTING BASIC CONTROLS

UNIT OBJECTIVES After studying this unit, the reader should be able to Describe and identify power passing and power consuming devices Describe how a voltmeter is used to troubleshoot electrical circuits Identify typical problems that arise in electrical circuits Describe how an ammeter is used to troubleshoot electrical circuits Recognize the electrical components of a heating/cooling system Describe the sequence of operations of a heating/cooling system Describe pictorial and line-type electrical wiring diagrams

INTRODUCTION TO TROUBLESHOOTING Recognize the control and its purpose in the system Controls are either electrical, mechanical or both Electrical devices Power consuming devices use power Example of a power consuming device: a light bulb Power passing devices pass power to the power consuming devices without consuming power themselves (ideally) Example of a power passing device: a switch

Power-consuming device Power-passing device Power-consuming device 115V

HOT NEUTRAL 115V Meter Switch 115V Meter Fuse 115V Meter T-stat (open) 0V Meter Bulb not lit

TROUBLESHOOTING COMPLEX CIRCUITS Check the thermostat 0 volts from R to W when there is a call for heat The coil of the heating relay should be energized Check the fan circuit 0 volts from R to G when the fan relay coil is energized Check the cooling circuit The Y terminal controls the cooling circuit 0 volts from R to Y when there is a call for cooling

Terminal block in air handler Thermostat wire R C G W Y To cooling contactor coil From heating, fan and cooling coils To heating relay Secondary Primary To fan relay Transformer

Zero volts from R to G when fan relay is energized Terminal block in air handler Thermostat wire R C G W Y Secondary 0V Primary Zero volts from R to G when fan relay is energized

Zero volts from R to W when heat relay is energized Terminal block in air handler Thermostat wire R C G W Y Secondary 0V Primary Zero volts from R to W when heat relay is energized

Zero volts from R to Y when cooling coil is energized Terminal block in air handler Thermostat wire R C G W Y Secondary 0V Primary Zero volts from R to Y when cooling coil is energized

TROUBLESHOOTING THE THERMOSTAT Control voltage must be present in order for the thermostat to operate Turn the fan switch to the ON position to see if the fan begins to operate If the fan comes on, there is low voltage present If the fan does not operate there may be a low voltage problem Check voltage supplied to the transformer primary Check voltage at the transformer secondary

Thermostat Fan switch FAN AUTO ON HEAT OFF COOL When switched to the “ON” position, the indoor blower should operate if there is low voltage present

TROUBLESHOOTING THE THERMOSTAT The thermostat can be removed from the subbase Install an insulated jumper between R and G (The fan should come on) Install an insulated jumper between R and W (The heat should come on) Install an insulated jumper between R and Y (The cooling should come on) If the circuits operate with the jumpers and not with the thermostat, the thermostat is defective

Line Voltage R G Fan circuit W Heating circuit Y Cooling circuit Insulated jumper Thermostat subbase

TROUBLESHOOTING THE THERMOSTAT On a call for heat, power is passed through the thermostat to the heating relays On electric heating systems, the fan will also be energized on a call for heat On a call for cooling, the following system components are controlled Compressor Condenser fan motor Evaporator fan motor

TROUBLESHOOTING THE THERMOSTAT The compressor and condenser fan motor are wired in parallel with each other Controlled by the Y terminal on the thermostat The Y terminal passes power to the contactor coil Contacts close and energize the compressor and condenser fan The indoor fan will operate continuously when the fan switch is in the ON position The indoor fan will operate only when the compressor is operating when the fan switch is in the AUTO position

TROUBLESHOOTING AMPERAGE IN LOW-VOLTAGE CIRCUITS Transformers are rated in volt-amperes, VA VA rating can be used to determine if the control circuit is drawing too much current Maximum amperage = VA rating/secondary voltage A 40 VA transformer with a secondary voltage can handle a maximum current of 1.67 amps Maximum amperage = 40/24 = 1.67

TROUBLESHOOTING AMPERAGE IN LOW-VOLTAGE CIRCUITS Using a clamp-on ammeter Coil a jumper wire around the jaws of the meter ten times Place the jumper is series with the circuit being checked Divide the ammeter reading by ten Actual circuit amperage should be lower than the calculated maximum circuit amperage Electronic clamp-on meters can often be used without using the 10-wrap method

Line Voltage R G Fan circuit W Heating circuit 7.0 amps Y Cooling circuit Actual amperage = 7/10 = 0.7 amps

TROUBLESHOOTING VOLTAGE IN THE LOW-VOLTAGE CIRCUIT Power consuming devices need to have the proper voltage supplied to them If a relay’s holding coil is rated at 24 volts, there should be 24 volts applied to the coil If there is a reading of zero volts across the coil, the problem is likely not the coil If there is a reading of 24 volts across the coil and the relay contacts do not switch position, the coil is defective and the relay should be replaced

GENERAL PURPOSE RELAY 24-volt coil Normally closed contacts Normally open contacts Relay

RELAY – NORMAL OPERATION 24-volt coil Coil energized Normally closed contacts are now in the open position Current flows through closed contacts Normally open contacts are now in the closed position Relay

RELAY – DEFECTIVE COIL - CONTACTS DO NOT CHANGE POSITION Voltage applied to the coil 24-volt coil Current flows through closed contacts Normally closed contacts remain closed Normally open contacts remain open Relay

TROUBLESHOOTING VOLTAGE IN THE LOW-VOLTAGE CIRCUIT Thermostats can be removed from the subbase to check the low voltage circuits There should be a reading of 24 volts between the R (hot) terminal and the Y (cooling) terminal There should be a reading of 24 volts between the R (hot) terminal and the W (heating) terminal There should be a reading of 24 volts between the R (hot) terminal and the G (indoor fan) terminal

Line Voltage R 24V G Fan circuit 24V W Heating circuit Y Cooling circuit 24V Thermostat subbase

TROUBLESHOOTING ELECTRICAL SWITCHES AND LOADS Switches are wired in series with power-consuming devices (light switch in series with a light bulb) When switches are wired in series with a load, all of the switches must be closed for the load to operate Switches in parallel provide alternative control sequences for the load If there is line voltage supplied to the circuit, there will be line voltage across an open switch

LINE VOLTAGE READING ACROSS THE OPEN SWITCH

BOTH SWITCHES MUST BE CLOSED FOR LOAD TO BECOME ENERGIZED 115V

BOTH SWITCHES MUST BE CLOSED FOR LOAD TO BECOME ENERGIZED 115V

BOTH SWITCHES MUST BE CLOSED FOR LOAD TO BECOME ENERGIZED 115V

SWITCHES IN PARALLEL PROVIDE ALTERNATIVE CONTROL PATHS

SWITCHES IN PARALLEL PROVIDE ALTERNATIVE CONTROL PATHS

SWITCHES IN PARALLEL PROVIDE ALTERNATIVE CONTROL PATHS

SWITCHES IN PARALLEL PROVIDE ALTERNATIVE CONTROL PATHS

SWITCHES IN PARALLEL PROVIDE ALTERNATIVE CONTROL PATHS

TROUBLESHOOTING ELECTRICAL SWITCHES AND LOADS There will 0 volts across a closed switch The voltage reading across the windings of a de-energized motor will be 0 volts An ohmmeter can be used to check switches and loads if all power and wires are disconnected Infinite resistance reading indicates an open circuit Never use an ohmmeter on energized circuits

READING OF ZERO VOLTS ACROSS THE CLOSED SWITCH

PICTORIAL WIRING DIAGRAMS Schematic diagram Used to show the location of circuit components Diagram configured to show the circuits as they are seen in the actual unit Wires are color coded in the diagram to make wire identification easier All wires and connections are included

PICTORIAL DIAGRAM (SIMPLIFIED) RED BK TRANS BK BL P1 S1 S2 L1 LIM1 LIM2 L2 COM Hi Lo G2 P2 6 5 4 3 2 1 G3 G1 C 1 2 3 4 C Y Gc Gh R W GRN Gas

LINE DIAGRAMS Used to follow the logic of the circuit Shows circuits and component functions Easier to use in the troubleshooting process as each circuit is on a separate line (ladder diagram) Lines representing the power supply are located on the left and right sides as vertical lines Power passing and power consuming devices are located on horizontal lines between the power lines The right side of the diagram often has no switches

SIMPLIFIED LADDER (LINE) DIAGRAM Load

UNIT SUMMARY - 1 Recognize each control and its purpose in the circuit Electric components can be power consuming or power passing devices A measurable voltage reading across a switch indicates that the switch is in the open position A reading of zero volts across a switch in an energized circuit indicates that the switch is in the closed position The thermostat can be evaluated by removing it from the subbase Jumper wires at the subbase can be used to check the individual circuits Control voltage must be present in order for the system to operate

UNIT SUMMARY - 2 If the system does not operate, the voltage at the primary and secondary of the transformer should be checked The indoor fan motor will operate if the fan switch is turned to the ON position The indoor fan motor will cycle on and off with the compressor (in the cooling mode) when the fan switch is turned to the AUTO position Max. control circuit amps = VA rating/secondary voltage Control circuit amperage is measured with an ammeter Power consuming devices must be supplied the proper voltage

UNIT SUMMARY - 3 If proper voltage is supplied to a component and it fails to operate, the component should be evaluated Switches are wired in series with the power consuming device in the circuit Multiple switches can be wired in series Switches in parallel provide alternate control sequences Pictorial diagrams show component locations, color-coded wires, and all electrical connections Line or ladder diagrams show each circuit on a separate line and make the troubleshooting process easier