Machine Protection Requirements and Concept Annika Nordt et al. European Spallation Source ERIC Machine Protection Review, December 2015 Lund, Sweden.

Slides:



Advertisements
Similar presentations
André Augustinus 15 March 2003 DCS Workshop Safety Interlocks.
Advertisements

ESS Timing System Plans and Requirements Timo Korhonen Chief Engineer, Integrated Control System Division May 19, 2014.
Concept & architecture of the machine protection systems for FCC
SNS Integrated Control System SNS Machine Protection System EPICS Workshop April 27, 2005 Coles Sibley.
Systems Engineering Approach to MPS Risk Management Kelly Mahoney Presented at the Workshop for Machine Protection in Linear Accelerators.
Safety Management of the LIU Project A. Funken Anne Funken, LIU PT 21/05/15.
© Palaniappan R Kannan PMP.,CFSE 1 IEC Standard – What is it? IEC is a Standard for the functional safety of Electric / Electronic / Programmable.
J. G. Weisend II Deputy Head of Accelerator Projects April 2, 2014 Actions at ACCSYS Resulting from the Recommendations of the Annual Review.
1 FRENCH PROPOSAL FOR ESARR6 1 - BACKGROUND - 15/02/00 : Kick-off meeting, Presentation of the CAA/SRG input (SW01), Request from the chairman to comment.
1 1. Some recent views ( ) 2 Linac tunnel
PLC Workshop at ITER, 4-5 th of December 2014 A. Nordt, ESS, Lund/Sweden.
This material is based upon work supported by the U.S. Department of Energy Office of Science under Cooperative Agreement DE-SC , the State of Michigan.
Preliminary Functional Analysis of ESS Superconducting Radio-Frequency Linac C. Darve, N. Elias, J. Fydrych, D. Piso European Spallation Source ESS AB,
Beam Interlock System Design H. Pavetits 1 PR a-HPA, June 27th, 2011.
LINAC4 COMMISSIONING 1 LESSONS LEARNT DURING MY VISIT AT LINAC4 COMMISSIONING Evangelia Vaena, 02/02/2016.
Beam Interlock System Technology Evaluation and Design MACS Week 1, 2011 Hannes Pavetits 1 R. Gutleber PR a-HPA, March 28 th, 2011 H. Pavetits.
LHC machine protection close-out 1 Close-out. LHC machine protection close-out 2 Introduction The problem is obvious: –Magnetic field increase only a.
Responses to recommendations of TAC 11 Integrated Control Systems Henrik Carling ESS/ICS Date:
Page Beam Instrumentation mini- workshop Conclusions from the Hardware, Timing and MPS mini-workshop Lund, Miha Reščič Deputy Head of
Personnel Safety Systems Stuart Birch Senior Engineer, Personnel Safety Systems November 6 th, 2014.
ESS Vacuum Standardization
Mitigation Devices External Interface ICS Nick Levchenko Lund Date:
Summary of Session 1 - CLIC MP workshop 6-8/6/2012, R.Schmidt 1.
Machine Protection Systems (MPS) Arden Warner, and Jim Steimel Project X Machine Advisory Committee March 18-19, 2013.
Maximum Credible Beam Loss in the Main Injector D. Capista January 26, 2012.
Accelerator Systems Integration Stephen Molloy Section Leader for Accelerator Integration April, 2016.
M. Munoz April 2, 2014 Beam Commissioning at ESS.
Design process of the Interlock Systems Patrice Nouvel - CERN / Institut National Polytechnique de Toulouse CLIC Workshop Accelerator / Parameters.
Integrated Control Systems Status and Plans Garry Trahern Head of ICS Division TAC 9, 3 rd April, 2014, ESS, Lund.
ESS Timing System Plans Timo Korhonen Chief Engineer, Integrated Control System Division Nov.27, 2014.
Reliability and Performance of the SNS Machine Protection System Doug Curry 2013.
GSI Helmholtzzentrum für Schwerionenforschung GmbH Fast Beam Abort FAIR FC2WG: M.S. Mandaković, CSCO
Introduction; Machine protection, experience and challenges: Review of existing solutions and challenges faced by future installations Purpose of machine.
PERSONAL SAFETY INTERLOCKS External EHS Expert Panel Workshop
Outcome of BI.DIS Fast Interlocks Peer Review
The TV Beam Observation system - BTV
R. Denz, A. Gomez Alonso, AT-MEL-PM
Dependability Requirements of the LBDS and their Design Implications
SNS Status Report Karen S. White 10/15/08.
STPA FOR LINAC4 AVAILABILITY REQUIREMENTS
Acknowledgments: LIU-PT members and deputies, H. Bartosik
LHCCWG Meeting R. Alemany, M. Lamont, S. Page
Interlocking of CNGS (and other high intensity beams) at the SPS
Tim Grow, CPA Charleston Office Managing Shareholder
Charge 2. Equipment Protection 3. Definition and Documentation
RF Local Protection System
BCM-BIS Interface Szandra Kövecses
TS2 PSS Architecture, Concepts of Operations and Interfaces
PSS0 Design & Concept of Operations
Testing Coordination at ESS
PSS verification and validation
MPS commissioning at ESS
PSS Verification and validation
Safety Analysis and Safety Functions
TSS System Requirements - TSS CDR1
(Beam) Commissioning Plan
Interlocking strategy
Safety Readiness Review (SRR) Thomas Hansson, ESH
Machine Protection PLC Based System Verification and Validation Plan
TS2 PSS; update on concepts of operation and system's architecture
Operation of Target Safety System (TSS)
Test Beamline System Requirements and Charge to PDR Committee
CDS-EL IRR Closeout 28 March 2019 J.G. Weisend II, Chairman.
TS2 PSS Software Requirements and Software Design
Mikael Olsson Control Engineer
Charge and Agenda of the 18th TAC meeting
ESHAC #8 Safety Readiness Review Thomas Hansson, ESH
Review of hardware commissioning
Close-out.
Management of Change GROUP HSE RULE (CR-GR-HSE-302)
Presentation transcript:

Machine Protection Requirements and Concept Annika Nordt et al. European Spallation Source ERIC Machine Protection Review, December 2015 Lund, Sweden

Overview 1.Transition from previous talks to this one 2.Damage Potential of the Proton Beam at ESS 3.Machine Protection Goals 4.Machine Protection General Requirements 5.Machine Protection SoS Architectural Framework 6.Summary 2

Transition from Previous Talks to This One So far we heard that: 1.A lot of equipment is built by in-kind partners, 2.Installation of accelerator equipment will start end of 2017, 3.First beam tests (front end) start right after that, 4.Hardly time for “cold” commissioning (without beam), 5.Ongoing commissioning and further installation during 2018 and 2019, 6.Ramp up to 680 MeV in a staged approach & be done by June 2019, 7.In short: Time allocated to commissioning is quite restricted, 8.But, the damage potential of the proton beam is higher in the lower energy part (warm linac) than in the cold linac, 9.Its enough to overlook 1 vacuum valve!  1 closed valve + inject beam  we start melting in a few μs!  would cause delay of project. 3

Damage Potential of the Proton Beam I Assuming worst case scenario: Proton beam impinging perpendicularly on copper or steel (3mm beam size). ics.atlassian.net/wiki/download/attachments/ /Time_Response_Requirements_BLM.pdf?version=1&modificationDate= &api=v2 Fastest reaction time required to stop proton beam is 4-5μs (within the first 50m). This includes detecting, processing and actual stopping of the proton beam. It’s a challenging task, requiring fast systems! 4

Damage Potential of the Proton Beam II But…Can it be worse??  YES ! Assuming 1 mm beam size, then melting starts in 1 μs Basically no “active” protection possible, thus we must rely on other “passive” ways to protect, and that is: A well orchestrated way of implementing machine protection relevant systems! 5

Machine Protection Goals Machine protection shall, in that order, prevent and mitigate damage to the machine, be it beam-induced or from any other source, in accordance with beam and facility related availability requirements. Machine protection shall protect the machine from unnecessary beam- induced activation having a potential to cause long-term damage to the machine or increase maintenance times, in accordance with beam and facility related availability requirements. 6

Machine Protection General Requirements I Machine protection shall: detect all off-nominal states that can lead to relevant damage to the machine. take all the necessary actions needed to, in that order, prevent and mitigate damage in case of detection of a relevant off-nominal state, including switching-off of the proton beam. detect all off-nominal states that can lead to relevant unwanted beam- induced activation. take all the necessary actions needed to, in that order, prevent and mitigate unwanted beam-induced activation in case of detection of a relevant off-nominal state, including switching-off of the proton beam. 7

Machine protection functions shall be implemented: with timing and protection integrity levels in accordance with damage risk reduction requirements. such that the probability of spurious trips is reduced in accordance with availability and damage risk reduction requirements. 8 Machine Protection General Requirements II

Machine Protection General Requirements III Machine protection shall: transmit all necessary information to the responsible staff allowing them to take adequate actions to resume facility operation within a minimum amount of time. record all information about detected off-nominal states and performed prevention and mitigation actions to allow for a-posteriori event reconstruction and analysis. support operation during all foreseen lifecycle phases of the machine, including, but not limited to assembly and installation, commissioning, tuning, operation, fault-finding, maintenance, and dismantling. 9

Machine Protection General Requirements IV Machine protection shall support: all foreseen operating modes of the machine, including but not limited to proton-beam up to intermediary targets, proton-beam with reduced beam power or alternative beam envelopes, and proton-beam with alternative duty cycles. operation in case of degraded mode of operation of equipment under control, if required for reaching the availability goals and if compatible with damage risk reduction requirements. operation in case of degraded protection functions, if required for reaching the availability goals, and still be compatible with damage risk reduction requirements. 10

Machine Protection SoS Architectural Framework Machine Protection has been recognized to be a System-of-Systems (SoS). It is composed of five classes of constituent systems: 1.Local MP-related systems located in the accelerator, the target station and the neutron science segment of the ESS facility, 1.MP-related proton beam monitoring systems, 1.Beam Interlock System, 1.MP-related beam switch-off actuation systems, 1.MP management systems. 11

Local MP Related Systems I The local MP-related systems located in the accelerator, target station and neutron science segments of ESS implement the needed local protection functions to: keep the local system protected from non-beam-induced damage, prevent beam from being switched on/injected to the linac or sent to the target if the local system is not ready to support beam operation, If a local damage risk gets detected, these local protection functions will result in a locally protected state for the affected system, If such an action has a potential to negatively influence the state of the proton beam, the local protection functions additionally trigger a switch-off of the proton beam. 12

Local MP Related Systems II If the local system is not ready to support beam production, the local protection functions will not permit beam. If other systems depends on the operation, then necessary actions will need to be taken to prevent damage to that other system. MP-related systems will implement a: LOCAL-PERMIT: state variable that is internal to the system and represents whether it is correctly functioning or an off-nominal state has been detected. BEAM-PERMIT: communicated to the Beam Interlock System and tells whether the system is in a state where beam production is safe. 13

Proton Beam Monitoring Systems MP related Proton Beam Monitoring Systems: The MP-related proton-beam monitoring systems detect any off-nominal states of the proton beam itself that might cause damage to or unnecessary activation of any equipment. The corresponding protection functions will trigger a switch-off of the proton beam by means of a BEAM-PERMIT signal transmitted to the Beam Interlock System. Beam Instrument Protection Systems: detect off-nominal states that might lead to damage to the beam instrumentation itself, detect states where the monitoring systems are not ready for beam 14

Beam Interlock System The Beam Interlock System evaluates the BEAM-PERMIT signals from all local MP- related systems and MP-related proton-beam monitoring systems. If required, the Beam Interlock System initiates the switch-off of the beam by triggering a set of MP-related beam switch-off actuation systems in a specific sequence, allowing for a painless recovery to normal operation. The BIS will verify the correct reaction of the actuation systems and, in case beam is not switched-off, an emergency sequence disregarding any recovery requirements will be triggered. After an interlock, beam production will only be allowed to resume once all BEAM- PERMIT input signals are in the expected state and all affected MP-related systems as well as the Beam Interlock System have been actively reset. 15

Actuators Timing System: Beam Pulse inhibit Proton pulse generation is controlled by the Timing System. Preventing the timing system from generating the events leading to a proton beam pulse would prevent proton beam from being injected and accelerated. Proton Source Switch-Off “Soft”: Prevent the proton source from injecting protons into the Linac (remove the RF signal from the magnetron) [100 μs until no plasma is created]. Proton Source Switch-Off “Hard”: Switch off the HV power to the proton supply using redundant contactors to prevent protons from being injected into the Linac [~500 ms]. LEBT Chopper Activation: Activate the LEBT Chopper to deflect the beam onto the LEBT dump [300] MEBT Chopper Activation: Activate the MEBT Chopper to deflect the beam onto the MEBT dump [10 ns]. 16

Further Requirements MP Event Logging and Diagnostics System collects logged data from all MP-SoS constituent systems and provides means to perform automated of manual event analysis for diagnostic purposes. As the ESS operating procedures might require an operator to acknowledge the event analysis result before beam injection is allowed to proceed, the performance of this system might have a large impact on beam availability. MP Operating Mode Configuration System sets and reads configuration data to and from all MP-SoS constituent systems. MP Status and Configuration Monitoring System performs online monitoring of the status and configuration of all MP-related systems. Configuration data include: the current operating mode, hard-, firm- and software identifiers. can request to switch the beam off in case it detects a problem. 17

Functional MP Architecture Concept

Functional Review of MP During this first day of the review we will try to walk you through this concept! There will be presentations related to the: Proton Beam Monitoring Systems (e.g. Beam Current Monitors, Beam Loss Monitors) Local MP Related Systems or Local Protection Systems (e.g. RF, Magnets, Interceptive devices) Actuator Systems (Proton Source, LEBT chopper) Please note: This review is NOT about those systems! And it does not cover all LPS, all actuator systems, etc. This first part of the review is about the concept of Machine Protection. 19

Summary 20 The challenge is not only to build a Beam Interlock System that is fast, reliable and highly available, but also to make sure all MP relevant systems connected to the BIS provide sufficient protection integrity. Completeness and traceability of requirements as well as standardized documentation of all systems relevant for Machine Protection is very important (and hard to achieve without awareness of the consequences).

BackUp Slides 21

These are the most stringent requirements in terms of response time and PIL level. Based on preliminary risk analysis (IEC61508, IEC61511) Example of a Protection Function 22

Governance of Machine Protection 23 MPC domain/ responsibilities: Approval of concept, overall scope, Coordination of hazard risk analysis, Approval of overall machine protection requirements, Coordination of machine protection requirements allocation. Stakeholder Requirements System Requirements Operations Accelerator Controls Target CF NSS PSS TSS - Requirements for Proton Source - Requirements for LEBT chopper - …. - Beam Interlock System - …. - Provide systems suitable for allocated machine protection functions -…. - Provide systems suitable for allocated machine protection functions, - Requirements on work procedures, checklists, training for personnel -… Provide run permit signal according to MP interface specification Specification of signal, cable, connector type - Provide systems suitable for machine protection functions, (Corresponding to analysis part of IEC61508) XY,… … Provide run permit signal according to MP interface specification Machine Protection Committee: Take on responsibility and take decisions