Steve Clarke MVHR Designer / Service Engineer Commissioning and Maintenance of MVHR Systems.

Slides:



Advertisements
Similar presentations
World Health Organization
Advertisements

Heating, Ventilation, and Air-Conditioning (HVAC) Systems
USER MAINTENANCE.
Chapter 8: Duct Design and Sealing To be used with the Guide to Building Energy Efficient Homes in Kentucky.
Lodging HVAC and Refrigeration
Unit 206: Domestic hot water systems
Foundations of Real Estate Management TM BOMA International ® Module 3: Building Operations I Heating, Ventilating, and Cooling the Building.
Common Faults - Machinery Cover missing or not fitted correctly Action : replace or refit covers Nuts or bolts missing from covers Action : replace Seals.
Pollution Control PPT03A 1 POLLUTION CONTROL an Overview POLLUTION CONTROL an Overview.
Coupling a Network HVAC Model to a Computational Fluid Dynamics Model Using Large Eddy Simulation Jason Floyd Hughes Associates, Inc Fire + Evacuation.
11-1 Copyright  2010 McGraw-Hill Australia Pty Ltd PowerPoint slides to accompany Puffett, Hossack, Stone, Burn & Miles, Gasfitting 2e Chapter 11 OPERATION.
Condensation Solutions “Breathe easy…”. Cost effective solutions for condensation and mould.
Active Solar Heating Liquid Solar Heating System Travis Ricard.
Management training Jumeirah beach residence sector 3 Presented by November 15 th 2006.
Condensation Piping and Installation Drain Pans
Welcome to Field Controls: HRV / ERV Training Duct Systems Part 3
Refrigeration and Heat Pump Systems Refrigeration systems: To cool a refrigerated space or to maintain the temperature of a space below that of the surroundings.
Presentation on Installation of a Domestic Cold Water Storage Cistern
TRI MARTIANA.  A good and effective ventilation system is necessary in a workplace which have processes that emit air contaminants such as dust, fumes,
Air Handling Systems Heating Ventilation and Air Conditioning (HVAC) Part 2: Components Supplementary Training Modules on GMP Module 3, Part 2: Components.
WHO - PSM Air Handling Systems Heating Ventilation and Air Conditioning (HVAC) – Part 2 Pharmaceutical Quality, Good manufacturing Practice & Bioequivalence.
10 Energy Saving Advices. 1- Lowering of the temperature at night Limit the lowering of the temperature at night. If the temperature is reduced too much,
Windows Do not open or close all windows and doors at the same time. Optimise the ventilation by experimenting with opening different windows instead.
DST H.O.M.E. Home Ownership Maintenance and Education Property Maintenance: Protect Your Property Value.
Learning, our way Examples of bad installation. CONTENT Installation related examples Installation related examples Application related examples Application.
1 HVACR416 – Design Principles Air Exchange. 2 HRV’s (Heat Recovery Ventilators)
Unit 205: Cold water systems
Settings & Adjustments. Settings & Adjustments.
World Health Organization
Lindab Solus - Simply the natural choice.... lindab | comfort Chilled beam revolution! + Save up to 45 % cooling energy!* + Installation and investment.
NOVO ETS IMPROVING YOUR ORGANIZATIONS’ ENVIRONMENTAL, HEALTH AND SAFETY PERFORMANCE ENERGY MANAGEMENT IN THE CONTEXT OF GREEN PRODUCTIVITY.
The Renson Headquarters Renovation issue Renovation issue Major findings Major findings The RENSON- The RENSON- Headquarters More information... More information...
The EWZ building Presentation of the building Presentation of the building The design issue The design issue The building concept The building concept.
CO2 Scrubber Bracket The Carbon Dioxide Removal Assembly is the system that removes carbon dioxide from the Space Station atmosphere. Usually it works.
World Health Organization
Heat Exchange Ventilation Heat Exchange Ventilation.
-Too little or too much ventilation -Insufficient ventilation results in excessive indoor humidity -Uncontrolled ventilation can cause exhaust leaks within.
1-1-Why Maintenance HVAC ? Increases equipment life & reliability Reduces size & scale & number of repairs Lowers maintenance costs through better.
Bathroom Exhaust fans Reduce energy use by 90% and cut through that thick shower fog Philip Jones.
HEATING AND COOLING SYSTEMS
Engine Performance BASIC MAINTENANCE AND LIGHT REPAIR.
When drawing your plan, try and add as much detail as you can, labelling different features, such as double glazed windows and cavity walls. Draw two.
Unit 209: Drainage systems
Central Heating and air conditioning protection. It is important to have your ductwork professionally cleaned every three-4 years. This will now not best.
The C.I. Engines Fuel System  The C.I. engine demands that the fuel supplied is –  Timed to inject when the piston is near the end of the compression.
Welcome Dealing with Condensation & Damp. Condensation, Damp & Mould Causes and Prevention.
Product Awareness, Commissioning & Maintenance
Maria’s Restaurant Chapter 2 Section 6
Air source heat pump Understand the fundamental principles and
POSITIVE CRANKCASE VENTILATION AND SECONDARY AIR-INJECTION SYSTEMS
Draught Finder Trevor Clark 10. Available Ventilation System Types
Maria’s Restaurant Chapter 1 Section 4
Maria’s Restaurant Chapter 3 Section 13
Part 2 Technician’s Guide & Workbook for Duct Diagnostics and Repair
HVAC Repair - A Guide for Everyone
AC Repair & Furnace Repair - Tips To Consider
Electrical Gas Plumbing Heating & Cooling
Cooling System Get the engine up to optimum operating Temperature as quickly as possible and maintains it at that temperature. Controls the heat produced.
Smoke Detector Installation Guidelines
Cisterns and Insulation
Moisture and Poor Ventilation
Flip The Long House Let’s imagine the Long house example in Manual J has undergone a house flipping/energy savings update. The insulation was increased,
Adding Zones to Existing Systems
FBE03: Building Construction & Science
Error codes for split systems
ELECTRICAL INSTALLATION
Cooling System Get the engine up to optimum operating Temperature as quickly as possible and maintains it at that temperature. Controls the heat produced.
Determination of Vacuum Pump Operational Efficiency
Presentation transcript:

Steve Clarke MVHR Designer / Service Engineer Commissioning and Maintenance of MVHR Systems

Why do we have to commission MVHR systems? Optimise the efficiency of the heat recovery. Maximise the energy efficiency of the system. Deliver the required amount of air into / out of each room. Ensure controls are correctly set for the MVHR equipment, building and occupants. Ensure air transfer paths are sufficient. Ensure the system has been installed as designed, many are not ! Check for air leaks. Record all settings for future reference. Produce documentation for Building Control / Consultants

Why do we need ventilation ? 7l/s = 25.2m3/hr therefore ideally m3/hr/person

Air flow measuring Swema hot wire anemometer 7 to 450m3/h, a net of hot wires. Pros: very low pressure loss in the domestic range. measures air mass flow rate not just volume flow rate therefore more accurate at different temperatures. Cons: quite large measuring head. expensive at around £1,600. Best tool for commissioning

Air flow measuring Airflow LCA 301, moving vane with hood 100l/sec 360m 3 /hour. Pros: smaller so will fit awkward places easier. relatively cheap about £400 Cons: higher pressure loss. takes a while to run up to speed. susceptible to air jet causing false reading. Probably the best tool for maintenance checks.

Commissioning – air flows

Commissioning – recording settings

Supply or extract air valves fitted in the wrong locations, i.e. valves switched. Incorrect air valve mounting rings used or not properly secured. Air valves and external grills fitted in positions that make it very difficult to collect the air for commissioning. Air valves caulked in place (not possible to adjust). Intake and exhaust duct insulation missing or not properly installed. Wet seal not dry seal trap used on condensation outlet or no trap fitted at all (drain under negative pressure, wet trap could dry out in summer). Condensation outlet put through wall to outside (could freeze up). Frost protection pre-heater or supply duct heaters not properly wired up. Noisy air valves (especially relevant in bedrooms). Difficulties achieving desired boost air flows on flexible ducting systems. Common commissioning issues

Less Common…but have happened Ducts connected to the wrong ports on the MVHR unit, i.e. supply valves sucking, extract valves blowing ! Air leaks found on the ductwork system i.e. damaged flexible ducting or poor duct connections. Wrong handed unit used, duct ports switched. Frost protection pre-heater installed upside down. i.e. filter after the heater cassette. Inappropriate dampers used on extract system. Professional commissioning therefore advised as some of these issued would not necessarily have been identified. Less common issues

External grill locations Roof terminals make it impossible to measure the air flows externally to check for leaks. High level grills make it difficult to measure external air flows. MVHR units located in lofts therefore not ideal.

Air valve locations Please locate air valves in locations that are easy to access for air flow measuring purposes: o not too close to wall / ceiling corners o above shower rails o above kitchen cupboards o behind wardrobes

MVHR maintenance requirements Every 4 to 6 months: MVHR and kitchen extract filters to change however there are exceptions: - due to external conditions / events. - due to internal activity / cleanliness. External grills to check for blockages. Condensate drain to check for leaks. Periodically: Clean extract air valves – potentially dusty or greasy Cleaning of the extract ductwork, is this required ?

External event MVHR unit left running whilst paving was being cut and laid. Intake grill positioned quite low to the ground. Result – very fine dust particles penetrated through the intake filter into the heat exchanger. It is important to keep the MVHR systems turned off while the site or property is still dusty.

Intake grills What is wrong with the location of the intake grills in these two pictures ? And by the way what is that white insulated plastic pipe with a tundish ? Intake

Intake grills continued This is the intake grill from the previous slide after being in service for only 12 months. This is why it is not a good idea to have grills too low down especially with an insect mesh behind the louvres. Insects will end up in the MVHR unit intake filter but this is a serviceable component.

Internal event The occupier was in the habit of burning several large candles in the bathroom. Result after 6 weeks the extract filter was almost blocked with a thick waxy soot deposit. Better to be in the filter rather than lungs however ?

Set of dirty filters, about 1 year old Which is intake which is extract, why?

A final note on filters…. Central London intake filter Pre-occupancy building dust

Extract valves Extract air valve found in a kitchen in a 12 month old house. Flies and dust stuck to grease. The air valve also had a cone shaped filter behind it but this trapped the flies between the valve and the filter. A better solution would have been to fit a filtered kitchen extract grill with a visible filter.

More extract valves Bathroom extract valve after a few years in service. The dust is lint off towels etc. Possible to fit a cone shaped filter behind the valve to stop dust entering the ductwork however “out of sight” usually means “ out of mind” The filter will substantially reduce air flow when dirty and could be sucked further into the ducting system if not secured.

Yet more extract valves “Bunch of straws” damper in a plenum chamber behind the bathroom extract grill shown below. The grill is also partially blocked. A traditional adjustable circular extract valve would have been a better option. Dampers behind extract valves or grills is not to be recommended. Periodic checking and cleaning of extract valves is recommended.

Cleaning extract ductwork system ? Ductwork bend above a bathroom extract air valve, these can be cleaned with a damp cloth very easily. Extract fan blades after 4 years. If accessible these can be cleaned, however unless the fan is very dirty it is probably not cost effective, especially if the fans are difficult to access.

MVHR maintenance in summary Change the filters at regular intervals. Check the intake & exhaust grills for blockages or obstructions. Clean the extract air valves if necessary. Clean the ductwork behind the extract air valves if necessary. Maybe clean the fan blades if easily accessible.

For more information contact: Steve Clarke Designer / Services Engineer Green Building Store Tel: