Incandescent Light Bulb LUMEN DESIGN METHOD Where: N = E A F UF LLF N = number of lamps E = level of illuminance A = Area at working plane.

Slides:



Advertisements
Similar presentations
Sustainable Lighting Strategies
Advertisements

EGEE 102 – Energy Conservation And Environmental Protection Energy Efficient Lighting.
LAMPS (Chapter 3) Lamp efficacy, life, and color Incandescent
7 Artificial Lighting 人工照明
Lighting System Design
Professor Mark A. Comeau, AIA © Interior Environment Week 9 Lighting: High efficiency Day-lighting Occupancy & daylight sensing, programmable operations.
DRAFT BEE CODE - LIGHTING Prepared by Devki Energy Consultancy Pvt. Ltd. Vadodara
16469 Low Energy Building Design Lighting Cameron Johnstone Department of Mechanical Engineering
MEETING TC 4-15 “Road Lighting Calculations, Test Data and Measurement” 16 May 2005 / Leon.
CFL ENERGY EFFICIENCY LABELLING/ PUBLIC PROCUREMENT Presented at the workshop on “energy efficient procurement” Mumbai, September 20, 2005.
Management and Organisation of Electricity Use Energy Efficient Lighting Techniques Belgrade November 2003.
Key criteria for selecting an LED solution Marco Wendling Lietcorp GmbH.
16469 Lighting and Daylighting Design. Energy Efficient Lighting Lighting accounts for a significant portion of energy use in commercial buildings We.
Lighting Calculations
Why BoldPlay? Brilliant Design. Intuitive Engineering Innovation + Design = Performance Serious Energy Savings Ideal direct/indirect distribution maximum.
1) This classroom has _______. A)Too much lighting B)Not enough lighting C)About the right amount of lighting.
K. F. Chan (Mr.)ELEC LUMEN METHOD Utilization factor -- Ratio of flux received by reference plane to total rated lamp flux in the installation. Utilization.
Light Quantity Lighting Metrics Luminous Flux Illuminance
An enterprise of the WALDMANN GROUP © Herbert Waldmann GmbH & Co. KG MAIA TASK LUMINAIRE.
Lighting calculations
Electrical Lighting & Cable Selection D.K.Pathirana.
Kitchen & Bath Lighting. A good lighting design should: Look good – both people and design space Provide the proper amount of light in every room Be.
Photometric Data Photometry is the science of measurement of light.
Compact fluorescent light bulb Filed by: Gunter Franck Filing date: Oct 23, 1995 Issue date: Mar 17, 1998.
Artificial Lighting Design Task lighting for general purpose rooms involves the installation of light sources that will provide the optimum amount of.
FLUORESCENT LUMINAIRES Fluorescent Luminaires U.S. Department of Energy Rebuild America Business Partners And Lithonia Lighting.
Landscape for Deemed Lighting Workpapers Building Code and Voluntary Program Relationship Building Code Changes Driven by Big Vision Voluntary Program.
Lighting System A lighting system consists of : 1.Light sources 2.Luminaires (or fixtures) 3.Ballasts.
K. F. Chan (Mr.)ELEC INTERIOR LIGHTING DESIGN The basic aim of good lighting design should be to create a lighting installation that provides both.
Block Diagram. Computer Simulation Color Mixing.
1 Lighting Learning outcome from this topic, the student is able to – recognize the definitions and meanings for terms used in lighting – calculate lighting.
Chap 16-1 Light Fundamentals.
Chap 16-1 Light Fundamentals. What is Light? A transverse electromagnetic wave.
DAYLIGHT CALCULATIONS. Components of the Natural Light :  There are three separate components of the natural light that reaches any point inside a building:
Stacking Footballs How many footballs can you fit in a classroom?
ACOSHAPE Acoustic Lighting Case Study Document. Requirements General school areas such as; meeting rooms, offices, libraries and classrooms have to reach.
Department of Technical Education
Chapter 8 Quantity of Lighting © 2006 Fairchild Publications, Inc.
Department of Technical Education Andhra Pradesh
The School Of Forest Resources Building University Park, Pennsylvania Chris Hoyman The Pennsylvania State University Architectural Engineering Lighting/Electrical.
9EE605A.7to81 Department of Technical Education Andhra Pradesh Name Designation Branch Institute Year/Semester Subject Subject Code Topic Duration Sub.
Objectives Learn about lighting design.
Internal use only PLS India, Munish Peshin, September 2012, Reference Extendable Suspended Led luminaire with Up-Down lighting. 70 % Down-lighting and.
Lighting facts.  Lighting can be a big energy consumer in offices and production areas and experience shows that energy savings may be achieved - often.
Lighting systems in labs & offices1 Subject: By:a.Yousefvand.
LEVEL 4 ENERGY ASSESSOR TRAINING 8. Level 3 re-cap lighting and Power Factor Correction.
Power consumption is calculated in kW-Hr = Total Power x time of use
Illumination Devices Measurement Unit.
Beghelli.
Module 5 Lighting Calculations
ART 2640, Building Systems of Interior Environments Fall Semester 2016 Tuesdays & Thursdays 9:00-10:20 Grover Center E218 Matthew Ziff, Associate Professor.
LIGHTING IMPROVEMENT IN CUTTING STATION
Lux The lux (symbol: lx) is the SI unit of illuminance and luminous emittance, measuring luminous flux per unit area.[1] It is equal to one lumen per square.
METHODS OF ILLUMINANCE CALCULATION
CORE AREA K. F. Chan (Mr.) MEBS6002.
ILLUMINATION.
Introducing: the vertex
LUMEN METHOD E= N x n x ø x UF x MF A
Point-by-Point Factors
New Conventional AV.
Definitions Luminance:The amount of light reflected from or transmitted through a material. Measured in candelas/ft (candelas/m ). Perceived as brightness.
LED Bulbs vs. CFL Bulbs vs. Incandescent Bulbs
Technology in Architecture
can be used with current lighting fixtures
Objectives Learn about lighting design.
Construction Studies Resources
Announcement Filed trip is on Monday, May 6th from 8 to 9 AM
Announcement Next class: 15 minutes quiz
Ameri Energy Group SunShine II Simulations
Objectives Finish Lighting system design Daylighting.
Presentation transcript:

Incandescent Light Bulb

LUMEN DESIGN METHOD Where: N = E A F UF LLF N = number of lamps E = level of illuminance A = Area at working plane height F= Flux output of each lamp UF = Utilisation Factor LLF = Light Loss Factor N = E A F UF LLF From Guidance (eg CIBSE) Calculated Manufacturers’ literature By calculation or tables By calculation or tables

EXAMPLE A factory space measuring 40m by 12m by 4m in height requires a service illumination of 500 lux on the workbenches which are set 1m above the floor. The 65W tubular fluorescent lamps chosen have a luminous efficacy of 80lm/W. They are to be mounted on the ceiling in luminaires which have a DLOR of 50%. The room reflectances are 0.5 for the ceiling and 0.3 for the walls; the initial light loss factor is 0.7. Using the lumen design method to calculate the number of lamps required and suggest a suitable layout for the fittings.

E = 500 lux A = 40m x 12m = 480 m2 F = 65 W x 80 lm/W = 5200 lumens N = E A F UF LLF E = 500 lux A = 40m x 12m = 480 m2 F = 65 W x 80 lm/W = 5200 lumens LLF = 0.7 UF = (next slide…….)

UF First we need to calculate the Room Index (RI) RI = L W Hm (L + W) Where: L = length of room W = width of room Hm = mounting height of luminaire above working plane RI = 40 x 12 3 (40 + 12) RI = 3

0.46

E = 500 lux A = 40m x 12m = 480 m2 F = 65 W x 80 lm/W = 5200 lumens N = E A F UF LLF E = 500 lux A = 40m x 12m = 480 m2 F = 65 W x 80 lm/W = 5200 lumens LLF = 0.7 UF = 0.46 N = 500 x 480 5200 x 0.46 x 0.7 N = 144 lamps

144 lamps Suggested layout = 9 rows of 16 luminaires Check spacing using Smax = 1.5 x Hm Smax = 1.5 x 3 = 4.5 m So the suggested layout is satisfactory provided that the distance between lamps is not greater than 4.5m.

40m I I I I I I I I I I I I I I I I 12m

I I I So, 40m with 16spacings = 2.5m each space This is well below the Smax of 4.5 m 12m with 9 spacings = 1.33m each space I I I HALF SPACE HALF SPACE 1 SPACE 1 SPACE This is well below the Smax of 4.5 m 1 SPACE Therefore this layout should work. 1 SPACE

EXAMPLE A workshop is 12m by 6m by 4m high and has workbenches 1m high. Discharge lamps, each with an output of 3700lm, are to be fitted in aluminium industrial reflectors at ceiling level. The surfaces have reflectances of 0.7 for the ceiling and 0.5 for the walls. The light loss factor is 0.7. The illuminance required is 400 lux. Find the utilisation factor for the room Calculate the number of lamps required

EXAMPLE A classroom with an area 10m by 6m is illuminated by 18 tubular fluorescent lamps, where each lamp is 60W with a luminous efficacy of 80lm/W. The utilisation factor is 0.46 and the light loss factor used is 0.8. Calculate the average illuminance in the classroom.

EXAMPLE A lecture room which is 15m long, 10m wide and 4m high is to be illuminated by ceiling mounted luminaires each housing three compact 20 watt fluorescent lamps. Calculate the number and spacing of luminaires required if a minimum illuminance of 300 lux is required on the working plane (desk surface) which is 0.8m above the floor. Ceiling reflectance 0.7, wall reflectance 0.1 Lamp efficiency = 40 l/w LLF = 0.8 Max spacing to height ratio = 1.5