ME 312 PPE POWER SYSTEM ANALYSIS

Slides:



Advertisements
Similar presentations
ENERGY VALUE. Summary  Operational Value is a primary component in the Net Market Value (NMV) calculation used to rank competing resources in the RPS.
Advertisements

CVP Cost Allocation Public Workshop – January 18, 2013 “PLEXOS Methodology and Assumptions”
Technical Conference Avoided Cost Modeling January 6, 2015.
1 John J. Conti Acting Director Office of Integrated Analysis and Forecasting Prepared for the Energy Technology System Analysis Program (ETSAP) Florence,
I/O Curve The IO curve plots fuel input (in MBtu/hr) versus net MW output.
EE 369 POWER SYSTEM ANALYSIS
Lecture 16 Economic Dispatch Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
ECE 333 Renewable Energy Systems Lecture 2: Introduction, Power Grid Components Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.
Miao Lu 1. Content Overview I. Load Models II. Economic Dispatch III. Disturbance and Recovery IV. Demand-Side Management V. Energy Storage Units VI.
System Planning & Operations Spring 2010
Preliminary Analysis of the SEE Future Infrastructure Development Plan and REM Benefits.
EE 369 POWER SYSTEM ANALYSIS
1 Least Cost System Operation: Economic Dispatch 2 Smith College, EGR 325 March 10, 2006.
Least Cost System Operation: Economic Dispatch 1
Hydropower and thermal1 ECON 4925 Autumn 2007 Electricity Economics Lecture 5 Lecturer: Finn R. Førsund.
Northwest Power and Conservation Council 6 th Plan Conservation Resource Supply Curve Workshop on Data & Assumption Overview of Council Resource Analysis.
HYDROPOWER. Objective: The student will be become familiar with the Corps policy for hydropower development. The student will be have a basic understanding.
Announcements Homework 7 is 6.46, 6.49, 6.52, 11.19, 11.21, 11.27; due date is Thursday October 30 Potential spring courses: ECE 431 and ECE 398RES (Renewable.
Sixth Northwest Conservation & Electric Power Plan Draft Wholesale Power Price Forecasts Maury Galbraith Northwest Power and Conservation Council Generating.
Mechanical Engineering Department ME 332 Operation and Management of Power Plants Prof. Osama A El Masry Power Plant Selection & Economics Prof. Osama.
ECE 476 Power System Analysis Lecture 15: Power Flow Sensitivities, Economic Dispatch Prof. Tom Overbye Dept. of Electrical and Computer Engineering University.
1 System planning 2013 Lecture L9: Short term planning of thermal systems Chapter Contents: –General about thermal power –Production cost –Start.
Diagram from the publication
Lecture 16 Economic Dispatch Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
SHP – Columbia University
Lecture 15 Economic Dispatch Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Electricity Basket Price & 2013 Power Policy Hammad Hashmi Advisor Technical (USAID) MWP.
0 Balanced 3 Phase (  ) Systems A balanced 3 phase (  ) system has three voltage sources with equal magnitude, but with an angle shift of 120  equal.
Announcements Please read Chapter 7 HW 6 is due today
Estimating the resource adequacy value of demand response in the German electricity market Hamid Aghaie Research Scientist in Energy Economics, AIT Austrian.
Assoc. Prof. Dr. Tarkan Erdik
Using Technology for Electricity improvements
Reading and Homework For lecture 3 please be reading Chapters 1 and 2
RENEWABLES AND RELIABILITY
GENESYS Redevelopment
Integrated Resource Plan 2016
Announcements Homework 7 is due now.
Electricity System Cost Outlook
ECE 476 Power System Analysis
Chapter 6 Production.
UNIT 6 COSTS AND PRODUCTION: LONG AND SHORT-RUN, TOTAL, FIXED AND VARIABLE COSTS, LAW OF DIMINISHING RETURNS, INCREASING, CONSTANT AND DIMINISHING RETURNS.
What is POWERBALANCE?.
Economic Operation of Power Systems
Energy Resources Table of Contents Fossil Fuels
ECE 476 POWER SYSTEM ANALYSIS
ECEN 460 Power System Operation and Control
Combined operation of different power plants PREPARED BY : Priyanka Grover Btech (EE) SBSSTC,FZR.
Hidden Costs of Wind and Solar Power
Renewable vs. Non-Renewable
ECEN 460 Power System Operation and Control
EE 369 POWER SYSTEM ANALYSIS Lecture 15 Economic Dispatch Tom Overbye and Ross Baldick 1.
Evolving Economic Dispatch in SPP
MRES Resource Operations in SPP
LMP calculations Congestion evaluation
CSP Grid Value of Energy Storage and LCOE Implications 26 August 2013
Security of supply - deriving a winter energy standard using the DOASA model EPOC Winter Workshop September 2018.
ECE 333 Renewable Energy Systems
Additional clarifications on economic and adequacy running hours
Basin Electric SPP Market Update
Energy (TKK-2129) Instructor: Rama Oktavian; Dr. Rizka Zulhijah
Generation Expansion Daniel Kirschen
ECEN 460 Power System Operation and Control
Chemical Process Development 450/650 May 4, 2016 Session 14
energy and environment
New Zealand’s Unique Electrical System
An Overview of the U.S. Electric Power Grid
Wholesale Electricity Costs
energy and environment
Some Basic Concepts ENERGY INSTITUTE Econ 3385 – Economics of Energy
Linear Programming.
Presentation transcript:

ME 312 PPE POWER SYSTEM ANALYSIS Economic of power gene ration

Retail Electricity Prices There are many fixed and variable costs associated with power systems, which ultimately contribute to determining retail electricity prices. The major variable operating cost is associated with generation, primarily due to fuel costs: Roughly 30% to 50% of retail costs. Retail prices also reflect the capital costs of building the generation, transmission, and distribution system as well as other costs.

Power System Economic Operation Different generation technologies vary in the: capital costs necessary to build the generator fuel costs to actually produce electric power For example: nuclear and hydro have high capital costs and low operating costs. Natural gas generators have low capital costs, and (with gas available from fracking) moderate operating costs.

Power System Economic Operation Fuel cost to generate a MWh can vary widely from technology to technology. For some types of units, such as hydro, “fuel” costs are zero but the limit on total available water gives it an implicit value. For thermal units it is much easier to characterize costs. We will focus on minimizing the variable operating costs (primarily fuel costs) to meet demand.

Power System Economic Operation Power system loads are cyclical. Therefore the installed generation capacity is usually much greater than the current load. This means that there are typically many ways we could meet the current load. Since different states have different mixes of generation, we will consider how generally to minimize the variable operating costs given an arbitrary, specified portfolio of generators.

Thermal versus Other Generation The main types of generating units are thermal and hydro, with wind and solar rapidly growing. For hydro the fuel (water) is free but there may be many constraints on operation: fixed amounts of water available, reservoir levels must be managed and coordinated, downstream flow rates for fish and navigation. Hydro optimization is typically longer term (many months or years). We will concentrate on dispatchable thermal units, looking at short-term optimization: Non-dispatchable wind and solar can be incorporated by subtracting from load.

Generator types Traditionally utilities have had three broad groups of generators: “Baseload” units: large coal/nuclear; almost always on at max. “Midload,” ‘intermediate,” or “cycling” units: smaller coal or gas that cycle on/off daily or weekly. “Peaker” units: combustion turbines used only for several hours. during periods of high demand

Block Diagram of Thermal Unit To optimize generation costs we need to develop cost relationships between net power out and operating costs. Between 2-10% of power is used within the generating plant; this is known as the auxiliary power.

Thermal generator Cost Curves Thermal generator costs are typically represented by one or other of the following four curves input/output (I/O) curve fuel-cost curve heat-rate curve incremental cost curve For reference 1 Btu (British thermal unit) = 1054 J 1 MBtu = 1x106 Btu 1 MBtu = 0.29 MWh

I/O Curve The IO curve plots fuel input (in MBtu/hr) versus net MW output.

Fuel-cost Curve The fuel-cost curve is the I/O curve multiplied by fuel cost. A typical cost for coal is $ 1.70/MBtu.

Heat-rate Curve Plots the average number of MBtu/hr of fuel input needed per MW of output. Heat-rate curve is the I/O curve divided by MW. Best heat-rate for most efficient coal units is around 9.0

Incremental (Marginal) cost Curve Plots the incremental $/MWh as a function of MW. Found by differentiating the cost curve.

Mathematical Formulation of Costs Generator cost curves are usually not smooth. However the curves can usually be adequately approximated using piece-wise smooth, functions. Two approximations predominate: quadratic or cubic functions piecewise linear functions We'll assume a quadratic approximation:

Coal Usage Example A 500 MW (net) generator is 35% efficient. It is being supplied with coal costing $1.70 per MBtu and with heat content 9000 Btu per pound. What is the coal usage in lbs/hr? What is the cost?

Wasting Coal Example Assume a 100W lamp is left on by mistake for 8 hours, and that the electricity is supplied by the previous coal plant and that transmission/distribution losses are 20%. How much coal has he/she wasted?