Title © Siemens Switzerland Ltd 2007 Big Plants with KNX - Topology - Devices - Planing, rules - Commissioning - Applications with heating/cooling-changeover
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 2October Topology (= Arealine 0)
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 3October Topology ACS Alarm, Pager, SMS, FAX N140/13 Area coupler RXB2.. RM..RMB.. RM.. RMB.. RMZ792 RM.. OZW775 Area 1Area 2Area 3 Arealine 0 (Backbone) N140/13 Line coupler Line 1 N140/13 Line coupler Line 1 N140/13 Line coupler Line 1 ACS Mainline 1 Mainline 2Mainline 3
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 4October Topology N140/13 Area coupler N140/13 Area coupler N140/13 Aera coupler RXB RXB RXB RM RM RRM RMB RM OZW Area 1 Area 7Area 15 Backbone 0 N140/13 Line coupler Line 1 N140/13 Line coupler Line 2 N140/13 Line coupler ACS RM RM RM RMB RM RM Line 15 RM RM RMZ Max. 64 Synco – Devices
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 5October System devices For more information see: Area-/Line coupler N140/13 5WG AB13 IP Router N146 5WG AB01 Bus power supply unit N125/x1 5WG ABx1
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 6October Bus power supply Central bus power supply unit (PSU): Decentral bus power supply (DPSU): Devices with no decentral bus power supply: For each line at least 1 bus power supply is required, either PSU or DPSU, however, never both of them together.
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 7October a Decentral bus power supply With decentral bus power supply (DPSU): Rules for designing the bus power supply with DPSU: Y = Devices with running decentral bus power supply DPSU X = Devices with no decentral bus power supply No decentral bus power supply: YX 1 „Y“ can supply 2 „X“ and 1 OCI700.1 and 1 OZW771 Don‘t use more than 8 „Y“ in one line! (also area line, main line)
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 8October a Decentral bus power supply Power demand of the Synco devices and couplers / Power supply into the KNX bus RMU, RMU-B5 mA25 mA RMH, RMH-B 5 mA25 mA RMK770, RMB795, RMS7055 mA25 mA OZW775 5 mA25 mA QAX910 5 mA12.5 mA OZW771 5 mA RXB21.1/ mA RXL21.1/ mA QAW740, QAW740-B 7.5 mA RMZ792 (direct connection to the KNX bus) 5 mA (with external power supply), 45 mA (no external power supply) OCI mA Area/Line coupler N140/13 6 mA primary line / 8 mA secondary line IP Router N mA
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 9October b Central bus power supply Rules how to use the central bus power supply unit: Application: A central bus power supply unit shall be used: - if more than 8 DPSU are necessary to supply the line - if KNX devices from third parties are connected to the line Requirements: If a central bus power supply unit is used, all DPSU have to be turned off In each line not more than 2 central bus power supply units are allowed
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 10October b Central bus power supply unit Bus power supply with integrated inductor. Provides and monitors the system power required for the KNX bus. Typs: 5WG AB01 (N125/01)160 mA 5WG AB11 (N125/11)320 mA 5WG AB21 (N125/21)640 mA
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 11October Area / Line coupler N140/13 Area coupler Mainline Arealine N140/13 Line coupler Line Mainline Purpose of the Area /Line coupler and IP Router: To extend the plant when more than 64 bus devices are needed Reduction of the data traffic by using programmed filter tables
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 12October Area / Line coupler N140/13 Area /Line coupler Area couplers Line couplers How to address the coupler: 1.Put the coupler into the address mode 2.Edit device list 3.Define the address 4.Refresh device list
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 13October IP Router N146 IP Router (Auxiliary power supply AC/DC 24V needed) Mainline / Line IP Network How to address the router: 1.Put the coupler into the address mode 2.Edit device list 3.Define the address 4.Refresh device list
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 14October IP Router IP Router N146 Area coupler / IP Router N146 Area coupler / Point to Point Connection The IP routers N146 have to be connected by a crossed Ethernet cabel Input (in Parameter menu) of: IP Address (unique) Subnetmask (defines the max. number of devices in the network) Multicastaddress (standard for KNX devices: ) IP Standard Gateway (Default: )
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 15October IP Router IP Router N146 Area coupler / IP Router N146 Area coupler / Connection of more than two IP Routers N146 Using a ‚Switch‘ The IP Routers N146 have to be connected to the switch by a straight Ethernet cabel Input (in Parameter menu) of: IP Address (according to the ‚individual address‘; unique) Subnetmask (defines max. number of devices in the network) Multicastaddress (according to the ‚group address‘; standard for KNX components: ) IP Standard Gateway (default: ) IP Router N146 Area coupler / IP Router N146 Area coupler /
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 16October IP Router Settings IP Router in existing network The following points have to be discussed with the network administrator: automatic allocation of the IP Address (DHCP – Service) or manual allocation of the IP address IP Address Subnetmask Multicastaddress (standard for KNX components: ) IP Standard Gateway (default: )
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 17October LTE filter table N140 Area/Line coupler (from Version R2) N146 IP Router (from Version R4) Arealine / Line Backbone / Area line Geographical zone Heat distribution zone Refrigeration distribution zone Domestic hot water zone Programmed LTE Filter Tables etc.
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 18October LTE filter table + Time switch zone, Time switch-slave, Master/slave zone, QAW-operating zone …which can be blocked by the LTE filter table + Heat distribution zone source side, heat distribution zone consumer side, heating radiation, heating coil + Ref distribution zone source side, ref distribution zone consumer side, cooling radiation, cooling coil + Time switch-slave domestic hot water zone + Heat distribution zone main distributor, heat distribution zone primary controller Air distribution zone
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 19October LTE filter table Zones 1…31 Filter = „Block all“ Zones 1…15 Filter = „Normal“ Zones 16…31 Filter = „Route all“ Zones 1…31
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 20October LTE filter table Attention: In order to avoid a data jam in the area/line couplers*, we highly recommend not to use more than 15 devices in the same zone if the zone reaches over the line coupler. * The same rule is valid for IP routers as well! Air distribution zone Example: a lot of controllers switch from ECO to COMF and all controllers send the confirmation message back at the same time. This is valid for the following zones:
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 21October LTE filter table Area coupler Area 1Area 2Area 3
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 22October LTE filter table S-Mode Group Object: -Time / Date Filter = normal: Time remote control by the time slave does only work, if the time master is placed in the same or higher line. S-Mode Group Objects (like system time) are not concerned by the LTE filter table. LTE Datapoints: - LTE Alarms - Time remote control Zeit / DatumLTE Alarme Filter = block all: If the filter is set to „block all“, no LTE telegrams are routed. S-Mode Group Object: -Time / Date LTE Datapoints: - LTE Alarms - Time remote control Mainline / Line Area / Line coupler One and two-way communication: Mainline
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 23October LTE filter table Settings in ACS Service: Normal (route with activated filter, standard setting) Route all Block all Attention: These settings only have an impact on LTE telegrams. S-Mode Groupe Objects are not affected! Concerning the S-Mode Groupe Objects please pay attention to the ETS settings!
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 24October LTE filter table LTE – Filter: 1) Normal (filter) / 3) block all N140/13 Area coupler N140/13 Area coupler N140/13 Area coupler RXB RXB Switch RM RM Dimmer Switching actuator RM OZW Area 1 Area 7Area 15 Backbone 0 N140/13 Line coupler Line 1 N140/13 Line coupler Line 2 N140/13 Line coupler ACS Dimmer RM Switches / Actuator RMB RM RM Line 15 Switch Inputs RMZ Max. 64 Synco – Devices Max. 64 KNX – Devices Max. 64 Synco – Devices LTE – Filter: 1) Normal (filter) / 3) block all 1) 3) 1) No access for LTE telegrams! = block all
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 25October Topology with IP
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 26October Topology with IP IP Router N146 Area coupler / 24 IP Router N146 Area coupler / 24 IP Router N146 Area coupler / 24 RXB RM RM RM RMB Area 1 Area 7 Area 15 IP Data Network N140/13 Line coupler Line 1 N140/13 Line coupler Line 2 N140/13 Line coupler RM RM RM OZW RM RM Line 15 RM RM RMZ ACS Max. 64 Synco – Devices 1) 2)1) LTE – Filter: 1) Normal (filter) / 2) Route all 1) Attention: Alarm drain must be installed in the main line and the filter of the IP router must be set to ‚route all‘. = route all = Backbone
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 27October How to plan a big plant Topics: 1.Number of bus devices in a area / line / network 2.- Distance between bus devices - Distance between bus devices and the next bus power supply unit - Length of bus lines 3.Location of alarm drains 4.Location of room units
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 28October How to plan a big plant 1.Number of bus devices in a area / line / network Arealine, Mainline, Line: Number of Synco bus devices + KNX devices from third parties <= 64 Number of arealines 1 Number of mainlines Number of lines Number of bus devices1..64 Number of Backbones 1 Number of areas Number of lines1..15 Number of bus devices 1..64
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 29October How to plan a big plant 2a. Distances and lengths of bus lines with PSU Network with central bus power supply (PSU): Distance between… two PSUsmin. 200m bus device and closest PSUmax. 350m two bus devicesmax. 700m length of a linemax. 1000m
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 30October How to plan a big plant 2b. Distances and lengths of bus lines with DPSU Network with 1 decentral bus power supply units: Bus device and closest device with DPSUmax. 350m Between two bus devices max. 350m Length of a linemax. 350m Network with 2 decentral bus power supply units: Bus device and closest device with DPSU max. 350m Between two bus devices max. 700m Length of a line max. 700m Network with 3-8 decentral bus power supply units: Bus device and closest device with DPSU max. 350m Between two bus devices max. 700m Length of a line max. 1000m
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 31October How to plan a big plant 3. Location of alarm drains Alarm drains are devices like communication centrals (OZW775), bus remote units (RMZ792) and steering and control devices with failure relays (RMS705), which are able to receive alarm messages. Alarm drains shall be installed in the highest arealine (Backbone). Only devices with central functions like alarm drains and time master shall be installed on the backbone. 4. Location of room units Devices with room functions (QAW740, RXB…) and devices like RMB which are exchanging data with the room controller RXB shall be installed in the same line.
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 32October Commissioning General points to check: 1.Bus devices and field devices are installed 2.Wiring has been checked 3.Power supply available at all devices 4.Bus power supply available in all lines Check the communication: 1.Bus power supply available 2.Device addresses defined between 1…253 (254 only for OCI700.1) 3.Devices are not in the commissioning mode 4.Time and Date are up to date 5.Zones are defined and the devices are able to communicate using the same zone addresses
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 33October Sequence of project steps
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 34October a Applications with heating/cooling-changeover Changeover by a digital input (Thermostat in flow tube)
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 35October b Applications with heating/cooling-changeover Changeover by an analog input (Outside temperature sensor)
Building Technologies / HVP SYS SYNRené Kämpfer © Siemens Switzerland Ltd 2007 Page 36October c Applications with heating/cooling-changeover Changeover by a calendar (in precontroller)