Copyright 2011, Toshiba Corporation. Toshiba International Corp - Houston Tx Jim Hartzel Section Mgr - Water / Waste Water Business 20 Yrs Field Service.

Slides:



Advertisements
Similar presentations
VFDs Energy Savings A Case Study on Boilers National Grid Solutions & Opportunities Upstate New York Energy Efficiency Conference & Expo April 7, 2011.
Advertisements

References Which were useful? Sources Fluid Power with Applications; Anthony Esposito Basics of Hydraulic Systems Qin Zhang Hydraulic and Pneumatics.
SAMPLE SLIDES OF THE 1-DAY SEMINAR FOR PUMP USERS
Welcome Using Variable Speed Drives to Save Energy. Dan Reilly June 22 nd 2010.
Variable Frequency Drives Energy Savings Applications & Benefits National Grid-NYSERDA Upstate NY Commercial Industrial Efficiency Expo March 30, 2010.
HVAC & WATER Application note
Variable Frequency Drives VFD Basics
CHE Pumps and gas moving equipment  For the fluid flow from point to another, a driving force is needed.  The driving force may be supplied by.
Booster System Basics: Constant Speed Systems
Energy Efficient Fluid Flow
Energy Efficient Fluid Flow. Fluid Flow System Fundamentals W motor = W fluid / (Eff motor x Eff drive x Eff pump )
APPLICATION OF MOTORS TO ADJUSTABLE FREQUENCY DRIVES PART 1 Alan Lowe, Senior Electrical Consultant.
Motor Designs A, B, C, D ECE 441.
Application Types Variable Torque Constant Torque.
Contemporary Engineering Economics, 4 th edition, © 2007 Life-Cycle Cost Analysis Lecture No.22 Chapter 6 Contemporary Engineering Economics Copyright.
PENTAIR 1.
Energy Savings in Water and Wastewater Segment
“Energy Efficiency Guide for Industry in Asia”
WISA Meeting Help Arrange a Speaker, Write Bio, Introduce
7154/7156 Variable Speed Drives
Jim Chmielewski – HVAC Sales Manager Emerson Control Techniques
Fifteenth Annual Vail Operator Training Seminar Understanding Centrifugal Blower Operation in Wastewater Aeration and Dissolved Oxygen Control Presented.
Make the most of your energy Make the most of your energy SM Add photo in this area Chicago Advanced Energy Stakeholder Series 2014 Mike Mattingly Oct.
Lesson 26 CENTRIFUGAL PUMPS
Demystifying SelfSensing Pumps. Design Operating Point 300 Gallons Per Minute 53 Feet of Head System Curves 150 ton 12deg Delta T 60 GPM each.
EPANET FOR PRESSURIZED PIPE SYSTEMS
Pumps.
Static Pressure Control Loop The purpose of the static pressure control loop is to maintain an optimal static pressure in the ductwork. The control loop.
1 Multi-use Facility. 2 Occupancy – 140 persons Building Characteristics Single story 20,000 square feet (250’ x 80’) Standard construction.
POWER SAVING BY ROCKSOLID INDUSTRIAL SOLUTIONS SYSTEMS REQUIRING PUMPS USING VALVE CONTROL SYSTEMS REQUIRING FANS USING DAMPER CONTROL SAVE GOOD $MONEY$
7154 VFD Presentation #4 May 2002 Paul Weingartner.
Grundfos FLOW THINKING Air conditioning the Grundfos Way.
1 Medical Office Building. 2 Occupancy – 400 persons 8 a.m. – 5 p.m. Monday - Friday Building Characteristics Three stories 40,000 square feet (200’ x.
Pumps and Lift Stations. Background Fluid Moving Equipment Fluids are moved through flow systems using pumps, fans, blowers, and compressors. Such devices.
automation 4 me TYPES OF LOAD 1 automation 4 me CONSTANT TORQUE LOAD : PERCENT SPEED NOTE:- A CONSTANT TORQUE LOAD IS NOT NECESSARILY 100% LOAD TORQUE.
Variable Frequency Drives and Irrigation Pumps Stefanie Aschmann Bozeman, MT 11/30/11 1.
SAMPLE SLIDES OF THE 2-DAY SEMINAR FOR ENGINEERS As you will notice there are few words on these slides, your trainer will provide you with his experience.
The EnergyMizer Power Reduction & Conditioning System ®
1 CEE 426 Wastewater Treatment Plant Design November 12, 2012 Thomas E. Jenkins President JenTech Inc N. Elm Tree Road Milwaukee, WI
Variable Speed Applied to Pumps. Life Cycle Costs - Courtesy of Hydraulic Institute and Europump Initial cost is not the only cost associated with a pump.
Energy Saving Measures - 1
1 Hospital Building and Campus Piping. 2 Hospital Building Occupancy – office and patient areas Patient areas: 24 hours per day Office areas: 8 am – 5.
EE130 Electromechanics 2013 J. Arthur Wagner, Ph.D. Prof. Emeritus in EE
1 ME444 ENGINEERING PIPING SYSTEM DESIGN CHAPTER 6 : PUMPS.
Learning Outcomes Upon completion of this training one should be able to: Identify hydronic chilled water system applications. Define the difference between.
1 JCI 1 1 Energy can be neither created nor destroyed, but only converted from one form to another. First Law of Thermodynamics Karl Friedrich Mohr In.
7/15/2002PP.AFD.09 1 of 43 Yaskawa Electric America Variable Frequency Drives In HVAC Applications.
SUDHIR REDDY S.V.R M.TECH(CAD/CAM)
Irrigation Pumping Plants
Energy Efficient Motors and Variable Speed Drives
Lecture Objectives: Learn about thermal storage systems
Components Motors and Generators.
Components Pumps.
Components Motors and Generators.
Yaskawa Electric America on Variable Torque Loads
Variable Frequency Drive Savings Calculator Tools
HIGH PERFORMANCE PRESSURE SYSTEMS.
Parul Institute of Technology
SPOC Automation and BECI- who are we?
Motor Drive Prof. Ali Keyhani. Modern Variable Speed System A modern variable speed system has four components: 1. Electric Motor 2. Power Converter -
CENTRIFUGAL PUMP TROUBLESHOOTING
Traditional Water Booster System
Volume Control in fluid distribution systems
ME444 ENGINEERING PIPING SYSTEM DESIGN
Pumps and Lift Stations
Fans and Blowers Module V.
MOTOR SELECTION Electric motors should be selected to satisfy the requirements of the machines on which they are applied without exceeding rated electric.
Single Phase Electric Motor Speed Control
Multi-Pump Control Strategies
Presented by Mike Zacharias
Presentation transcript:

Copyright 2011, Toshiba Corporation. Toshiba International Corp - Houston Tx Jim Hartzel Section Mgr - Water / Waste Water Business 20 Yrs Field Service / Training Engr

Agenda Affinity Laws Basic Operation of a VFD VFD and Energy Savings $$$ Other Benefits of Using a VFD Questions and Comments welcomed any time

Variable Speed Drives in Pumping Applications Should we use a VFD on our Pump? Why ? Our Pump is running fine ! Should I buy a VFD ? Is it worth it ? Should I stick with my valve Throttling

Affinity Laws for Centrifugal loads 50% 100% 50% 12.5% Flow is proportional to Pump Speed (RPM) Power (KW) is Proportional to the cubed of Pump Speed (RPM)

Affinity Laws for Centrifugal loads Reduce Speed by 10% Reduces Flow by 10% Reduces Energy by 27%

. E NERGY S AVINGS There are applications where you need to change the amount of fluid you are pumping. There are FOUR ways you can do this: Regulate the discharge of the pump – Throttling Change the speed of the pump – VFD, Eddy Current clutch… Change the diameter of the impeller – Fixed speed Purchase a new pump – Fixed Speed

Basic Motor Characteristic RPM 0 Available Motor Torque Load Torque 1750RPM 1800R PM Pullup Torque Breakdown Torque Breakaway Torque Typical Nema B Speed Torque Curve 100% 60% 1777RPM Motor Current 100% 600% RPM = 120 Freq # Poles RPM = 120 x 60 4 RPM = = Constant #Poles = Fixed What's Left = Freq RPM = 120 x 40 4 RPM = 1200

Controlling Flow P Throttling Valve 200 GPM P Full Open 200 GPM 80% Speed 80%

Energy Savings

Example 1 - Utility Cost

Pump Example 1

Flow Rate

Pump Example 1 Return on Investment Break Even Pt

Pump Example 1 Energy Consumption: Throttling vs VFD

Pump Example 1 Annual Energy Usage: Throttling vs VFD

Pump Example 1 Annual Energy Savings: VFD

Pump Example 2

Flow Rate

Pump Example 2 Return On Investment Break Even Pt

Pump Example 2 Energy Consumption: Throttling vs VFD

Pump Example 2 Annual Energy Usage: Throttling vs VFD

Pump Example 2 Annual Energy Savings: VFD

Motor Starting Across Line Line Voltage Power line Disturbance Caused by Starting Across the Line Equipment shutting Off/Tripping High Peak Power $$$

VFD Features: V/F Curves VOLTAGEVOLTAGE FREQUENCY 0 100% 50% V/F Curve Eliminates High Inrush to motor

Accel / Decel 100% Speed 0 60 Sec Accel Rate Decel Rate 90 Sec 110 Sec Slowly Accelerates Motor Slowly Decelerates Motor Adjustable.1sec to 6000 sec

VFD Features: Energy Savings Curve VOLTAGEVOLTAGE FREQUENCY 0 100% 50%

Water Hammer 100% Speed 0 60 Sec Accel Rate Decel Rate 90 Sec 110 Sec Eliminate Water Hammer cause by sudden changes in pressure Adjustable.1sec to 6000 sec

VFD Features Adjustable Accel and Decel Rates Upper and Lower Limits Special V/F Curve for High Efficiency PID Control

. Reduced start inrush Unlimited starts per hour in most applications. Reduces Peak Demands. Power Factor Correction Higher PF (0.98) than running motors across the line Speed control Control process with changes in speed instead valves, vanes or dampers Energy Savings $$$$ Eliminates Water Hammer Saves wear and tear on equipment VFD B ENEFITS

Scada P VFD 4-20ma Flow sensor PLC VFD AC Power Typical Contol system

.

.

. Typical Applications: Raw Water Pumps Return Activated Sludge Pump (RAS) High Service Pumps Low Service Pumps Blowers Chopper Pumps