Session 13 System Protection

Slides:



Advertisements
Similar presentations
Bonding and Grounding What? Why? How?
Advertisements

Electrical Installation
BS7671 Formula and Tips.
1 CNS/GSS/2008/M1 1 Module 1 Basic Terminologies and Characteristics of Switchgear.
FIRE PUMP ELECTRICAL CONFIGURATIONS UNDER 600 VOLTS.
CIRCUIT ARRANGEMENT (Note: All the mentioned tables in this course refer to, unless otherwise specified, Low Voltage Electrical Installation Handbook,
EET Survey of Electronics
Proposed Design and the Operation of a Disconnecting Device for Small EG Installations Prepared by Hendri Geldenhuys.
During a mains supply interruption the entire protected network is dependent on the integrity of the UPS battery as a secondary source of energy. A potential.
Electrical Safety Testing of Electrical Installations and the verification of Electricians Test Tools Michael Bailey Transmille Ltd NCSLi 2014Transmille.
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE PV APPLICATIONS CODES AND STANDARDS EMERGENCY RESPONSE.
1. Presentation Overview  Solar Industry Overview  Intro into Solar Photovoltaics  Types of PV Systems  Solar Product Offering –Solar Combiner Boxes.
Circuit Protection Electrical circuits require protection to prevent fire or electrocution in the event of a fault. There are two main types of circuit.
EKAS Disconnect & Reconnect UEE31307 Certificate III in Refrigeration and Air Conditioning Stage 2A Units: UEENEEPOO1B Chris Hungerford Sunday,
Physiological Effects of Electricity on Human Body by Mohd Yusof Baharuddin.
Copyright 2005 Ted "Smitty" Smith Two Minute Drill Number Three Improving your skill in code Look Up Increasing Speed Drill.
Protection against Electric Shock (Note: All the mentioned tables in this course refer to, unless otherwise specified, Low Voltage Electrical Installation.
Electrical Installation 2
Equipment Use In Occupancies  A receptacle shall not be grouped or ganged in enclosures with other receptacles unless they are so arranged so that voltage.
Dimensioning and Protection of PV Plants with examples of design
Electrical Safety in Construction. Objectives In this course, we will discuss the following: Common electrical hazards Standards relating to those hazards.
MAINS ELECTRICITY. Specification Electricity Mains electricity understand and identify the hazards of electricity including frayed cables, long cables,
©Ted “Smitty” Smith This speed drill focuses on subjects that will be required for the journeyman and masters examination arranged by chapter of.
Solar Energy Technology Science Summer Camp Session 9: Fri 9:00 AM - 12:00 N : Field trip to Energy Masters and Installing/Commissioning the System.
PORTABLE & TRANSPORTABLE ELECTRICAL EQUIPMENT. Legal Requirement and References Abu Dhabi RSB Electrical Regulations - makes reference to the need to.
Introduction to switchgears
SERVICE ENTRANCE EQUIPMENT
PV System Design and Installation LO 10 Performance Analysis and Troubleshooting.
ELECTRICAL INSTRUMENTS ( service and utilization )
Chapter 3 PHYSICAL INJURY AND CONTROLS 3.2 Electrical Safety
SYNERGY INSTITUTE OF ENGINEERING AND TECHNOLOGY
Creating sustainable change through education, communication and leadership© 2016 GSES P/L Training Consulting Engineering Publications Inspections of.
UNIT-5. ELECTRICAL SAFETY, WIRING & INTRODUCTION TO POWER SYSTEM
4.0 DOMESTIC ELECTRICITY Domestic electricity is that electricity which is supplied to homes under specific conditions of current and voltage. Voltage,
Lesson 4: Series DC Circuits and Kirchhoff’s Voltage Law (KVL)
Sub Station.
PROTECTION AGAINST INDIRECT CONTACT
EV DOMESTIC CHARGING UNIT
PV Array DC Isolator Rating
SUB-STATIONS.
2011 Changes Two Minute Drill
AS3000:2017 Changes Alterations Additions and Repairs
ELECTRICAL INSTALLATION AND MAINTENANCE (EIM) 5 INSTALL ELECTRICAL PROTECTIVE DEVICES FOR DISTRIBUTION, POWER, LIGHTING, AUXILIARY, LIGHTNING PROTECTION.
Personal Protective Equipment
AFCI Protection: AFCI Receptacles and the NEC
Installation And Estimation of Service Connection
Engineering Project Cable Management.
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE
ELECTRICAL POWER-II Electrical engineering sixth semester
Calculations: Transformers and Service Conductor Calculations
EET 323 – Electrical System Design Lecture 4: Wiring Devices
Smitty’s Two Minute Drill #1: Feeders and Branch Circuits
Sizing Methodologies • Sizing Calculations
Smitty’s Two Minute Drill Photovoltaic Systems
Overcurrent Protection— Fuses and Circuit Breakers
EET 323 – Electrical System Design Lecture 9: Grounding
EE-4TH SEMESTER ESTIMATING AND COSTING.
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE
Safety Meeting Topics Standby Generator Safety
A. Touching both terminals with the hands can cause electrical shock
MAINS ELECTRICITY.
Electrical components and systems
Electrical components and systems
Dominion Energy South Carolina: Solar Equipment Requirements
Fluid Power System Electrical Control
Presentation transcript:

Session 13 System Protection Grid Connect Session 13 System Protection J.P. Teasel version 12/11/2011.1

System Protection is designed to protect cabling & PV modules Grid Connect Session12 System Protection System Protection is designed to protect cabling & PV modules PV modules generate current in relation to the solar irradiance available in the installation plane. PV modules are a ‘current limited ‘power source (irradiance available to them is finite) However damaging fault currents may be generated in the PV array i.e. shading causing a single module/ string not to generate current or an earth fault If enough cells are hard shaded, the module will not convert any energy and will, in fact, become a tiny drain of energy on the entire system. J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection What part of the Grid connected PV System is considered to be prescribed electrical installation work? (also see next slide) Those parts of the generation system operating at or above 120 Volt dc, cables installed between panels and between the array and inverter and the ac cables installed between the inverter and the switchboard to which the generation system is connected along with all the required isolation and protection devices, are prescribed electrical installation work. J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection What part of the Grid connected PV System is considered to be prescribed electrical installation work? (continued) . For the purpose of section 45 of the Electricity Safety Act 1998, prescribed electrical Installation work means work on all or any part of the following electrical installations if they ordinarily operate at low voltage or a voltage exceeding low voltage. (f) Wiring systems, switchgear, control gear and accessories installed to provide control and protection of generation systems (excluding stand alone power systems with a power rating that is less than 500 volt-amperes) J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection The following activities are considered to be prescribed electrical installation work; Adding panels to an existing solar grid connected PV where the open circuit voltage (Voc Array) exceeds Extra Low Voltage. Upgrading the inverter due to increase in generation capacity The replacement of one component part of prescribed electrical installation work ‘like for like‗ such as an inverter or isolator can be entered on a non-prescribed certificate without the mandatory inspection. Reference – Electricity Safety (Installations) Regulations 2009 – Regulation 238(3) J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection Voltage Differences in potential normally existing between conductors and conductors and earth as follows: Extra Low Voltage: not exceeding 50 V ac or 120 V ripple-free dc Low voltage: Exceeding extra-low voltage, but not exceeding 1000 V ac or 1500 V dc High Voltage: Exceeding Low-voltage. Reference - AS/NZS 3000:2007 Amd1 Clause 1.4.98 Voltage J.P. Teasel version 12/11/2011.1

What is Class II equipment (double insulated) also see next slides1/4 Grid Connect Session12 System Protection What is Class II equipment (double insulated) also see next slides1/4 Equipment in which protection against electric shock does not rely on basic insulation only, but in which additional safety precautions such as double insulation or reinforced insulation are provided, there being no provision for protective earthing or reliance upon installation conditions. Equipment may be one of the following types: abc . J.P. Teasel version 12/11/2011.1

What is Class II equipment (double insulated) slide2/4 Grid Connect Session12 System Protection What is Class II equipment (double insulated) slide2/4 : (a) Equipment having durable and substantially continuous enclosures of insulating material which envelops all metal parts, with the exception of small parts, such as nameplates, screws and rivets, which are isolated from live parts by insulation at least equivalent to reinforced insulation; such equipment is called insulation-encased Class II equipment. (b next slide)…………. J.P. Teasel version 12/11/2011.1

What is Class II equipment (double insulated) continued…………. Slide3/4 Grid Connect Session12 System Protection What is Class II equipment (double insulated) continued…………. Slide3/4 (b) Equipment having a substantially continuous metal enclosure, in which double insulation is used throughout, except for those parts where reinforced insulation is used, because the application of double insulation is manifestly impracticable; such equipment is called metal-encased Class II equipment. (c) Equipment that is a combination of the types described in Items (a) and (b). see next slide NOTES: J.P. Teasel version 12/11/2011.1

What is Class II equipment (double insulated) continued…………. Slide4/4 Grid Connect Session12 System Protection What is Class II equipment (double insulated) continued…………. Slide4/4 NOTES: 1. The enclosure of insulation-encased Class II equipment may form part of the whole of the supplementary insulation or of the reinforced insulation. 2. If the equipment with double insulation or reinforced insulation throughout has an earthing terminal or earthing contact, it is considered to be of Class I construction. 3. Class II equipment may be provided with means for maintaining the continuity of protective circuits, insulated from accessible conductive parts by double insulation or reinforced insulation. 4. Class II equipment may have parts operating at SELV Reference – AS/NZS 5033 Clause 1.4.8 Class II equipment J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection What is a separated circuit? Separated low voltage A low voltage system that is electrically separated from earth and from other systems in such a way that a single fault cannot give rise to the risk of electric shock ELECTRICAL SEPARATION (ISOLATED SUPPLY) The expression ‘electrical separation‘ has the same meaning as isolated supply‘. ‘Electrical separation‘ is used throughout this document. J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection Electric Shock 1/2 Several methods of protection against electric shock arising from indirect contact are recognised by Clause 1.5.5 of AS/NZS 3000:2007. These methods include that of protection by electrical separation of the supply. Protection by electrical separation is an alternative to other recognised methods and is intended, in an individual circuit, to prevent shock current through contact with exposed conductive parts that might be energized by a fault in the basic insulation of that circuit. See next slide J.P. Teasel version 12/11/2011.1

Electric Shock cont… 2/2 Grid Connect Session12 System Protection Protection by electrical separation shall be afforded by compliance with Clauses 7.4.2 to 7.4.4, of AS/NZS 3000:2007 and with — Clause 7.4.5 of AS/NZS 3000:2007 for a supply to one item of equipment; or (b) Clause 7.4.6 of AS/NZS 3000:2007 for a supply to more than one item of equipment. NOTE: Figure 7.7 of AS/NZS 3000:2007 provides an illustration of a separated supply to single and multiple items of equipment. Reference – AS/NZS 3000:2007 Clause 7.4 J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection AS/NZS5033: 2.4.3 PV strings Where there are more than Np parallel connected strings, fault current protection shall be installed unless the array is ELV and— (i.e. there are more than 3 strings) the PV modules are mounted in such a way and location that an arc or molten metal coming out of the back of any of the PV modules shall not result in property damage or risk to the lives of people or animals; or (b) the PV modules are of a type which prevents any molten metal coming out of the back of the module. J.P. Teasel version 12/11/2011.1

AS/NZS5033: 2.4.3 PV strings Grid Connect Session12 System Protection The rated trip current (I trip) of fault current protection devices for PV strings shall be as specified by the PV module manufacturer. If the manufacturer does not give any recommendation, Itrip shall be determined by the following formula: 1.25 × I sc mod ≤ I trip ≤ 2 ×I sc mod (in english the circuit breaker or fuse will be of a rating between these values) J.P. Teasel version 12/11/2011.1

String fuse protection: When is it required & when not? System Protection Grid Connect Session13 5.5A String fuse protection: When is it required & when not? Example Module Sunshine Model S185 Isc 5.5A Maximum series fuse rating 15A Max fault current 5.5A No fault protection required Faulty Shaded module Output current 5.5A 11A Max fault current 11A No fault protection required Faulty Shaded module Output current 5.5A Output current 5.5A 16.5A Max fault current 16.5A fault protection required Faulty Shaded module Output current 5.5A Output current 5.5A Output current 5.5A Output current 5.5A J.P. Teasel version 12/11/2011.1

‡‡ ‡ ‡‡‡ Grid Connect Session12 System Protection AS/NZS 5033:2005 Clause 3.4.1(table 3.1) String Cable sizing No downstream fault current protection device therefore cable must carry min. current 1.25 x Isc mod x(no. of parallel strings -1) 1.25 x 5.5 x (3-1) = 13.75A min (13.75A< Max.series fuse rating = 20A) Isc=5.5A Voc = 44.5V Imp= 4.95A Vmp = 35.4V Pmp = 175W Max.series fuse rating = 20A ‡‡ ‡ ‡‡‡ AS/NZS 5033:2005 Clause 2.4.1 No of string fault current protection required Disconnection means still required Clause 2.5.3 Np = max. series fuse rating/Isc=20/5.5= 3.6 round up Np =4 J.P. Teasel version 12/11/2011.1

‡‡ ‡‡‡ ‡‡ ‡‡‡ Grid Connect Session12 System Protection AS/NZS 5033:2005 Clause 3.4.1(table 3.1) String Cable sizing must carry current of protective device i.e. 10A 1.25 x 5.1 x (5-1) = 25.5A min which exceeds max. series fuse rating of 20A fault current protection device required 10A was chosen carry min. current 1.25 x Isc mod Isc=5.1A Voc = 44.2V Imp= 4.7A Vmp = 35.2V Pmp = 165W Max.series fuse rating = 20A ‡‡ ‡‡‡ Np = max. series fuse rating/Isc=20/5.1= 3.9 round up Np =4 String cable sizing/ fault protection device ‡‡ ‡‡‡ AS/NZS 5033:2005 Clause 2.4.3 & 2.5.3 Number of strings greater than Np (we calculated 4) String fault current protection &disconnection required each string Single pole floating double insulated Rated trip current protection device must be between 1.25 x Isc mod & 2 x Isc mod 1.25 x5.1 =6.375 &2x 5.1 = 10.2 10A ok J.P. Teasel version 12/11/2011.1

‡‡ ‡‡‡ ‡‡ ‡‡‡ Grid Connect Session12 System Protection AS/NZS 5033:2005 Clause 3.4.1(table 3.1) PV Array Cable sizing 1.25 x Isc string 1.25x [( 5.1 x (5-1)) = 25.5A] =31.9A Isc=5.1A Voc = 44.2V Imp= 4.7A Vmp = 35.2V Pmp = 165W Max.series fuse rating = 20A ‡‡ ‡‡‡ ARRAY cable sizing/ fault protection device ‡‡ ‡‡‡ AS/NZS 5033:2005 Clause 2.4.5 No fault current protection required on the PV array cable-there are no batteries Disconnection still required Clause 2.5.3 J.P. Teasel version 12/11/2011.1

‡‡ ‡‡‡ ‡‡ ‡‡‡ Grid Connect Session12 System Protection AS/NZS 5033:2005 Table (2.3) String Disconnection means A readily available disconnection device both positive & negative legs) Isc=5.1A Voc = 44.2V Imp= 4.7A Vmp = 35.2V Pmp = 165W Max.series fuse rating = 20A ‡‡ ‡‡‡ String & array fault protection /disconnection ‡‡ ‡‡‡ AS/NZS 5033:2005 Table 2.3 Double pole, readily available, load breaking disconnection device lockable in the off position J.P. Teasel version 12/11/2011.1

‡‡ ‡‡‡ ‡‡ ‡‡‡ Grid Connect Session12 System Protection AS/NZS 5033:2005 Table (2.3) String Disconnection means A readily available disconnection device both positive & negative legs) Can be achieved by plug/socket/ or by virtue of using the DC circuit breaker Isc=5.1A Voc = 44.2V Imp= 4.7A Vmp = 35.2V Pmp = 165W Max.series fuse rating = 20A ‡‡ ‡‡‡ String & array fault protection /disconnection ‡‡ ‡‡‡ AS/NZS 5033:2005 Open circuit voltage is low voltage (LV) requires separation into ELV segments J.P. Teasel version 12/11/2011.1

Reference Array String LV Strings Sub Array Grid Connect Session12 System Protection Location Protection Description Protection Device Check Protection Size & Guild lines Reference String Fault Current Protection Device Fuse/ circuit breaker Np. No. of strings If Np<No. of strings 1.25x Isc mod≤ Itrip≤ 2x Isc mod If Np is greater No of string Not required AS/NZS 5033:2005 Clause 2.4.1, 2.4.3 Cable Disconnection Device Switch ELV or LV Must have the same rating as the cable Readily available Clause 2.5.3/2.5.4 LV Strings Disconnection Measure LV Segmentation to ELV Plug &Socket String voltage > 120 Vdc Sub Array LV array Clause 2.4.3/2.5.3 Sub disconnection Device LV: Readily available load breaking disconnection device Clause 2.5.3 Array Array Disconnection Device Readily available load breaking disconnection device lock in off position Must be rated same as cable J.P. Teasel version 12/11/2011.1

Schematic diagram of a Grid Connected PV system Session12 System Protection MAIN SWITCHBOARD PV Array Load isolator d.c. isolator Inverter AC isolator Solar supply isolating switch MSB main switch NET METERING Service fuse x x x x LOCAL SERVICE RULES LOCAL SERVICE RULES Ccts no RCD /with RCD protection Schematic diagram of a Grid Connected PV system ) NB: System Protection derived from AS/ NZS 50332005 J.P. Teasel version 12/11/2011.1

Standards and regulations for installation Grid Connect Session12 System Protection Standards and regulations for installation The following standards and regulations shall be complied with where applicable. Electrical Safety Act 1998 Electricity Safety (Installations) Regulations 2009 NSW Service and Installation Rules 2011 AS/NZS 3000:2007 Wiring Rules AS/NZS 3008.1.1:2009 Electrical Installations-Selection of cables AS/NZS 4777.1:2005 Grid connection of energy systems via Inverters –Installation requirements AS/NZS 4777.2:2005 Grid connection of energy systems via Inverters –Inverter requirements AS/NZS 4777.3:2005 Grid connection of energy systems via Inverters –Grid protection requirements AS/NZS 5033:2005 Installation of photovoltaic (PV) arrays J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection There are two types of protection devices required in PV systems for safety Over-current protection Disconnection means (which can be either :Load-breaking or non load breaking) Polarised or non polarised Over-current protection and disconnection devices requirement need assessing at the following system levels String Sub-array array J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection PV ARRAY DIAGRAM: CASE WHERE ARRAY NOT DIVIDED INTO SUB-ARRAYS J.P. Teasel version 12/11/2011.1

CASE WHERE ARRAY IS DIVIDED INTO SUB-ARRAYS Grid Connect Session12 System Protection PV ARRAY DIAGRAM: CASE WHERE ARRAY IS DIVIDED INTO SUB-ARRAYS J.P. Teasel version 12/11/2011.1

Fault current protection Grid Connect Session12 System Protection Fault current protection The need for current protection in PV array occurs when other strings in the array feed current into a single string of the array is affected by shading or an earth fault Current feed back from other strings in the array may be grater than the current which can safely handled by modules in that string some manufactures specify ‘maximum series fuse rating’ also known as ‘reverse current rating’ this is not an actual fuse within the module It is the maximum current that can pass through the module with damaging it J.P. Teasel version 12/11/2011.1

How to determine when Fault Current Protection is required Grid Connect Session12 System Protection How to determine when Fault Current Protection is required It is required, whenever the combined short circuit current of all the strings in the array , minus one, is greater that the reverse current rating of the models in the remaining string Isc x (No of strings -1) ≥ Module Reverse Current Rating J.P. Teasel version 12/11/2011.1

How to determine Np Grid Connect Session12 System Protection where Np is the maximum number of parallel strings without protection No = I mod reverse if not a whole round up Isc mod Worked example :If a PV module has a reverse current rating of 15a and a short circuit current of 5.5 A then Np =15/5.5 = 2.27 therefore round up to 3 AS/NZS 5033 2.4.1 Number of parallel strings without overcurrent protection The maximum number of strings connected in parallel without overcurrent protection shall be nP where nP is related to the PV modules reverse current rating and is given by Table 2.1 unless the conditions of Clause 2.4.3 apply. If IMOD REVERSE is not obtainable from the manufacturer of the PV modules, nP shall be taken as 1 J.P. Teasel version 12/11/2011.1

String fuse protection: When is it required & when not? System Protection Grid Connect Session13 5.5A String fuse protection: When is it required & when not? Example Module Sunshine Model S185 Isc 5.5A Maximum series fuse rating 15A Max fault current 5.5A No fault protection required Faulty Shaded module Output current 5.5A 11A Max fault current 11A No fault protection required Faulty Shaded module Output current 5.5A Output current 5.5A 16.5A Max fault current 16.5A fault protection required Faulty Shaded module Output current 5.5A Output current 5.5A Output current 5.5A Output current 5.5A J.P. Teasel version 12/11/2011.1

LOCATION OF FAULT CURRENT PROTECTION DEVICES Grid Connect Session12 System Protection LOCATION OF FAULT CURRENT PROTECTION DEVICES Fault current protection devices, where required by Clauses 2.4.2 through 2.4.5 for PV strings, PV sub-arrays and PV arrays, shall be at the load (downsteam) end of those cables. NOTE: Because PV strings/arrays are inherently current limited, the source of fault current is likely to be from other parallel connected strings/sub-arrays. Hence, the protection needs to be near the parallel connection point (i.e. the load end) Source: http://www.solarbos.com/products.php J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection Do I need to install an isolating device at the PV array location that can isolate the dc cable to the inverter? Also see next slide exceptions Yes - each electricity generation system shall be provided with an isolating switch, in accordance with Clause 2.3.2.2 of AS/NZS 3000:2007, that — shall be installed adjacent to, or on, the electricity generation system so that a person operating the switch has a clear view of any person working on the electricity generation system; see next slide J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection Do I need to install an isolating device at the PV array location that can isolate the dc cable to the inverter? Cont……… and shall be d.c. rated, double pole, non polarised; and may be combined with overcurrent protection required by Clause 7.3.5.1 of AS/NZS 3000:2007; and shall be under manual control only; and shall not be capable of being overridden or bypassed by programmable control systems or the like. Also see next slide exceptions J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection Do I need to install an isolating device at the PV array location that can isolate the dc cable to the inverter? Continued Exception: The internal isolation arrangements for systems, in accordance with AS 4509.1 or AS 4777, are deemed to satisfy these requirements. Reference - Clause 7.3.4 of AS/NZS 3000:2007 Each dc solar supply cable shall be capable of being isolated at the PV array and be appropriately rated (rated for current, voltage and IP). The installation of the isolation device is mandatory for emergency services to disconnect the supply under emergency conditions. Reference- Victorian Electrical Inspectors Guidance notes March-2010 J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection 2.5.3 Disconnection device requirements Table 2.3 specifies disconnection device requirements for PV array installations. Table 2.4 specifies the location of these devices, when required. J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection Do I need to provide isolation for the PV array (dc) cable at or near the inverter? Yes - it requires an appropriately rated dc device unless the inverter is physically integral with the energy source. Isolation of the inverter from the energy source – an isolation device shall be provided between the energy source and the inverter unless the inverter is physically integral with the energy source. This device shall comply with the requirements for devices for isolation and switching in AS/NZS3000 and be capable of safely breaking voltage and current under both normal and fault conditions. Reference AS/NZS 4777.1 -2005 Clause 5.4 J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection DC isolation & switching devices – general requirements (also see next slide) All switching devices shall comply with all the following requirements: Be rated for dc use. (b) Have a voltage rating equal to, or greater than, 1.2 X VOC ARRAY. (c) Not have exposed metallic live parts in the connected or disconnected state. In addition non-load-breaking switches shall have a current rating equal to, or greater than, their associated fault current protection device, or in the absence of such device, have a current rating equal to, or greater than, the required current carrying capacity of the circuit to which they are fitted. Cont…next silde J.P. Teasel version 12/11/2011.1

DC isolation & switching devices – general requirements (continued) Grid Connect Session12 System Protection DC isolation & switching devices – general requirements (continued) AS/NZS5033 Clause 4.3.3 Current breaking devices In addition circuit breakers and any other load breaking disconnection devices used for protection and/or disconnecting means shall comply with all the following requirements: a) Not be polarity sensitive (as fault currents in a PV array may flow in the opposite direction to normal operating currents) except for the PV array main switch in systems without batteries. (see next slide b &c ) J.P. Teasel version 12/11/2011.1

DC isolation & switching devices – general requirements (continued) Grid Connect Session12 System Protection DC isolation & switching devices – general requirements (continued) (b) Be rated to interrupt full load and prospective fault currents from the PV array and any other connected power sources (e.g. batteries, generators and the grid). (c) When fault current protection is incorporated, the trip current shall be rated according to fault current protection requirements. also see next slide J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection The PV Array double-pole isolator specified on the dc side of the inverter is required to be a load breaking isolator, but many installers are using double pole dc circuit-breakers because they are readily available. These dc circuit-breakers can be polarized or non-polarized. It is anticipated that the new version of AS/NZS 5033 will not allow polarized breakers to be used. Additional Information is available from ‘Correct wiring of double pole dc Circuit-breakers‘ - published by Global Sustainable Energy Solutions. J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection It is essential that polarized breakers are wired correctly as they are a potential fire hazard when incorrectly wired. Reference- Global Sustainable Energy Solutions –Inspecting the PV Array dc Isolators (Circuit Breakers) J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection Do I need to link the dc circuit breakers when there are multiple dc supplies feeding into an inverter? It is desirable to link the circuit breakers for the isolation of supply, but it‘s not mandatory. If the circuit breakers are not linked there is a possibility that there is a voltage on the load side of the circuit breaker that is turned off. A sign advising users to isolate all dc supplies is required. J.P. Teasel version 12/11/2011.1

Are all inverters suitably IP rated for outdoor installation? Grid Connect Session12 System Protection Are all inverters suitably IP rated for outdoor installation? No, not all inverters are suitable to be installed where they exposed to weather. Caution - Inverters with an IP rating can be similar in appearance to those without an IP rating. Check the specifications supplied with the inverter J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection Is there a minimum or maximum height for the installation of an inverter? Yes, the maximum height to the top of the inverter is 2 metres above ground, floor or platform, the minimum height to the bottom of the inverter shall not be less than 500mm from ground, floor or platform. Appears to be a Victorian install rule J.P. Teasel version 12/11/2011.1

2. A solar (PV) array is a current limited source. Grid Connect Session12 System Protection Do I need to provide isolation for the ac circuit at or near the inverter? Yes, a device that provides isolation is required to be mounted immediately adjacent to the inverter. Exception: the above device is not required to be installed if the inverter is mounted within direct view and within 3 metres of the switchboard. Where the inverter is not in close proximity to the switchboard it supplies, some form of overcurrent protection shall be provided to prevent excessive current flow through the cables feeding into the switchboard unless the inverter is supplied from a current limited source. NOTES: 1. Typically cable lengths of 3 m would be considered as close proximity (close proximity means within 3 metres and within direct view of the switchboard). 2. A solar (PV) array is a current limited source. 3. The preferred location for this overcurrent protection device is at the inverter end of the cable. Reference AS/NZS 4777.1:2005 Clause 5.3.5 &5.4 J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection How should I connect the inverter energy system (generator) to the installation? The inverter energy system shall be connected by fixed wiring to a dedicated circuit on a switchboard. The inverter energy system should be connected directly to the main switchboard. In installations where this is not possible or not desirable, the inverter energy system should be connected to the distribution board located physically nearest to the inverter, and the main switchboard. All intermediate distribution boards shall be appropriately labelled in accordance with Clause 5.5 of AS/NZS 4777.1. Reference AS/NZS 4777.1 -2005 Clause 5.3.1 J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection How should I connect the inverter energy system (generator) to the installation? Cont…….. All the cables between the inverter energy system and any switchboard and all the cables between any distribution boards and a main switchboard which carry current from the inverter energy system shall be rated for at least the full output current of the inverter energy system and, if the inverter energy system is configured as a UPS, for at least the full input current of the inverter energy system. Reference AS/NZS 4777.1 -2005 Clause 5.3.2 J.P. Teasel version 12/11/2011.1

Does the solar main switch need locking facilities? Grid Connect Session12 System Protection Does the solar main switch need locking facilities? Yes, the main switch shall be provided with a permanent locking facility so it can be the locked in the OFF position. This cannot be achieved using a plug in circuit breaker in a semi enclosed rewirable fuse base. The solar main switch for the switchboard, to which the inverter energy system is connected, shall be a lockable switch. An appropriately labelled lockable isolation switch or circuit breaker, which is lockable in the OFF position and operates in all active conductors, shall be provided on the switchboard to which the inverter energy system is directly connected. See next slide Reference AS/NZS 4777.1 -2005 Clause 5.3.3 J.P. Teasel version 12/11/2011.1

Does the solar main switch need locking facilities? Grid Connect Session12 System Protection Does the solar main switch need locking facilities? Yes cont…….. This switch shall be capable of breaking the full output current of the inverter. Operation of this switch shall isolate the inverter energy system from that switchboard. This isolation switch shall be installed to the requirements for main switches, as specified in AS/NZS 3000. NOTE: This switch is to provide isolation of the inverter energy system for persons working on other parts of the electrical installation. Reference AS/NZS 4777.1 -2005 Clause 5.3.3 J.P. Teasel version 12/11/2011.1

Common requirements for isolating devices Grid Connect Session12 System Protection Common requirements for isolating devices Provision shall be made to enable isolation of electrical equipment and to prevent electrical equipment from being inadvertently energized. The means of isolation shall be such that a deliberate action in addition to the normal method of operation is required to energize the circuit. NOTE: Such precautions may include one or more of the following measures: (a) Provision for the fitting of a padlock. (b) Location within a lockable space or enclosure. J.P. Teasel version 12/11/2011.1

System Earthing Grid Connect Session12 System Protection The requirement for earthing exposed conductive part of PV array (bonding system arises for the following reasons: Bonding to avoid uneven potentials across the installation Protective earthing so that there is a low ohmic fault current path T o provide lightning protection See AS/NZS 5033:2005 Clause 5.3 J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection Do the exposed metallic parts of the solar array require be earthed or equipotential bonded? A solar generation system with a non-isolated (transformer-less) inverter requires the metallic frames and conductive structural supports of the PV arrays to be earthed in accordance AS/NZS 3000:2007 with the requirements of a protective earthing conductor. This shall be achieved by connecting the earthing conductor with a minimum cross-sectional area of 4mm2 directly or via the inverter to the installations earthing system. J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection A surge protector (or surge suppressor) is an appliance designed to protect electrical devices from voltage spikes. A surge protector attempts to limit the voltage supplied to an electric device by either blocking or by shorting to ground any unwanted voltages above a safe threshold Source: http://selink.schneider-electric.com.sg/selink/sg/H_Homepage.nsf/($All)/BC5A006E7D26490F4825733E00123765/$file/PRF1%20PRD%20PF%20SurgeArrest-M9DP80AEN.pdf J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection The earthing requirements of other solar generation systems shall be determined following figure 5.9 of AS/NZS 5033:2005 ―PV array framework earthing decision tree. Equipotential bonding or protective earthing is intended to minimize the risks associated with the occurrence of voltage differences between exposed conductive parts of electrical equipment and extraneous conductive parts. Reference - AS/NZS 5033:2005 Clause 5.3 see next slide J.P. Teasel version 12/11/2011.1

The earthing requirements of other solar generation systems cont…… Grid Connect Session12 System Protection The earthing requirements of other solar generation systems cont…… All PV array system bonding conductors shall comply with the material, type, insulation, identification; installation and connection requirements specified in AS/NZS 3000 but shall not have a cross-sectional area less than 4mm2. Reference - AS/NZS 3000:2007 Clause 5.6.3.2 Where the solar supply is connected to a sub-board the protective earth between the main switchboard and sub-board shall be of a cross-sectional area of not less than 4mm2. Reference – ruling from EL 001 committee - AS/NZS 3000:2007 J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection Does the interconnecting wiring between each PV module require mechanical and IP protection? Yes - the installation of wiring associated with PV array systems (operating at ELV or LV) shall be installed in accordance with AS/NZS 3000 except where varied by the additional requirements of AS/NZS 4777 Series & AS/NZS 5033. Reference –Clause 3.1 of AS/NZS 5033 J.P. Teasel version 12/11/2011.1

Clauses related to the wiring connecting panels and arrays Grid Connect Session12 System Protection Clauses related to the wiring connecting panels and arrays Voc Array (open circuit voltage at standard test condition) - shall not exceed the maximum allowed operating voltage of the PV modules (as specified by the manufacturer). Reference –Clause 3.2 of AS/NZS 5033 Extra Low voltage – Segmentation (disconnection requirements) Reference –Clause 2.5.4 of AS/NZS 5033 PV array wiring – protection and installation Reference –Clause 3.3 of AS/NZS 5033 Wiring loops – installation Reference - Clause 3.3.2 of AS/NZS 5033 String wiring - installation Reference – Clause 3.3.3 of AS/NZS 5033 IP rating of the enclosure and cable entries Reference –Clause 3.3.4 of AS/NZS 5033 PV array and PV sub-array junction boxes locations Reference –Clause 3.3.5 of AS/NZS 5033 J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection Are the conductors installed between the PV array and the main switchboard classified as consumer’s mains? Yes – the conductors between the output terminals of an electricity generating system that provides another source of electrical energy within the installation and the switchboard where they are connected are consumers mains. Consumers mains - those conductors between the point of supply and the main switchboard. Reference – AS/NZS 3000:2007 Clause 1.4.33 Point of supply - the junction of the consumer‘s mains with— (a) conductors of an electricity distribution system; or (b) output terminals of an electricity generating system within the premises. Reference – AS/NZS 3000:2007 Clause 1.4.75 J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection What considerations need apply to the unprotected PV array consumer’s mains (dc array cable)? See next slide ½ The PV (dc) array cable between the arrays and inverter are deemed to be electrically unprotected consumer‘s mains. Unprotected consumer‘s mains would normally be installed fully enclosed in heavy duty conduit. As a PV array is a current limited generator the Australian Standards committee EL 042 ruled that the dc cable can be installed with mechanical protection this can be achieved by the cable location or additional protection by installation within a wiring enclosure. J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection What considerations need apply to the unprotected PV array consumer’s mains (dc array cable)? Consumers mains not provided with short-circuit protection on the supply side, shall— (a) be constructed in such a manner as to reduce the risk of short-circuit to a minimum; and (b) be installed in accordance with the relevant additional requirements of the electricity distributor. The following wiring systems are deemed to reduce the risk of short-circuits to a minimum: (i) Insulated and sheathed cables enclosed in heavy-duty insulating conduit to AS/NZS 2053. (ii) Insulated and sheathed cables installed in underground wiring enclosures. Reference – AS/NZS 3000:2007 Clause 3.9.7.1.2 J.P. Teasel version 12/11/2011.1

Grid Connect Session12 System Protection FAQ 20-2009 – Consumer‘s mains - Unprotected Under what conditions would an unenclosed, insulated and sheathed cable be permitted as unprotected consumer‘s mains for installations? Subject to any additional requirements or restrictions of the electricity distributor, the following installation conditions for an insulated and sheathed cable are deemed to minimise the risk of short–circuit: (a) Installed in areas that would not be subject to mechanical damage (see AS/NZS 3000:2007 Clause 3.9.4), for example – (i) supported more than 50mm from surfaces in a roof space that may be penetrated by nails, screws or drills and in a location not subject to damage by access within the roof space (ii) run in double brick or brick veneer wall cavities; or (iii) supported by cable trays or ladders or at the point of attachment at a height of not less than 2.5m from the ground, floor or platform (out of arms reach); and, see next slide J.P. Teasel version 12/11/2011.1

FAQ 20-2009 – Consumer‘s mains - Unprotected Grid Connect Session12 System Protection FAQ 20-2009 – Consumer‘s mains - Unprotected (b) Additional mechanical protection of the cable, by insulating, enclosing or installing barriers, at any points along the mains likely to be damaged due to movement, for example where the cable passes through or contacts abrasive building materials or for any other reason. Additional requirements may be applied by various States in Australia. Reference – FAQ 020/2009: AS/NZS 3000:2007—CLAUSE 3.9.7.1.2 The section of consumer‘s mains installed between the inverter and the switchboard are considered to be electrically protected when an appropriate sized ac circuit-breaker is installed as the solar main switch. J.P. Teasel version 12/11/2011.1

What type of cable is suitable for the dc PV array wiring system? Grid Connect Session12 System Protection What type of cable is suitable for the dc PV array wiring system? To minimize corrosion (electrolytic effect) and the risk of breakage the cables should be fine-stranded tinned copper conductors. The cables shall be rated for the maximum voltage and current carrying capacity to which it is subjected. PV array cables shall be clearly identified so they cannot be mistaken for other power cables within the installation. The cross-sectional area of the dc cable shall be a minimum of 4mm2 and rated at the appropriate voltage up to 1500 volts dc. Note: Where PV array cabling could be confused with other wiring systems, appropriate identification shall be provided at regular intervals (typically, identification should be not more than 3m apart). J.P. Teasel version 12/11/2011.1

NOTE: When calculating cable size, consideration needs to be given to; Grid Connect Session12 System Protection Cable size - the minimum cable sizes for PV array wiring, based on current carrying capacity, shall be based upon a current rating calculated from Table 3.1 of AS/NZS 5033. NOTE: When calculating cable size, consideration needs to be given to; (a) voltage drop (a maximum of 5% is recommended); and (b) de-rating of the current carrying capacity of a cable due to temperature. J.P. Teasel version 12/11/2011.1

Australian Standards EL 42 committee proposed changes. Grid Connect Session12 System Protection Australian Standards EL 42 committee proposed changes. Standards Australia Committee (EL-42) proposes changing the appropriate standards to reflect the following: Due to the inability to provide short-circuit protection at the origin of the circuit, the dc PV Array cable shall be mechanical protected this can be achieved by the cable location or installing the cable in an PVC conduit complying with AS/NZS 2053. Where the wiring system or conduits are exposed to direct sunlight protection against UV shall be provided. The dc PV array cable shall be of a type specifically designed for dc currents and comply with the appropriate IEC standards. J.P. Teasel version 12/11/2011.1