Two Stage Communicating System

Slides:



Advertisements
Similar presentations
WHIRLPOOL Vertical modular Washer
Advertisements

Wall Mounted J series Troubleshooting.
Operating Functions.
…just got better.
402 COMFORT CONTROL LOGIC. Questions SUB BASE Up to 16 wires may be required.
Daikin Altherma™ Troubling Shooting
Thermostats, Pressure Switches, and Other Electric Control Devices
WebStat™ Programming and Configuration of Thermostats.
HEAT PUMPS.
HEATING AIR © Commonwealth of Australia 2010 | Licensed under AEShareNet Share and Return licence.
Setup/Installation/Operation of an Environmental Control Unit (ECU)
Left Side Discharge Pressure Regulator
38GXC(Q)/40GXC(Q) Service Training Sizes 18 and 24K.
Graphic Symbol Location 1. DIN Terminal X52 The machine is powered by electricity using copper cable with 5 wires (3 phase wires + neutral wire +
AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS
Cooling Only 38MFC/ 40MFC Heat Pump 38MFQ/ 40MFQ
Product Introduction.
AccuMax Multi-Point Injection Mechanics
Variable Speed Indoor Blower Motor Robert Helt Technical Conference - Panama City Beach, Fl
E2 Motors and Motor Starting
Electrical Electricity Fuses Relays Solenoids Electrical Testing
2-Stage Heat Pump Defrost Options Defrost options: –30, 60, 90, 120 or Auto (Infinity/Evolution only) Defrost initiate temp: 32° F Defrost terminate temp:
1 Air Conditioning Pressure Switches. 2 High Pressure switch Used to protect the compressor When condensing temp gets too high Reads High Side Pressure.
Air-Source Heat Pumps I North Seattle Community College HVAC Program Instructor – Mark T. Weber, M.Ed. Airsource Heat Pump 1.
General Troubleshooting Tips.
Air Handler Terminology
Introduction to Defrost
TECHNICAL TRAINING SMART COMMANDER System Requirements CPU : 800MHz and aboveCPU : 800MHz and above Memory : 256MB RAM or HigherMemory : 256MB.
TECHNICAL TRAINING INVERTER-Y
Two-Stage Copeland Scroll Compressors. DESIGN AIR UNIVERSITY External view 1 st stage = 67% 2 nd stage = 100% Used in 17 SEER AC.
We apply 120 VAC to the HM Unit (Remember to check polarity!) Our primary step down T/X provides power to terminal “X” and “COM” on the ignition control.
AIR CONDITIONING (COOLING)
AIR CONDITIONING (COOLING)
USER GUIDE TEMPERATURE CONTROLLER TR-2006 Hot runner temperature controller ShenZhen TanRex Electronic Co.ltd.
Service Section Technical Training. Sequential Controller SQ 1.0.
BASIC ELECTRICITY AND MAGNETISM
James McIntyre VRF Training Manager V5 Key Components.
EMERGING TECHNOLOGIES AVAILABLE TO REDUCE COMPRESSED AIR DEMAND Double Acting Air Cylinder Double Acting Air Cylinder Air Operated Diaphragm Pumps Air.
Refer to Service Manual for details Fault codes. To retrieve fault codes from the remote controller Press the ‘CHECK’ button for approximately.
2013 CHIGO Product CHIGO CMV VRF Control System.
E3 HVACR Controls and Devices
shift to the Test Mode (Forced Operation).
Duct Free System.
TXV Devices.
Comparison between L – Series / K - series
CHIGO VRF System Commissioning.
E1 – Electrical Fundamentals
E3 HVACR Controls and Devices
E2 Motors and Motor Starting
GROUND-FAULT GROUND-CHECK MONITOR
MPU-16A / FPU-16 TEST UNIT TUTORIAL
Table of Contents Heat Pump Operation Charging Procedure Defrost Board
Roof Top Unit Overview (MAGNUM)
ObserverTM Communicating Wall Control Service Training
R3 Controls, Valves, Accessories & Heat Pumps
Model Output Current Battery Life BATPSU VDC 2A 1.2Ah BATPSU VDC 2.3Ah
NRL NRL - Welcome to the NRL Sales Training Program
Universal Interrupted Electronic Oil Primary R7184U Training Module
NRL NRL - Welcome to the NRL Sales Training Program
Error codes for split systems
NRL NRL - Welcome to the NRL Sales Training Program
NRL NRL - Welcome to the NRK Sales Training Program
System 57 Gas Control System
Confidential Oilfree Scroll Compressor   Simplex/Multiplex SRL kW   Troubleshooting Hitachi Industrial Equipment Systems Co., Ltd. Air Compressor.
NRL NRL - Welcome to the NRL Sales Training Program
Fluid Power System Electrical Control
Presentation transcript:

Two Stage Communicating System Company Private

Model 2 Stage Communicating R410A Air Conditioner (2-5 ton even sizes) CCA9, HCA9, TCA9 CCA7, HCA7, TCA7 R410A Heat Pump (2-5 ton even sizes) CCH9, HCH9, TCH9 CCH6, HCH6, TCH6 CCA724GKA100 HCA724GKA100 TCA724GKA100 CCA736GKA100 HCA736GKA100 TCA736GKA100 CCA748GKA100 HCA748GKA100 TCA748GKA100 CCA760GKA100 HCA760GKA100 TCA760GKA100 CCA024GKA100 HCA024GKA100 TCA024GKA100 CCA036GKA100 HCA036GKA100 TCA036GKA100 CCA048GKA100 HCA048GKA100 TCA048GKA100 CCA060GKA100 HCA060GKA100 TCA060GKA100 CCH624GKA100 HCH624GKA100 TCH624GKA100 CCH636GKA100 HCH636GKA100 TCH636GKA100 CCH648GKA100 HCH648GKA100 TCH648GKA100 CCH660GKA100 HCH660GKA100 TCH660GKA100 CCH924GKA100 HCH924GKA100 TCH924GKA100 CCH936GKA100 HCH936GKA100 TCH936GKA100 CCH948GKA100 HCH948GKA100 TCH948GKA100 CCH960GKA100 HCH960GKA100 TCH960GKA100

SAME WALL CONTROL AS SINGLE STAGE Observer™ Wall Control

OD Control Board P/N 1184935

What allows the communication: Outdoor Indoor fan coil Observer™ Control

Communication or Standard Stat Do not use both connections, either use the DX connections or the standard stat connections. If you planning to use an Observer™ but need to use standard stat for emergency, make sure the communicating plugs are removed from equipment DX connectors.

Model Plug location Model Plug Uses model plug to determine: ·  Unit capacity ·  Compressor type ·  Outdoor fan type ·  Type of the outdoor unit (AC/HP) Model Plug Doesn’t matter which way installed on pins Replacement board will not come with model plug, must transfer plug to new board. Model plug takes priority over factory model information input at the factory . If removed after initial power up the unit will operate according to the last valid model plug installed. Pull insert of this model plug to other pic

Model Plug On new units, the model and serial numbers are input into the boards memory at the factory. Replacement boards have no model plug therefore the model plug must be saved from original board and transferred to new board.

System Communicating Concept Input/Output logic communicating between variable speed indoor and outdoor units through the Observer™ wall control. Allows system to adjust for maximum comfort and efficiency. (multiple stages of cooling and heat.) Airflow for two stage outdoor requires two different indoor airflow settings for proper operation. Indoor blower must be set up per indoor instructions for 2 stage outdoor CFM requirements.

All have the communication bus in ID board ID Fan Motor Types 9MAC Full Function ECM 9MVT PWM ECM 8MVL Full Function ECM FCM4X PWM ECM All have the communication bus in ID board

OD Fan Motor Type (Single Stage OD) PSC Type: CCH6, HCH6, TCH6, CCA7, HCA7, TCA7 Fan relay on control board turns the fan on and off by opening and closing the high voltage circuit to the motor. It does not change speeds between low and high stage operation of the compressor. (Two Stage OD) ECM Type: CCH9, HCH9, TCH9, CCA9, HCA9, TCA9 Motor is continuously powered with high voltage, speed determined by electrical pulses from the PWM outputs on the OD control board. The motor adjust RPM to outdoor conditions. Table in the install manual explains.

High Voltage sensing and for FAN and CCH PWM output for ECM fan PWM1 PWM2 P/N 1184935

OD Fan Motor Troubleshoot Test PWM output at OD board terminals with a voltmeter set to DC volts.

Compressor Staging Basic scroll design modified with internal unloading mechanism. It opens a bypass port in first compression pocket and reduces the displacement of the scroll when unloading. Operates approximately 67% capacity when the solenoid is not energized and 100% capacity when the solenoid is energized. Loading and unloading is done “on the fly” without shutting off the motor between steps.

Scroll Compressor Unloading Molded solenoid plug to compressor converts 24Vac to 24Vdc with an internal rectifier. Plug output should read 24Vdc if calling for high stage. Internal Protection Internal Pressure Relief (IPR)-relieves pressure discharge gas into compressor shell if differential between suction and discharge exceeds 550-625 psig. Internal overload in motor windings.

Control Inputs Low pressure Switch input High pressure switch input OCT Compressor Transformer input OAT P/N 1184935

Compressor Control VS and L2 function Monitors high voltage to the compressor and for diagnostics. Voltage should be present anytime compressor contactor is pulled in, no voltage if not pulled in. Compressor always starts in Low for 5 seconds regardless of call Easier starting C-24VAC com rtn contactor C-24VAC com rtn solenoid Lo/on-run cap Hi-compressor solenoid

Troubleshooting Compressor Staging Suction pressure at the service valve should be reduced by 3-10% when switching from low to high capacity. Note the liquid pressure will be very similar in high and low stage so do not use this to determine. Compressor current should increase 20-45% when switching stages. In high stage the compressor DC solenoid coil should be energized

Unloader Test Procedure Check for amperage change at least 20 percent when cycling from high to low at wall control. If not, remove the solenoid plug from compressor. With unit running and wall control calling for high stage, check voltage at the plug with a DC meter..should be 24volt DC. If correct DC at control circuit molded plug, measure the compressor unloader coil resistance. Resistance should be 32-60 ohms depending on compressor temp. If coil resistance is infinite, much lower than 32 ohms or is grounded, the compressor must be replaced.

HP DEFROST Quiet Shift can be enabled: on the board (non communicating) or with the observer™ wall control (comm) Add purpose of quiet shift Forced Defrost Pins Defrost time and Quiet Shift switches

Defrost Reversing Valve Outdoor coil temperature Outdoor air temperature Control Board interval times

Quiet Shift Field selectable defrost mode which may eliminate occasional noise that could be heard at the start and end of defrost cycles. At start of defrost cycle the reversing valve will energize and compressor will turn off for 30 seconds, then turn back on to complete defrost. At the end of defrost cycle the reversing valve de-energizes, compressor will turn off for another 30 seconds, then the fan will turn off for 40 seconds before starting in the heating mode.

Defrost Options and Operation Interval Time options: 30, 60, 90, 120 or Auto (Observer™ Control overrides the dip switch settings (see next slide) Defrost initiate temp: 32° F Defrost terminate temp: 65° F or 10 min has passed. Defrost will not occur if over 50° F outdoor temperature exist. If OAT is >25*F defrost will occur in high or low stage as demanded by stat or observer. If OAT is </= 25*F defrost will occur in high stage and terminate at 50*F coil temp with min 2.5 min defrost.

Auto Defrost: Adjust the defrost interval time based on the last defrost time DEFROST TIME NEXT DEFROST INTERVAL < 3 minutes 120 minutes 3 to 5 minutes 90 minutes 5 to 7 minutes 60 minutes > 7 minutes 30 minutes

Forced Defrost Forced defrost pins provided on board Short pins for 5 sec and release If coil temp is below initiate and outdoor temp is below 50*F – full defrost cycle If coil temp is above initiate temp OR outdoor temp is above 50 – 30*F second defrost cycle occurs

Defrost Termination Fan Operation ODF will remain off for 20 seconds after defrost termination. Allows time for system to capture the heat from the od coil and reduce the steam cloud effect that may occur on transition of defrost to heating cycle

Defrost hold On non-communicating system the thermostat becomes satisfied (Y1 or Y1 and Y2) before the defrost cycle is terminated, the control will “hold” in defrost mode and finish the cycle on the next call for heat. On communicating systems the Observer™ doesn’t need hold because the system will complete the defrost cycle before shutting down the system.

Time Delays 20 second outdoor fan delay after defrost Reduces fog effect 15 second aux heat hold after defrost termination (W1) Prevent cold blow 1 minute delay in cooling mode before turning outdoor fan off if outdoor temp is 100 deg F or higher For easier starting 30 second compressor delay and 40 second OD fan delay after defrost before starting in heat mode if Quiet Shift enabled. The 2 wire control board does not give a status code when you defeat these time delays so with no way to tell if it is on or not we chose not to allow it to be defeated at this time. Next version of UI software may allow it.

Time Delays (cont.) 2 minute to return to standby from last valid communication (Observer™ Wall Control Only) 5-minute time guard between compressor cycles Can be defeated by shorting forced defrost pins for 1 second and releasing Or by pressing heat to or cool to button for 10 seconds. 5 minute compressor re-cycle delay on return from a brown-out condition.

Refrigerant Control ID all to have cooling TXV OD Heat pumps will have heating pistons.

the system reverts to default operation Outdoor Thermistors Electronic devices that sense temperature, as temp increases, resistance decreases. OD unit has two: OAT and OCT Coil and Outdoor temp thermistors are compared to verify proper operating range Sensor failure: the system reverts to default operation If OAT fails low ambient cooling will not be allowed and one minute outdoor fan off delay will not occur. If OCT fails low ambient cooing will not be allowed. COMPARISON OCCURS: 20 min after defrost termination, not during defrost Ignored until unit as run for 5 consecutive minutes

Troubleshoot Thermistors Sensors may be out of range if: If OAT indicates 10*F warmer than the OCT If the OAT indicates 20*F cooler than the OCT OPEN if resistance is reads 500K Ohms or higher (-50ºF or below) SHORTED if resistance reads 1K ohms Or lower (188ºF or higher)

Liquid Line Solenoid Standard Stat: LLS is connected to the Y1 and C terminals. Energized anytime compressor is running. Observer™: LLS output is at the Y1. The LLS coil is 24Vac. Y1 gives 24Vac signal anytime the compressor is energized. LLS is required in HP long line applications to control refrigerant migration in the heating mode. Install near outdoor unit with the arrow facing the outdoor unit, this is direction of flow.

Utility Saver Operation Communicating Mode Utility Curtailment is not available directly with the Observer™ Wall control. To accomplish curtailment with the Observer a daughter board kit must be used to convert the control signals to standard thermostat signals.

Utility Saver Operation Non-Communicating Mode The utility company provided relay should be wired in the Y2 thermostat lead. This allows a power utility to interrupt high stage compressor operations during peak load periods. If the utility requires control of the low stage compressor operation a second utility curtailment relay should be wired in the Y1 lead.

Low Ambient Cooling Operation Is not available for the 2 stage communicating or non communicating system at this time. Low ambient kits are not set up and not to be installed. Consideration may be given in future Observer™ software to allow this to be done. Single stage communicating and non communicating systems can apply low ambient cooling controls. See single stage training and literature. Considering if future may allow this in Observer software. ECM motors are used in outdoor units (19 SEER) which is why the external low ambient pressure switch cannot be used. If the UI has low ambient in software it will allow the UI communicating low ambient for future.

Diagnostics

Status Codes

Diagnostics LED on OD Board Green COMM LED1 will indicate successful communication Off until communication is established Amber STATUS LED2 to display operating mode or error conditions If multiple errors exist, the highest priority error will be flashed on circuit board Status (amber) light is read by series of short and long flashes. Example: code 74 7 short flashes followed by 4 long flashes.

High Voltage Monitoring Brown Out Detection (230V) Code 46 If line voltage drops below 187, a brown out condition is declared Operation is not allowed until voltage is 190 or higher for at least 4 seconds Unit is shipped with Brown Out Active Can be defeated if needed. Defeat by shorting forced defrost pins from power up with both OAT and OCT sensors removed. Status Code 6 disabled. Code 5 is active. Install instructions detail.

Observer™ Marketing Training