PS / Booster septa control Control upgrade Marco Pimentel TE-ABT-EC
PS / Booster septa positioning system OUTLINE Equipments presentation Equipment / control connection Control presentation Upgrade motivations Process Planning Marco Pimentel TE-ABT-EC
PS / Booster septa positioning system Equipment's presentation: location PS / Booster rings Equipment 1 BESMH 2 BT1SMV10; BT4SMV10 3 SMV20 4 PISMH42 5 SMH57 6 SMH16 7 SEH23 8 SMH26 9 SEH31 Marco Pimentel TE-ABT-EC
PS / Booster septa positioning system Equipment's presentation: Classification Horizontal displacement SEH23 Electrostatic septa (3 motors) SEH31 SMH16 Electromagnetic septa (2 motors) SMH26 SMH57 BESMH PISMH42 Vertical displacement BTSMV20 BT1SMV10 BT4SMV10 Marco Pimentel TE-ABT-EC
PS / Booster septa positioning system Equipment's presentation: Control components Each movement is composed by: 1 Motor 1 Potentiometer 2 Micro-Switches { Potentiometer’s 4 / 22 units total 3600° +10° -5° 5 / 10 KΩ SCEM Code: 11.87.12.800.8 micro-switches 44 units total SCEM Code: 06.92.32.562.5 Septum Electro Static Motors + worm gear’s 22 units total Zürrer LFV55/4-1 1kW Septum Electro Magnetic Marco Pimentel TE-ABT-EC
PS / Booster septa positioning system Equipment’s / control connection Pinout tables Electrical schemas Electrical cabinet sample (Ring) SMB: septa monitoring box Patch panel sample (Surface) Marco Pimentel TE-ABT-EC
PS / Booster septa positioning system Control presentation: location Building 359/R Building 361/R Rack Hosted controls 1 CHR 122 SMH26 2 CHR 121 SMH57 3 CHR 120 SMH16 4 CHR 119 SEH23; SEH31 Rack Hosted controls 1 658 BESMH; PISMH42 2 659 BT1SMV10; BT4SMV10 3 660 BTSMV20 Marco Pimentel TE-ABT-EC
PS / Booster septa positioning system Control presentation: Equipment’s Building 359 (PS) Building 361 / BCER (PSB) Marco Pimentel TE-ABT-EC
PS / Booster septa positioning system Control presentation: Equipment description TE-ABT 1. Anti-collision 2. Position acquisition 3. Movement Interlock (Single axis) 4. Power supply (24v/2A Interlock system) 5. Power supply (15v/2A SMB movement acquisition) 6. Power supply (48v/2A SMB movement control) 7. Position comparators 8. G64 8.1. RTI – (remote terminal interface ) 8.2. CPU 8.3. Digital input/output (Status) 8.4. Movement position command (DAC) 8.5. Movement position acquisition(ADC) 8.6. Power supply (5-15v/1A) BE-CO Control panel (SEH31) Marco Pimentel TE-ABT-EC
PS / Booster septa positioning system Control presentation: Architecture Marco Pimentel TE-ABT-EC
PS / Booster septa positioning system Upgrade motivations GM classes to be replaced by FESA G64 not supported anymore. Apply updated control standards. Replace equipments with approximately 20 years old. Improve remote control of the installations. Frame the facilities in TE/ABT current standards. Keep current infrastructure (cabling, SMB) Marco Pimentel TE-ABT-EC
PS / Booster septa positioning system Process Planning Study Functional specification approval (EDMS 1551291) Planning Engineering specification approval Preparation Production Removal preparation Execution 1/2 PSB - Installation Commissioning Execution 2/2 PS - Installation } EYETS 2016-2017 } YETS 2017-2018 Marco Pimentel TE-ABT-EC