LIGHTING IMPROVEMENT IN CUTTING STATION

Slides:



Advertisements
Similar presentations
LAMPS (Chapter 3) Lamp efficacy, life, and color Incandescent
Advertisements

PH 0101 UNIT- 3 LECT - 1 BASIC DEFINITIONS 2 PRINCIPLES OF PHOTOMETRY
Management and Organisation of Electricity Use Energy Efficient Lighting Techniques Belgrade November 2003.
ASSIGNMENT BOOK Unit 8 Part 3 Part 3 Take Up the Challenge 1. Corridor lighting can be controlled by 2 two-way switches ( 雙切開關 ), i.e., you can switch.
Lighting Calculations
1 ISAT Module III: Building Energy Efficiency Topic 6:Stead-State Building Loads z Fabric Loss z Ventilation Loss z Environmental Temperature z Steady-State.
Light Chapter 16 & 17. What is light? Usually we think of only visible light but visible light is just a part of the electromagnetic spectrum. Light sources:
LIGHTING ID 320 – LIGHTING\ACOUSTIC\HVAC Done by: Amjad AlFawaz Light Reflection & Transmission Color Glare.
K. F. Chan (Mr.)ELEC LUMEN METHOD Utilization factor -- Ratio of flux received by reference plane to total rated lamp flux in the installation. Utilization.
Light Quantity Lighting Metrics Luminous Flux Illuminance
EDSGN 100 Section 001 Team 5 Submitted To: Smita Bharti 10/16/2012
1 CCTV SYSTEMS LIGHTING AND ILLUMINATION. 2 CCTV SYSTEMS A video camera requires light to work properly, without sufficient light the video camera can’t.
Paint It Black 9-5 Project 1. Purpose The purpose of this experiment is to investigate the relationship between heat conservation and color. The questions.
Analysis of the influence of aiming, on visibility distance and glare Poland 65 GRE, 29 March 2011 Dr EngTomasz Targosinski Informal document No. GRE
Lighting calculations
Chapter 16.  Ray Model of Light- Light is represented as a ray that travels in a straight line.
Kitchen & Bath Lighting. A good lighting design should: Look good – both people and design space Provide the proper amount of light in every room Be.
Photometric Data Photometry is the science of measurement of light.
IES 303 Engineering Management & Cost Analysis | Dr. Karndee Prichanont, SIIT 1 IES 303 Chapter 5: Process Performance and Quality Objectives: Understand.
Early Work – Feb. 20 Explain the uses of light Definitions from Ch. 16.
ARC 810: Building Climatology Department of Architecture, Federal University of Technology, Akure, Nigeria ARC 810: Building Climatology Department of.
Artificial Lighting Design Task lighting for general purpose rooms involves the installation of light sources that will provide the optimum amount of.
Kwok Ngai Kan ES The benefits of proper lighting  To allow employees to comfortably see what they’re doing, without straining their eyes or their.
Chapter 16 Fundamentals of Light The Ray Model of Light -light is represented by a ray that travels in a straight path -can only be changed by placing.
Visible light is electromagnetic radiation with wavelengths from 400 to 700 nm. The electromagnetic spectrum Includes more that just Visible light.
Color Why is the Sky Blue? Atmosphere scatters blue light because of the shorter λ.
0 Load Calculation Manual Output : 1. Screen Outputs (Results, Pareto Chart, Hourly Estimation) 2. Optional Outputs (*CLTD.txt, *TETD.txt) 3.
Chap 16-1 Light Fundamentals.
Chap 16-1 Light Fundamentals. What is Light? A transverse electromagnetic wave.
DAYLIGHT CALCULATIONS. Components of the Natural Light :  There are three separate components of the natural light that reaches any point inside a building:
Objectives Finish commercial electrical systems
Department of Technical Education
Physics 1 H Created by Stephanie Ingle
9EE605A.7to81 Department of Technical Education Andhra Pradesh Name Designation Branch Institute Year/Semester Subject Subject Code Topic Duration Sub.
Part I: Temperature and Thermal Energy Transfer
Application of Standard Normal Distribution Q1: A certain type of storage battery lasts, on average 3.0 years with standard deviation of 0.5 year, assuming.
LED Filament Bulb Introduction A. Current LED Filament Bulb B. Why has the LED filament bulb been developed? C. Product Comparison 1. Which is the end.
Lighting facts.  Lighting can be a big energy consumer in offices and production areas and experience shows that energy savings may be achieved - often.
Chapter 16 Fundamentals of Light Understand sources of light and how light illuminates the universe around us. Chapter 16 In this chapter you will:
Introduction to Power Save LED Module March 2015.
How to Selecting Quality LED ceiling Light Wisely January 15th, 2015 / Blmall.com Most of my friends have some doubts about how to selecting quality LED.
LABORATORY 4 TITLE: Circuit Control Operation OBJECTIVE: To understand circuit control using time switch. NOT ES: While it is possible to control electric.
LEVEL 4 ENERGY ASSESSOR TRAINING 8. Level 3 re-cap lighting and Power Factor Correction.
Power consumption is calculated in kW-Hr = Total Power x time of use
EFFECT of LIGHT INTENSITY on COMPLAINTS FATIGUE EYE on COMPUTER USERS of EMPLOYEES in PT. PLN (PERSERO) PARENT UNIT II UNIT IMPLEMENTING DEVELOPMENT.
Reflections in Plane Mirrors
Lighting Design: Energy Efficient Lighting Design:
LIGHT LIGHT AND COLOR.
Incandescent Light Bulb LUMEN DESIGN METHOD Where: N = E A F UF LLF N = number of lamps E = level of illuminance A = Area at working plane.
METHODS OF ILLUMINANCE CALCULATION
Chapter 32Light: Reflection and Refraction
Part I: Temperature and Thermal Energy Transfer
Drill: Calculate the speed of a water wave when waves 5
ILLUMINATION.
WORK, POWER, & EFFICIENCY
Understand Lighting (Photons, Lumens, Foot Candles and More)
Electrical Calculations
Tas Climate Based Daylight Modelling
Climate Based Daylight Modelling
Chapter 2C: BASIC THERMAL SCIENCES: RADIATION HEAT TRANSFER
Current and Resistance
Point-by-Point Factors
ELL100: INTRODUCTION TO ELECTRICAL ENGG.
In this presentation you will:
Circuit Components.
Announcement Filed trip is on Monday, May 6th from 8 to 9 AM
Light and Illumination
Light Waves, Mirrors and Reflection
Chapter 2C: BASIC THERMAL SCIENCES: RADIATION HEAT TRANSFER
The Properties of Light
Presentation transcript:

LIGHTING IMPROVEMENT IN CUTTING STATION Dini Wahyuni Rahmi M. Sari Nismah Panjaitan Irwan Budiman Marintan Sitorus Industrial Engineering University of Sumatera Utara

INTRODUCTION Lighting is one of the working environment factors which need special attention from the management. Lighting conditions as well as temperature and humidity workspace, giving effect to the work result of a worker. Insufficient lighting can effect to eye fatigue for the operators and affect to the performance by decreased work productivity and work accidents. Previous research conducted in sorting station at printing industry and plastic packaging industry indicates low lighting can lead to increased number of defective products which passed inspection.

This research was conducted at the cutting station at a coachbuilder industry (autobody manufacturer) in North Sumatra. Approximately 40% of cases of occupational accidents that occurred in 2015 are located in the cutting station. The accident cases such as entrapment of hand in the cutting machine, operator struck down by aluminum plate and severed fingertip by cutting machine. At the initial observation, the illumination is 30 lux at the cutting station, is so much under the terms of the government regulation at 200 lux, so it is necessary to design the lighting improvements.

METHOD The study was conducted at the cutting station in coachbuilder industry. Area of the work station is 95 m2, with incoming light from two lamps and each lamp has 23 watts. The distance from the lamp to working surface is 9 m. Measurement points was determined by following the provisions of SNI 16-7062-2004 which divides the workspace in cutting station on grids with certain size depending on the area. For room size: Under 10 m2, the size of the grid is 1 m x 1 m; room with an area between 10-100 m2, grid is 3 m x 3 m; room with area exceed 100 m2, grid is 6 x 6 m.

Measuring instrument for this research is 4-in- 1 environment meter Measuring instrument for this research is 4-in- 1 environment meter. Grid size is 3 m x 3 m and gained 6 points of measurement. The measurement of Illumination performed thrice at any point during the three days of observation from 9:00 a.m until 4:00 p.m in West Indonesia Time. The luminance measurements were also conducted on a number of material objects in the cutting station.

From the measurement results will be calculated the average value of illumination, number of reflectance, the number of lumens required at the cutting station and energy needs to fulfill them. Selection for the type of light bulb can be considered based on the number of lumens and lower energy needs so that operating costs will be lower.

RESULT AND DISCUSSION Illuminance and luminance measurement During 3 days the measurement of illumination was performed in the cutting work station and cutting machine area, and the data were presented in Table 1. Table 1. The average of Illumination level in cutting station (lux) Point of measurement SK AK 1 28,16 21,81 2 38,77 21,39 3 41,87 28,44 4 25,51 24,87 5 48,61 32,91 6 40,39 36,94 SK = Illumination level in Cutting Station AK = Illumination level in working area of cutting machine operator

The illumination data in cutting station, cutting machine operator area and number of illumination level required by government regulations can be seen in Figure 1. From Fig. 1 can be seen that the existing illumination is still below the requirements. Fig. 1. Illumination level in cutting station and work area

Illuminance and luminance measurements carried out on the object material in the cutting station, such as left, right, front and back of wall, as well as floor and ceiling. The wall was formed of stone wall except on the right side formed of an iron door. The floor was also made of cement, and the ceiling is made of aluminium. Comparison of the luminance to the illumination level, obtained number of reflectance as in Table 2. Table 2. Number of reflectance of each object material in cutting station No Measurement area Num. Of reflectance Color explanation 1 Wall 0,50 Beige 2 Floor 0,38 Gray 3 Ceiling 0,53 Dull white

Luments and number of required lamps The type of existing lamps have luminuous flux about 1,900 lumens respectively. The calculation result of required lighting (flux luminuous) amounting to 79,835.90. If used the same type of light bulb with current, the required light bulb will be equal to 42 lamps. The type of LED lamp is recommended in this study because it has higher efficacy (115-180 lm / watt), longer-lived (35,000-50,000 hours) and shock- resistant. If alternatives for mounting the same as the existing condition (the distance light to the work plane 9 meters), then the use of LED lights with 88 watt nominal luminuous flux of 6,300 lumens each will need 12 unit of light bulbs. While using 74 watt LED lamps of different types with a nominal luminous flux of 9,000 lumens respectively, the number of light bulbs required is 8 units only.

Illumination level (lux) In the working area of operator, placement of the light bulbs by a distance of 30 cm from the working area (placed on the cutting machine, closer to the operator will receive a higher level of lighting). If 8 watts of LED lamp with an equivalent value to 112 lux, the light bulbs required to meet the standard of 200 lux is 2 units. As in the previous description, it was gained 3 lighting alternatives to meet the standard of 200 lux., as shown in Table 3. Energy usage Table 3. Lighting alternatives for working room and working area of operator Alternative Number of Lamps Power / lamp (watt) Illumination level (lux) Power needs (KW) I 12 88 1279 1,056 II 8 74 316 0,592 III 4 224 0,320

From alternatives above, it appears that the third alternative has the lowest required energy. If alternative III is implemented then the fulfillment of the lighting in the cutting station is simply adding lights in the work area operator 30 cm above working area. This solution will have much cheaper costs consequences compared to two other alternative uses the same installation as existing condition.