ONLOAD TAP CHANGING TRANSFORMER

Slides:



Advertisements
Similar presentations
Electrical Installation
Advertisements

 Without reference, identify principles relating to Fixed Radiological X-RAY PM with at least 70 percent accuracy.
Inspection & Preventive maintenance of breakers
E2 Motors and Motor Starting (Modified)
ADX 150 – Engine Repair ADX 170 – Climate Controls
Chapter 4 – Circuit Components
Traction Control of Electric Locomotives
Objective of the session.
Section 4: Electric Motors
Dynamic Resistance Measurement
Dry type transformers Zaragoza Accessories and options
Transformer.
DC Motor Drives Dr. Ahmad Harb.
Disconnect Switches There are many purposes for disconnect switches in substations and power lines. They are used to isolate or deenergize equipment for.
1 Lesson 3 Computer Protection Computer Literacy BASICS: A Comprehensive Guide to IC 3, 3 rd Edition Morrison / Wells.
Quality Service Providing Quality Performance.
Chapter 7 SYSTEM PROTECTION
Fuel Oil Systems Fuel Oil Systems consist of: Storage Tanks Pumps
Single Phase IEC and EATS Distribution Transformers
Mehran University Of Engineering & Technology, SZAB Khairpur Mirs Campus ENGR. AHSANULLAH MEMON LECTURER DEPARTMENT OF ELECTRICAL ENGINEERING MUCET KHAIRPUR.
CHAPTER 4 CPB 20004: Plant Utility n Maintenance
HVAC523 Circulator Pumps.
INTRODUCTION Definition:
Batteries The purpose of the battery is to act as a reservoir for storing electricity.
Transformer Taking the ratio of the two equations
Electrical Safety in Construction. Objectives In this course, we will discuss the following: Common electrical hazards Standards relating to those hazards.
Framed Canopy Fitting Instructions Contents – 6- Angled frame fixing brackets 1 x handle pack 6 x self drilling tech screws 3 keys 1x door 6 x coach screws.
PROGRAMMABLE LOGIC CONTROLLER (PLC) AND AUTOMATION
1 CXS490 - Pre-Engineered Fire Protection Systems Off-Road Vehicle Systems.
Zoning Hydronic Systems. Zone Control Divides the Space to be Heated 1.Each with its own heating needs and control systems 2.There are several reasons.
Embedded Design Using ARM For Strong Room Security System
Introduction to switchgears
Direct Hot Water. What Cold Water System is Pictured? What hot Water System is Pictured?
E2 Motors and Motor Starting (Modified)
Self Switching Power Supply. Introduction Self Switching Power Supply  Embedded system requires a regulated power supply.
Practical experience with the AD Stochastic Cooling Murphy’s Law R. Louwerse.
Single Phase Induction Motor Speed Control. Introduction Single Phase Induction Motor Speed Control  Induction motors are.
Auto turn off battery charger Auto turn off battery charger.
REDA Production Systems
GENERATORS A Large Piece of Equipment That Gets Ignored!
CLOSED LOOP SPEED CONTROL OF DC MOTOR WITH PWM TECHNIQUE
D.C. Machine & Transformer Topic: Instrument Transformer Electrical:-1 presented by: Jill Chauhan ( ) Chirag Agarawal ( )
Push Button Station and Relay
Piston Engine Propulsion Ignition. Ignition in a piston engine requires: Spark plugs Magneto Condensers Distributor Contact breakers electronic systems.
Valves.
CNC FEED DRIVES Akhil Krishnan G M.Tech 1. CONTENTS 1.Introduction 2.Requirements of CNC feed drives 3.Servo motor 3.1 Servo drive control 3.2 Components.
CNC FEED DRIVES.
VALVES IN PIPE LINES.
Protection and Relay Schemes
COMPRESSED AIR PRODUCTION USING VEHICLE SUSPENSOR for PNEUMATIC BRAKING SYSTEM with INTELLIGENT BRAKING APPLICATION(SEMI- AUTOMATED) BY VIDYAPUTRA.
Doble Power Factor Bushing Test
Sub Station.
APFC-03 Reactive Power Compensation Method & Settings
Single Phase Induction
Introduction of Eddy Current Brake Presented By :~ jayanti hazra.
dry-type transformers
Testing of Transformers
GUJARAT POWER OF ENGINEERING AND RESEARCH INSTITUTE (104)
A presentation on Measurement of Winding Resistance and Insulation Resistance of 3 Phase 11 kV/ 433 V, 16KVA Oil cooled type Transformer PRESENTED BY:
HIGH PERFORMANCE PRESSURE SYSTEMS.
HVI HIPOT TEST SET Pft sERIES.
Energy Conversion and Transport George G. Karady & Keith Holbert
Engineering Project Cable Management.
Components of Substation
TROUBLESHOOTING ELECTRIC MOTORS
Agenda Introduction of Protective Relays
FIGURE 31-1 Internal construction of an oil-cooled ignition coil
Topic 1: Cables and conductors
Custom Switch and Value Added Capabilities
Instruments & Electrical Measurements Lecture 4
Presentation transcript:

ONLOAD TAP CHANGING TRANSFORMER

ABSTRACT On-load tap-changers (OLTCs) are indispensable in regulating power transformers used in electrical energy networks and industrial applications. This project explains the technological developments of resistor-type OLTCs and reactor-type OLTCs. The general switching principles for OLTCs are discussed and OLTC applications are presented. Today’s OLTC design concepts, including the new generation of vacuum type OLTCs, are described. The vacuum switching technology used in OLTCs is the “state of the art” design now and in the foreseeable future. Examples of OLTC designs and the respective switching principles show the range of the usage of vacuum interrupters.

INTRODUCTION Power transformers equipped with on-load tapchangers (OLTCs) have been the main components of electrical networks and industrial applications for nearly 90 years. OLTCs enable voltage regulation and/or phase shifting by varying the transformer ratio under load without interruption. From the start of tap-changer development, two switching principles have been used for load transfer operation – the high-speed resistor- type OLTCs and the reactor-type OLTCs. Over the decades both principles have been developed into reliable transformer components which are available in a broad range of current and voltage applications.

SWITCHING PRINCIPLE The OLTC changes the ratio of a transformer by adding or subtracting to and turns from either the primary or the secondary winding. The transformer is therefore equipped with a regulating or tap winding which is connected to the OLT Simple changing of taps during an energized status is unacceptable due to momentary loss of system load during the switching operation . The “make (2) before break (1) contact concept”, is therefore the basic design for all OLTCs. The transition impedance in the form of a resistor or reactor consists of one or more units that bridge adjacent taps for the purpose of transferring load from one tap to the other without interruption or appreciable change in the load current. At the same time they limit the circulating current (IC ) for the period when both taps are used.

THE OPERATING CONDITION OF OLTC The storage ambient temperature of OLTC is from -25℃ to 40℃. The storage humidity of the OLTC should be no more than 85 percent. The service temperature of standard designed OLTC is -25℃ to 40℃ If the temperature exceeds the range of above (-25℃ to 40℃), please specify when ordering. To meet the ordering requirements and comply with the operating environment, if the requested service temperature is out of the range of -25℃ to 40℃, the material and accessories of the OLTC will be specially designed and selected. The non-perpendicularity of OLTC on the transformer with the ground level should not exceed 2% The space for mounting OLTC should be free from serious dust and other explosive and corrosive gases.

INSTALLATION METHOD OF OLTC 1. Put the diverter switch and tap selector of the tap changer separately on a level surface. 2. Remove the connecting screws (6×M12) between the diverter switch and the tap selector. 3. Remove the red painted dowel pin from the sliding connector of the tap selector's step-by-step Geneva wheel mechanism. Do not move the connector. 4. The conductor of the tap selector has been installed during factory delivery. 5. Lift the diverter switch and put it on the tap selector. Take care not to damage the sliding connector of the step-by-step Geneva wheel mechanism.

6. Tighten six M12 recessed cap screws between the supporting stand of the tap selector‘s Geneva wheel mechanism and cylinder bottom of the diverter switch. Pay attention to the perpendicularity of the diverter switch and tap selector. 7. Thoroughly clean the bottom surface of the tap changer head flange and the sealing surface of the mounting flange. Put an oil resistant sealing gasket on the mounting flange. 8. Lift the complete tap changer and carefully insert it into the transformer through the mounting hole on the transformer tank cover. Take care not to damage the terminals on the tap selector and corona rings on the diverter switch compartment. 9. Check the head position and its setting position. Secure the tap change head flange to the mounting flange. At last, remove the red painted dowel pin from the intermediate gear wheel connecter at the cylinder bottom of the diverter switch.

OPERATING TEST OF THE TAP CHANGER Mechanical operating test Before voltage is applied to the transformer, 5 complete cycles of mechanical operating test ( no less than 200 times) must be performed. There should be no damage to the tap changer and motor drive unit. The position indication of the motor drive unit, its remote position indication and the position indication of the tap changer should be the same. Both the mechanical and electrical limit protection should be reliable.   Final oil filling Final oil filling is done after the operating test of the tap changer. Before oil filling, loosen the bleeding screw on the suction pipe and the top cover of the tap changer. Use a spanner to pry up vent oil overflowing in on the top cover of tap changer.

ADVANTAGES - allows changes in voltage ratio without deenergizing the transformer  - if the application involves interconnecting generation, a transformer with on-load tap changing capability provides the ability to adjust both voltage magnitude AND reactive flow. Without on-load tap changing, only one of these can be controlled, and then not very well.  - provides finer control of voltage than would be possible with off- load taps 

DISADVANTAGES transformer is more expensive requires more maintenance transformer reliability suffers - load tap changer failures are far more frequent than failures of the transformer itself

CONCLUSION A conventional static resistance measurement can be used to check the winding as well as all of the fixed internal connections. In some cases, however, defects could not be detected using the standard winding resistance measurement [9]. Therefore, the DRM as a supplementary measurement has proven to be beneficial for analysing the switching process, and mobile contacts, of OLTCs on power transformers. By using the same test setup as for static resistance, the DRM function enables insight into the fast switching process of the diverter switch to detect mechanical wear and tear of contacts, leads and commutating resistors without additional wiring effort. As a result, the reliability of the OLTC assessment can be improved, maintenance costs can be reduced and most importantly, unexpected and expensive outages can be avoided.