Gas fitting line Sizing.

Slides:



Advertisements
Similar presentations
COPPER PIPE SIZING PROGRAM ProVersion. PRO CALCULATOR WILL WORK ON PHONE OR PC (and offline) ENTER START PRESSURE say 40m=392.4 kPa ENTER NUMBER OF DWELLINGS.
Advertisements

Manual Set-Up for Density by Hydrometer Method ASTM D1298, D287, D6822 and IP160 Feb
Finally, a compressed air piping system so simple…it’s EZ!
AIR FLOW IN DUCTS Shaharin Anwar Sulaiman
1 Natural Gas Pipe Sizing. 2 Size all piping using this column (mains, branches, etc.). Procedure: Find the longest run from the gas meter to the farthest.
CHAPTER 24 PIPING DRAWING Instructor: M.Yaqub. Chapter 24 piping week# Steel and Wrought Iron Pipe Common use for water, steam, gas and oil. Up.
Spiral Condensors. Working Principle The Spiral Condensor consists of two sheets stainless steel strips which have been wounded from the centre.
OLYMPUS Collaboration Meeting Cooling Water David Rodríguez Piñeiro Mainz University OLYMPUS Collaboration Meeting DESY
Fluid Mechanics 06. Energy, Work and Power Work:- Work is force acting through a distance when the force is parallel to the direction of motion. Energy:-
M1M2M3M4M5M6 M10 M20 M30 M40 M50 M M1M2M3M4M5M6.
2006 Oct. 19 DES Project -- Vaidas Simaitis, University of Illinois1 DHE – Detector Head Electronics Monsoon 80mm Crate Heat Load.
Pipe Sizing Sizing Gas Pipe for Low-Pressure Systems
Assignment No. 1 [Grup 8] Figure below shows a portion of a hydraulic circuit. The pressure point B must be 200 psig when the volume flow rate is 60 gal/min.
Domestic Natural Gas Installations Marc Billington.
Water piping design.
Section 1 Dr.Hoda’s part Sheet 1: Calculating equipment cost Eng. Reda Zein.
NSTX TF Bundle & Center Stack Curing Oven Mike Viola Joe Rushinski Frank Jones April 14, 2003.
Unit: V-Flow Through Pipes. Flow Through Pipes  Major Energy Losses - Darcy-Weisbach Formula - Chezy’s Formula  Minor Energy Losses -Sudden expansion.
12-1 Copyright  2010 McGraw-Hill Australia Pty Ltd PowerPoint slides to accompany Puffett, Hossack, Stone, Burn & Miles, Gasfitting 2e Chapter 12 METERS.
Basic Home Plumbing.
COPPER PIPE SIZING PROGRAM Free Version. FREE CALCULATOR WILL WORK ON PHONE OR PC ENTER START PRESSURE say 40m=392.4 kPa ENTER NUMBER OF DWELLINGS.
HVACR116 – Trade Skills Longest length method.
ME414 Spring 2006 Design Project 2 Heat Exchanger Ugo Anyoarah Osinanna Okonkwo Vinay Prisad Daniel Reed.
EXAMPLE 27.1: A copper wire carries a current of 10 A. It has a cross- sectional area of 0.05 cm 2. Estimate the drift velocity of the electrons.
MECHANICAL ENGINEERING FOR SYSTEM BALANCE ASHRAE MEETING 2/15/2007 NORTHERN NEVADA CHAPTER 126 MATT BRENNAN, TBE.
HVACR116 – Trade Skills Pipe Sizing Sizing Gas Pipe for Low-Pressure Systems.
10-1 Copyright  2010 McGraw-Hill Australia Pty Ltd PowerPoint slides to accompany Puffett, Hossack, Stone, Burn & Miles, Gasfitting 2e Chapter 10 PIPE.
Full Scale Thermosyphon Design Parameters and Technical Description Jose Botelho Direito EN/CV/DC 19 November, th Thermosyphon Workshop.
Manual Density Business Today
Product Introduction January 2009
Friction Loss Tutorial Used in conjunction with the Friction Loss Check Sheet and any Irrigation Plan.
ME444 ENGINEERING PIPING SYSTEM DESIGN CHAPTER 4 : FLOW THEORY.
ME444 ENGINEERING PIPING SYSTEM DESIGN CHAPTER 11: STEAM PIPING SYSTEM (1)
4.0 Equipment Installation Aspects (Section 4.5 On-Rate for Fuel-Fired Equipment)
Pipe Clips.
7 February 2012 Annekathrin Frankenberger (HEPHY Vienna) Open CO 2 Cooling System at the beam test Belle II SVD-PXD Meeting.
CHEMCAD Seminar Transport and Storage John Edwards, P&I Design Ltd
MVD COOLING STATUS MVD COOLING PROJECT: CHOICE of COOLING FLUID,
ME444 ENGINEERING PIPING SYSTEM DESIGN
PIPING DRAWINGS C H A P T E R T W E N T Y- O N E.
PIPING DRAWINGS C H A P T E R T W E N T Y- O N E.
Plumbing system fundamental and design course
DZ01 – Marka D B E C B G A B C.
Sizing Group Vent, Stack , Stack vent
EXERCISES Two water reservoirs are connected by a pipe 610m of 0.3m diameter, f’=0.038 and the flow produced by the difference in water surface elevations.
Presented by.
Presented by.
ARAC/H/F Air-cooled water chillers, free-cooling chillers and heat pumps Range: kW.
CORAYVAC® Design and Layout
Pipe Fittings.
Designing DOT Exchange and Stationary Cylinder Installations
Mass and Energy Analysis of Control Volumes
N F G C r e v I s I o n s.
By: Brittany Watton & Jeff Philippart
The Basic Direct Expansion Refrigeration Cycle
Date of download: 3/4/2018 Copyright © ASME. All rights reserved.
N F G C r e v I s I o n s.
Detector Technology Group
Frese DPRV Introduction Introduction 2017.
Hot water Systems Heaters.
ME444 ENGINEERING PIPING SYSTEM DESIGN
ME444 ENGINEERING PIPING SYSTEM DESIGN
Hot Water Systems Cylinders and Systems.
XP PLUS Intro High Efficiency Circulating Water Heater
Tracer Applications.
ESS elliptical cryomodule
Boiler Safety Valve Regulations
Sizing and Product Code
Presentation transcript:

Gas fitting line Sizing

Natural / LP Gas fitting line Sizing Information Needed. Type of Gas = ? Natural / LPG Type of Gas Heat Value = ? Heating Value Mj/m³ & Relative Density (RD) Available Pressure at start of consumer piping The Gas Authority should be consulted to determine the maximum pressure drop Allowed in area. To minimise noise the maximum pressure drop should not exceed 10% of the operating pressure. Type A appliances minimum - inlet pressure Clause No. 4.2.4 Table 4.1 Natural Gas- minimum - inlet pressure 1.13 kPa / Min. Inlet Pressure LPG 2.75 kPa Pressure drop = ? 0.075kPa Natural gas / 0.25 LPG

Natural / LP Gas fitting line Sizing Information Needed. Type of Pipe = ? Copper / Steel /Plastic Mj/h each Appliance ? Appliance Data Plate Manufactures Information sheet Main Run = ? Measure plan

Natural Gas fitting line Copper HWS 30Mj/h Gas Appliance Fitting line sizing. Main run is from the meter connection /supply to the gas appliance furthest away. B 1m 1.5m 1m + 13m +1.5m +1m = 16.5m 13m Main run = 16.5m Main run = A B A 1m Meter connection/ Gas Supply

Gas fitting line Sizing Ex 1 Main Run = 16.5m Type of Gas = Natural Type of Pipe = Copper Pressure drop = 0.075kPa Mj/h each Appliance 30 Mj/h Place information into Pipe sizing Chart Check gas reg. AG601 Table F1 Natural gas sizing

Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 30 Gas Flow Mj/hr NominalSize DN A-B 30 Check gas reg. AG601 Table F1 Natural gas sizing

Length of straight pipe in metres TABLE F1 Pressure Drop of 0.075 kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 18 20 Main Run = 16.5 m next highest 18 m Mj/h = 30Mj/h next highest 67Mj/h Pipe sizing taken right to left 20mm

Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 30 20 Gas Flow Mj/hr NominalSize DN A-B 30 20 Check gas reg. AG601 Table F1 Natural gas sizing

Natural Gas fitting line Sizing. Job 2 Fitting line with branch. Copper tube.

Natural Gas fitting line HWS 30Mj/h Fitting line sizing. Main run is from the meter connection /supply to the gas appliance furthest away. C 1m D 1.5m 1m Cooker 26Mj/h 5m 10m 1m + 2m+10m+1.5m +1m = 15.5m B Main run = 15.5m A 2m 1m Main run = A - C Meter connection/ Gas Supply

Gas fitting line Sizing Ex 2 Main Run = 15.8m Type of Gas = Natural Type of Pipe = Copper Pressure drop = 0.075/kPa Mj/h each Appliance From Chart Place information into Pipe sizing Chart Check gas reg. AG601 Table F1 Natural gas sizing

Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 26 +30 = 56 Gas Flow Mj/hr NominalSize DN A-B 26 +30 = 56 B-C 30 B-D 26 Check gas reg. AG601 Table F1 Natural gas sizing

Length of straight pipe in metres TABLE F1 Pressure Drop of 0.075 kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 16 20 Main Run = 15.5 m next highest 16 m A-B Mj/h = 56Mj/h next highest 71Mj/h Pipe sizing taken right to left 20mm

Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 26 +30 = 56 20 Gas Flow Mj/hr NominalSize DN A-B 26 +30 = 56 20 B-C 30 B-D 26 Check gas reg. AG601 Table F1 Natural gas sizing

Length of straight pipe in metres TABLE F1 Pressure Drop of 0.075 kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 16 20 Main Run = 15.5 m next highest 16 m B-C Mj/h = 30Mj/h next highest 71Mj/h Pipe sizing taken right to left

Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 26 +30 = 56 20 Gas Flow Mj/hr NominalSize DN A-B 26 +30 = 56 20 B-C 30 20 B-D 26 Check gas reg. AG601 Table F1 Natural gas sizing

Length of straight pipe in metres TABLE F1 Pressure Drop of 0.075 kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 16 20 Main Run = 15.5 m next highest 16 m B-D Mj/h = 26Mj/h next highest 71Mj/h Pipe sizing taken right to left

Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN B-C B-D A-B Gas Flow Mj/hr NominalSize DN B-C B-D A-B 26 +30 = 56 20 30 20 26 20 Check gas reg. AG601 Table F1 Natural gas sizing

LPG fitting line Sizing. Job 1 Fitting line with branch.

LPG fitting line Main run = A - C Fitting line sizing. HWS 188Mj/h Fitting line sizing. Main run is from the Gas supply to the gas appliance furthest away. C 1m D 1.5m 1m Cooker 26Mj/h 5m 10.3m 1m + 2m+10.3m+1.5m +1m = 15.8m B Main run = 15.8m A 2m 1m Main run = A - C Gas Supply

Gas fitting line Sizing Ex 1 Main Run = 15.8m Type of Gas = LP Type of Pipe = Copper Pressure drop = 0.25kPa Mj/h each Appliance From Chart Place information into Pipe sizing Chart Check gas reg. AG601 Table F29 LP gas sizing

Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 26 +188 = 214 Gas Flow Mj/hr NominalSize DN A-B 26 +188 = 214 B-C 188 B-D 26 Check gas reg. AG601 Table F29 LP gas sizing

Length of straight pipe in metres TABLE F29 Pressure Drop of 0.25 kPa LP GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 26 19 13 9 57 38 30 27 24 22 21 20 81 54 43 36 84 28 64 25 15 212 142 113 96 281 76 69 223 60 725 491 390 331 659 262 240 504 208 1628 1104 879 747 1283 594 544 984 472 32 3155 2145 1709 1454 2186 1156 1061 1679 920 40 5358 3647 2909 2477 4974 1974 1810 3826 1571 50 12123 8271 6607 5631 9274 4493 4123 7143 3582 65 22519 15389 12305 10495 14936 8382 7694 11514 6689 16 15 Main Run = 15.8 m next highest 16 m A-B Mj/h = 214Mj/h next highest 223Mj/h Pipe sizing taken right to left 15mm

Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 26 +188 = 214 Gas Flow Mj/hr NominalSize DN A-B 26 +188 = 214 15 B-C 188 B-D 26 Check gas reg. AG601 Table F29 LP gas sizing

Length of straight pipe in metres TABLE F29 Pressure Drop of 0.25 kPa LP GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 26 19 13 9 57 38 30 27 24 22 21 20 81 54 43 36 84 28 64 25 15 212 142 113 96 281 76 69 223 60 725 491 390 331 659 262 240 504 208 1628 1104 879 747 1283 594 544 984 472 32 3155 2145 1709 1454 2186 1156 1061 1679 920 40 5358 3647 2909 2477 4974 1974 1810 3826 1571 50 12123 8271 6607 5631 9274 4493 4123 7143 3582 65 22519 15389 12305 10495 14936 8382 7694 11514 6689 16 15 Main Run = 15.8 m next highest 16 m B-C Mj/h = 188Mj/h next highest 223Mj/h Pipe sizing taken right to left 15mm

Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 26 +188 = 214 Gas Flow Mj/hr NominalSize DN A-B 26 +188 = 214 15 B-C 188 15 B-D 26 Check gas reg. AG601 Table F29 LP gas sizing

Length of straight pipe in metres TABLE F29 Pressure Drop of 0.25 kPa LP GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 26 19 13 9 57 38 30 27 24 22 21 20 81 54 43 36 84 28 64 25 15 212 142 113 96 281 76 69 223 60 725 491 390 331 659 262 240 504 208 1628 1104 879 747 1283 594 544 984 472 32 3155 2145 1709 1454 2186 1156 1061 1679 920 40 5358 3647 2909 2477 4974 1974 1810 3826 1571 50 12123 8271 6607 5631 9274 4493 4123 7143 3582 65 22519 15389 12305 10495 14936 8382 7694 11514 6689 16 10 Main Run = 15.8 m next highest 16 m B-D Mj/h = 26Mj/h next highest 64Mj/h Pipe sizing taken right to left 10mm

Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN A-B 26 +188 = 214 Gas Flow Mj/hr NominalSize DN A-B 26 +188 = 214 15 B-C 188 15 B-D 26 10 Check gas reg. AG601 Table F29 LP gas sizing

To Exit press button To continue press enter or Space bar key Fitting line with more then one branch

Natural Gas fitting line Sizing Job 3 Fitting line with more then one branch

Natural Gas fitting line 1m Cooker 26Mj/h Space heater 35Mj/h 1.m 6m F HWS 188Mj/h 3.5m D 1m 2.5m 1.5m C 1m 5m 10m 1m + 2m+5m+1m+2.5m +5m+1m = 17.5m B Main run = 17.5m A 2m 1m Main run = A - E Meter connection/ Gas Supply

Gas fitting line Sizing Ex 3 Main Run = 17.5m Type of Gas = Natural Type of Pipe = Copper Pressure drop = 0.075kPa Mj/h each Appliance From Chart Place information into Pipe sizing Chart Check gas reg. AG601 Table F1 Natural gas sizing

Length of straight pipe in metres TABLE F1 Pressure Drop of 0.075 kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 18 32 Main Run = 17.5 m next highest 18 m A-B Mj/h = 249Mj/h next highest 257Mj/h Pipe sizing taken right to left

Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN B-E C-F A-B Gas Flow Mj/hr NominalSize DN B-E C-F A-B 26 +35+188 = 249 32 B-C 35 +188 = 223 C-D 188 26 35 Check gas reg. AG601 Table F1 Natural gas sizing

Length of straight pipe in metres TABLE F1 Pressure Drop of 0.075 kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 18 32 Main Run = 17.5 m next highest 18 m A-C Mj/h = 223Mj/h next highest 257Mj/h Pipe sizing taken right to left

Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN B-E C-F A-B Gas Flow Mj/hr NominalSize DN B-E C-F A-B 26 +35+188 = 249 32 B-C 35 +188 = 223 32 C-D 188 26 35 Check gas reg. AG601 Table F1 Natural gas sizing

Length of straight pipe in metres TABLE F1 Pressure Drop of 0.075 kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 18 32 Main Run = 17.5 m next highest 18 m C-D Mj/h = 188Mj/h next highest 257Mj/h Pipe sizing taken right to left

Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN B-E C-F A-B Gas Flow Mj/hr NominalSize DN B-E C-F A-B 26 +35+188 = 249 32 B-C 35 +188 = 223 32 C-D 188 32 26 35 Check gas reg. AG601 Table F1 Natural gas sizing

Length of straight pipe in metres TABLE F1 Pressure Drop of 0.075 kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 18 20 Main Run = 17.5 m next highest 18 m B-E Mj/h = 26Mj/h next highest 67Mj/h Pipe sizing taken right to left

Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN B-E C-F A-B Gas Flow Mj/hr NominalSize DN B-E C-F A-B 26 +35+188 = 249 32 B-C 35 +188 = 223 32 C-D 188 32 26 20 35 Check gas reg. AG601 Table F1 Natural gas sizing

Length of straight pipe in metres TABLE F1 Pressure Drop of 0.075 kPa NATURAL GAS flow through COPPER PIPE (MJ/h) Norm Diam (DN) Length of straight pipe in metres 2 4 6 8 10 12 14 16 18 3 1 9 5 27 15 61 45 38 32 26 21 20 205 137 108 95 87 80 75 71 67 25 466 313 247 209 184 165 151 141 134 912 614 487 412 362 326 298 276 257 40 1559 1052 834 708 622 560 513 475 443 50 3562 2410 1915 1627 1432 1291 1182 1095 1024 65 6662 4516 3594 3055 2692 2428 2224 2065 1928 18 20 Main Run = 17.5 m next highest 18 m B-E Mj/h = 35Mj/h next highest 67Mj/h Pipe sizing taken right to left

Pipe Sizing Chart Pipe Section Mj/hr NominalSize DN B-E C-F A-B Gas Flow Mj/hr NominalSize DN B-E C-F A-B 26 +35+188 = 249 32 B-C 35 +188 = 223 32 C-D 188 32 26 20 35 20 Check gas reg. AG601 Table F1 Natural gas sizing

Gas fitting line sizing Sizing of Fitting Line is quite easily with the right information etc :- Type of Gas / Type of Pressure drop / Type of Piping Gas Reg. AG601 Questions ? B Makin 18/5/2005 RMIT