New Low Capacity Gas Furnace
Current Situation Multi-family homes is the fastest growing HVAC market Current installations are grossly oversized Existing sizes cause Nuisance pressure switch tripping Cycle-related short run times cause vents to freeze
Solution-ICP Low capacity gas furnaces 2 new models @ 26,000 BTUH input Single stage ¼-hp w/PSC blower motor (N9MSE) Single stage 1/3-hp w/ Multi-Tap ECM blower motor (F/G9MXE) To serve new construction markets in Apartment Multi-family Low Energy homes
ICP® New Low Capacity Models N9MSE0261408A2 F(G)9MXE0261410A2 95% AFUE 2 tons nominal cooling 775 CFM @ 0.50 in. W.C. 675 nominal heating CFM 1/4 HP PSC blower motor (new) 4 speed taps 2 burner/2 cell heat exchanger 13,000 btuh per burner 14 3/16-in. casing 95% AFUE 2 ½ tons nominal cooling 895 CFM @ 0.50 in. W.C. 605 nominal heating CFM 1/3 HP Multi-Tap ECM blower motor (new) 5 speed taps 2 burner/2 cell heat exchanger 13,000 btuh per burner 14 3/16-in. casing
Installation Similarities Current to 4-way multipoise 90%furnaces Footprint Location requirements Duct connections Electrical requirements 15 amp circuit/14ga. wire Gas piping requirements Vent requirements New table for 26K models Condensate connections
Major Differences Inducer Choke Pressure Switches Multi-hole design Pressure Switches New set points Gas Valve & Manifold Pressure Lower set point & operating range 2-pipe venting Not considered “Direct Vent” Can be single pipe or VCA option Dedicated Conversion Kits Not approved for Mobile Home use
Inducer Inlet Choke 3-hole design Hole I.D. is 9.7 mm (3/8-in.) Same overall OD as other chokes Inducer service kit Single stage Includes inlet choke No outlet choke required
Pressure Switches Inducer Housing Pressure Switch Square tube Faces backward Max Make 0.25-in. W.C. Min Break 0.10-in. W.C. Collector Box Pressure Switch Round tube Faces forward
Gas Valve Uses a unique Low Capacity regulator spring Lower natural gas manifold pressure range 1.3-in. W.C. to 1.8-in. W.C. Lower propane manifold pressure 5.5-in. W.C. Certified for this model only Special color label Note the nominal regulator setting of 1.5-in. W.C.
¼ HP PSC Blower Motor 4 speed taps As shipped: 25 µF 370 VAC capacitor Black (high) Yellow (medium high) Blue (medium low) Red (low) As shipped: Black (cooling) Blue (heating) Yellow (spare) Red (spare) 25 µF 370 VAC capacitor 2 Brown leads
1/3 HP Multi-Tap Blower Motor 5 speed taps Grey (high) Yellow (medium high) Orange (medium) Blue (medium low Red (low) Green (common) As shipped: Grey (cooling) Blue (heating) Red (continuous fan) Yellow (spare) Orange (spare)
Max length (before deductions) Venting 3 options 2-pipe Single pipe Ventilated Combustion Air Max length (before deductions) 1 ½-in., 70 ft. max @ 2000 ft. 2-in., 200 ft. max @ 2000 ft. Approved for ULC S636 pipe (Canada)
Pipe Diameter (inches) Vent Tables Input Altitude (feet) Pipe Diameter (inches) 1 ½-in. 2-in. 2 ½-in. 3-in. 4-in. 26,000 BTUH Only 0-2000 70 200 NP 2001 to 3000 65 190 3001 to 4000 60 175 4001 to 4500 55 160 4501 to 5000 5001 to 6000 50 145 6001 to 7000 45 135 7001 to 8000 40 120 8001 to 9000 35 110 9001 to 10,000 30 95 NP means Not Permitted
Alberta/Saskatchewan clearances may not apply Terminations 2-in Concentric 3-in not recommend Standard 2-pipe Standard single pipe Alberta/Saskatchewan clearances may not apply Input less than 35,000 BTUH Final ruling required You must verify code requirements with the authority having local jurisdiction
Similar to current products Same minimum inlet gas pressures Start-up Similar to current products Same minimum inlet gas pressures 4.5-in. W.C. for natural gas 12.0-in. W.C. for propane Manifold pressure ranges are lower 1.3-in. to 1.8-in. W.C. for natural gas #44 orifices (0 to 2000 ft.) 5.5-in. to 5.2-in. W.C. for propane 1.25 mm orifices (0 to 10,000 ft.)
Startup-Check Inlet Gas Pressure Remove the inlet pressure tap plug (3/16-in. hex wrench) Install manometer fitting & manometer Install inlet pressure tap plug after checking inlet gas pressure.
Startup-Check Inlet Gas Pressure With manometer connected to inlet pressure tap: Turn gas supply ON Verify inlet gas pressure above 4.5-in. W.C. (natural gas) Set furnace to call for heat After ignition Verify inlet gas pressure does not drop below 4.5-in. W.C. Do not operate the furnace for more than about a minute After checking the inlet pressure Remove manometer Install the 1/8-in. pipe plug in the gas valve
Startup-Check Manifold Pressure Remove the outlet pressure tap plug (3/16-in. hex wrench) Install manometer fitting & manometer Install outlet pressure tap plug after checking manifold pressure.
Startup-Adjust Manifold Pressure With manometer connected to outlet pressure tap: Set furnace to call for heat After ignition and the burner stabilizes The manifold pressure range for natural gas: 1.3-in. W.C. to 1.8-in. W.C. (Refer to table in installation instructions) To adjust the manifold pressure Remove cap that conceals gas valve regulator adjustment screw Turn adjusting screw counterclockwise (out) to decrease manifold pressure clockwise (in) to increase manifold pressure Replace gas valve regulator seal cap Verify manifold pressure is correct
Startup-Adjust Manifold Pressure After adjusting the manifold pressure Terminate the call for heat Turn gas off/gas valve switch to OFF/power off Remove the manometer Install the 1/8-in. pipe plug in the outlet tap of the gas valve Turn furnace gas on/valve switch ON/power on Set room thermostat to call for heat Check pressure tap plug for gas leaks when main burners ignite Check for correct burner flame. Observe unit operation through 2 complete heating cycles
Check Temperature Rise Blower door must be installed when taking temperature rise reading Leaving blower door off affects temperature measurements Changes the duct static pressure and airflow This furnace must operate within the temperature rise ranges specified on the furnace rating plate
Temperature Rise Information 25-55 14-31 Temperature Rise Minimum Mid-Point Maximum Fahrenheit 25° 40° 55° Celsius 14° 22° 31° Min/Max temperature rise is shown on the unit rating plate. Mid-point of the rise range (shown above) is the ideal rise range point
Check Temperature Rise Determine the air temperature as follows: Place thermometers in return and supply ducts As close to furnace as possible Away from line-of-sight of the heat exchanger When thermometer readings stabilize Subtract return air temperature from supply air temperature to determine temperature rise
Adjust Temperature Rise Adjust blower speed to change temperature rise Increase blower speed to reduce temperature rise Decrease blower speed to increase temperature rise Change blower speeds at control board
Blower Speed Tap Locations PSC Models Neutral (white) to 3/16” L2 terminal marked “BLW” Speed taps to ¼” spade terminals on top of relay Unused taps to ¼” spade terminals labeled “Spare” on edge of control board
Blower Speed Tap Locations PSC models 115 VAC motor speed taps connect to the terminals on the relay. “COOL” & “HEAT” are marked on control board (red box). Motor neutral (white) connects to the 3/16 terminal marked “BLW” at the Neutral block (yellow box) Spare terminals connect to spade terminals on the edge of the control board (blue box)
Blower Speed Tap Locations Tap Select ECM models 24 VAC speed taps to 24V MTR TAPS Green wire to COM Neutral (white) to L2 block terminals 115 VAC (black) to terminal BL-1
Blower Speed Tap Locations Tap Select ECM models 24 VAC motor speed taps connect to the terminals on the furnace control board
Blower Speed Tap Locations Tap Select ECM models 115 VAC motor lead (black) connect to BL-1 Motor Neutral lead (white) connects to Neutral-L2
Condensate drain connected? Accessories installed? Other Tasks Filter installed? Filter(s) are external to the casing Condensate drain connected? Check for condensate drainage Accessories installed? Gas piping checked for leaks? Installation book left with furnace? Supply registers open/return grills not blocked? Outer doors installed?
Conversion to Propane NAHA01201LP includes: 1.25 mm orifices Regulator spring Spare spring-Regulator spring change not required Mixer screws with drill bit Low Gas Pressure Switch Brass fittings Wires Conversion Labels
Remove the manifold NOTE: Use a back−up wrench on the gas valve Prevent the valve from rotating on the manifold or damaging the mounting to the burner box Disconnect the gas pipe from gas valve and remove pipe from the furnace casing Disconnect: Wires from gas valve Hot Surface Igniter Flame Sensor Support the manifold and remove the four (4) screws that secure the manifold assembly to the burner box and set aside. Note the location of the green/yellow wire ground wire for re−assembly later
Remove the burner Slide one−piece burner assembly out of slots on sides of burner box Remove the flame sensor from the burner assembly
Remove the natural gas orifices Remove the #44 orifices Discard orifices
Install the orifices Inspect the 1.25 mm orifice for chips or debris Install 1.25 mm orifices There are enough orifices in each kit for largest furnace Do not use Teflon® tape or pipe dope Finger−tighten orifices At least one full turn to prevent cross−threading, Tighten with wrench Discard extra orifices NOTE: DO NOT reinstall the manifold at this time
Pre-Adjust the Gas Valve Green labeled gas valve ONLY! DOES NOT need regulator spring replaced Kit includes an regulator extra spring Regulator must be pre-adjusted for propane applications Extra Gas Valve Regulator Spring
Pre-Adjust the Gas Valve Remove the brass cap for the gas−valve regulator Turn the regulator adjustment screw clockwise 1.5 full turns This will adjust the valve closer to the propane set point If the regulator spring is removed Re-install the spring and the adjustment screw Turn the adjusting screw clockwise (in) 11.5 full turns This will increase the manifold pressure closer to the propane set point Do not install the brass regulator seal caps at this time Pre-adjust the regulator by turning the adjustment screw clockwise 1.5 full turns
Install Low Gas Pressure Switch NOTE: Install the Low Gas Pressure Switch before installing the manifold on the burner assembly Remove the 1/8-in. NPT pipe plug from the gas valve inlet pressure tap Do not discard plug NOTE: Use pipe dope approved for use with Propane Gas
Install Low Gas Pressure Switch Necessary fittings are supplied in the kit There are extra fittings in the kit LGPS is included it the kit CONTACTS OPEN ON PRESSURE FALL AT 7.20” W.C. +/- 0.70” W.C. CONTACT CLOSE ON INCREASING PRESSURE NO MORE THAN 10.20” W.C.
LGPS Fittings Black iron street ell Male x Female x Female Tee Male into inlet tap Points outward Male x Female x Female Tee Male end into street ell Female ends point Outward To your left Brass hex nipple Inserts into tee Brass Street ell Connects to hex nipple Male end connects to LGPS 1 2 3 4 Manometer connection. Install inlet pressure tap plug after checking inlet gas pressure.
Install Low Gas Pressure Switch Use pipe dope sparingly Install: Black iron street ell F x M x F Tee Open end of Tee points outward Connect inlet manometer fitting Brass hex nipple Brass street ell Tighten each fitting with a small wrench Install LGPS Tighten with a small wrench Terminals point outward If unit is to be started at a later date, install plug removed from inlet pressure tap and install in place of manometer fitting
LGPS Pressure Switch Wires There are 2 orange wires in the kit The straight terminals (1) connect to the LGPS The male spade terminal (2) connects to the orange wire of the low pressure switch harness The flag terminal (3) connects to the terminal on the low pressure switch 2 1 3
LGPS Pressure Switch Wires Before installing the manifold Connect the straight terminal from each orange wires to each terminals on the switch
Install the Mixer Screws Use only the parts in the bag marked: “REQUIRED FOR THE CONVERSION OF CONDENSING GAS FURNACES TO PROPANE GAS” Locate the dimple on each burner venturi tube. If you cannot locate the dimple Refer to Figure in the instructions for the location of the mixer screw
Install the Mixer Screws Use only the parts in the bag marked: “REQUIRED FOR THE CONVERSION OF CONDENSING GAS FURNACES TO PROPANE GAS” Bag includes: 7/64th drill bit (7) Mixer screws
Install the Mixer Screws Drill a 7/64−in (2.8 mm) hole in each dimple Install a mixer screw in each drilled hole As straight as possible Perpendicular to the gas flow stream The screw head should be flush with the top of the burner venturi
Install the Mixer Screws Install a mixer screws As straight as possible perpendicular to the gas flow stream The screw head should be flush with the top of the burner venturi
Re-assemble Burner Note the notch on front corner of burner Burner slides in slots in burner box Slide burner forward Notched area should be fully seated forward
Install Manifold Insert manifold Install the 4 mounting screws Verify orifices are captured by the burner mounting rings Install the 4 mounting screws Re-connect: Green ground wire HSI Flame Sensor Route HSI harness OVER manifold Route Flame Sensor harness UNDER manifold
Modify Pressure Switch Wiring Route the LGPS wires down to the LPS Disconnect the orange wire from the LPS (1) Connect the flag terminal (2) to the terminal on the LPS Connect the male spade terminal (3) to the orange wire (1) removed from the LPS 3 1 2
Modify Pressure Switch Wiring Flag terminal (2) connected to the terminal on the LPS Male spade terminal (3) connected to the orange wire (1) removed from the LPS Secure wires with wire tie included in the kit 3 1 2
Startup-Check Inlet Gas Pressure With manometer connected to inlet pressure tap: Turn gas supply ON Verify inlet gas pressure above 12.0-in. W.C. (propane) Set furnace to call for heat After ignition Verify inlet gas pressure does not drop below 12.0-in. W.C. Do not operate the furnace for more than about a minute After checking the inlet pressure Terminate the call for heat Remove the manometer Install the 1/8-in. pipe plug in the brass tee
Startup-Check Inlet Gas Pressure Install inlet pressure tap plug after checking manifold pressure Manometer connection at LGPS
Startup-Adjust Manifold Pressure With manometer connected to outlet pressure tap: Set furnace to call for heat After ignition and the burner stabilizes Verify the manifold pressure (see conversion rating plate) To adjust the manifold pressure Remove cap that conceals gas valve regulator adjustment screw Turn adjusting screw counterclockwise (out) to decrease manifold pressure clockwise (in) to increase manifold pressure Replace gas valve regulator seal cap Verify manifold pressure is correct
Startup-Adjust Manifold Pressure After adjusting the manifold pressure Terminate the call for heat Turn gas off/gas valve switch to OFF/power off Remove the manometer Install the 1/8-in. pipe plug in the outlet tap of the gas valve Turn furnace gas on/valve switch ON/power on Set room thermostat to call for heat Check pressure tap plug for gas leaks when main burners ignite Check for correct burner flame Observe unit operation through 2 complete heating cycles
Startup-Check Manifold Pressure Remove the outlet pressure tap plug (3/16-in. hex wrench) Install manometer fitting & manometer Install outlet pressure tap plug after checking manifold pressure
Check Temperature Rise Blower door must be installed when taking temperature rise reading Leaving blower door off affects temperature measurements Changes the duct static pressure and airflow This furnace must operate within the temperature rise ranges specified on the furnace rating plate
Temperature Rise Information 25-55 14-31 Temperature Rise Minimum Mid-Point Maximum Fahrenheit 25° 40° 55° Celsius 14° 22° 31° Min/Max temperature rise is shown on the unit rating plate. Mid-point of the rise range (shown above) is the ideal rise range point.
Check Temperature Rise Determine the air temperature as follows: Place thermometers in return and supply ducts As close to furnace as possible Away from line-of-sight of the heat exchanger When thermometer readings stabilize Subtract return air temperature from supply air temperature to determine temperature rise
Adjust Temperature Rise Adjust blower speed to change temperature rise Increase blower speed to reduce temperature rise Decrease blower speed to increase temperature rise Change blower speeds at control board
Blower Speed Tap Locations PSC Models
Blower Speed Tap Locations Tap Select ECM models 24 VAC speed taps to 24V MTR TAPS Green wire to COM Neutral (white) to L2 block terminals 115 VAC (black) to terminal BL-1
Blower Speed Tap Locations Tap Select ECM models 24 VAC motor speed taps connect to the terminals on the furnace control board
Blower Speed Tap Locations Tap Select ECM models 115 VAC motor lead (black) connect to BL-1 Motor Neutral lead (white) connects to Neutral-L2
Apply Labels-English Apply to inside of door Note label shows: Model number Orifice size (1.25 mm) Manifold pressure (4.5-in. W.C.)
Apply Labels-French Apply to inside of door Note label shows: Model number Orifice size (1.25 mm) Manifold pressure
Apply Labels-French/English Apply to inside of door Fill in: Date conversion was performed Company name Company address
Apply Labels-French/English Apply to gas valve Shown larger than actual size
Operate the furnace through 2 heating cycles Before You Leave Operate the furnace through 2 heating cycles Verify gas and electric are still on Perform final gas leak check Final inspections of installation Including accessories and filter installed Install outer doors Thermostat set correctly