THUM Adapter Impact on Hazardous Area Classification

Slides:



Advertisements
Similar presentations
Safety Absolutes Green Lake
Advertisements

IECEx MEETING IN FORTALEZA, BRAZIL
Chemical Storage. Objectives Separating incompatible materials Special hazards Flammable storage cabinets Corrosives cabinets Special versus general.
(Adapted from:D.T. Hall:Practical Marine Electrical Knowledge)
A PPARATUS G AS G ROUPS, T EMPERATURE C LASS AND T YPES OF E XPLOSION P ROTECTION (Adapted from:D.T. Hall:Practical Marine Electrical Knowledge)
(Adapted from:D.T. Hall:Practical Marine Electrical Knowledge)
2.5.2 Student Book © 2004 Propane Education & Research CouncilPage Examining, Maintaining and Operating ASME Tank Setting Trailers For the safe.
ExSite “ Sharing of Best Practices” The following illustrations of system interconnections are provided only as a guideline. Actual connections are dictated.
ELECTRICAL SAFETY / E N V I R O N H & S T R A I N I N G P R O G R A M ELECTRICAL SAFETY OSHA requires that electrical equipment be approved for use and.
Site Planning and Layout  In the design phase of a facility, fire protection requirements are considered in the site layout  Water supply, traffic and.
Vibration Sensors for Cooling Towers Challenges Cooling towers offer the vibration analyst many challenges in sensor selection, mounting and environmental.
CERTIFICATION OF EQUIPMENT FOR USE IN POTENTIALLY EXPLOSIVE ATMOSPHERES What do I Really Have to Do ?
Temporary Configuration Change Mike Hayes Exelon Nuclear.
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE PV APPLICATIONS CODES AND STANDARDS EMERGENCY RESPONSE.
CNG STATION & GARAGE MODIFICATION CODES & STANDARDS Graham Barker Business Development Manager.
Patrick Thornton, SNS/FPE June 9, 2008
Health and Safety. The Health and Safety at Work Act 1974 An Act to make further provision for securing the health, safety and welfare of persons at work,
Dr Daniel Colbourne 36th Meeting of the Open-ended Working Group of the Parties to the Montreal Protocol – Side Event UNEP.
Flammable and Combustible Liquids
Flammable and Combustible Liquids Presented by Martina Schmeling Adapted From OSHA.
Roadway Lighting on TxDOT Right of Way Greg Jones, EIT Master Electrician, State of Texas TxDOT, Traffic Operations Division, Illumination Branch.
Electrical Safety in Construction. Objectives In this course, we will discuss the following: Common electrical hazards Standards relating to those hazards.
3.4.7 Student Book © 2004 Propane Education & Research CouncilPage Examining Bulk Plant Electrical Systems Prevention of gas ignition in transfer.
Basic Awareness Training for all Staff
Flammable and Combustible Liquids. Introduction !The two primary hazards associated with flammable and combustible liquids are explosion and fire !Safe.
The work of CEN/TC 305 Potentially explosive atmospheres-
2 IMPACT - THE FIRE PERMIT = Hot Work Permit 3 Welcome ! This course is linked to the use of IMPACT, so it is assumed that: You know how to use IMPACT.
The world leader in serving science Antaris EX and Hazardous Locations Overview Matt Ebersole August 13, 2007.
TELECOMMUNICATIONS SPACES
Bi-Weekly Safety Meeting November 29, The days of using canaries in mines as primitive gas detectors are long gone..they've been replaced by fixed.
Flammable Liquids Directorate of Training and Education
Courtesy of Schools Insurance Authority. Title 8, California Code of Regulations, Section 5194 Hazard Communication determines the dangers of the chemicals.
Standards Certification Education & Training Publishing Conferences & Exhibits ISA SP12 Standards Related to Equipment in Hazardous Locations.
Excavation & Trenching Awareness Plus
Rev. 1 © Chevron 2009 Hot Work Awareness Plus. Rev. 1 © Chevron Training Objectives  To explain the type of work which may constitute Hot Work.
Safety Rule #1 Open flames are not allowed without first obtaining a permit. The exception to this rule is during a period of closely supervised instructions,
NCTCOG Electrical Advisory Board
Automotive Engines Theory and Servicing
NONINCENDIVE INSTALLATIONS FOR CLASS I DIV 2 AREAS
XTO Energy Safety Training
Special-Purpose Outlets— Electric Heating, Air Conditioning
Safety Instrumented Systems
T-1070 CHEMICAL SEGREGATION
OVERVIEW Control Of Hazardous Energy.
Gasunie is one of the biggest gas infrastructure companies in Europe
Safety Instrumented Systems
Welcome! Thank you for joining us. We’ll get started in a few minutes.
Who should use this presentation & read code
Smitty’s Two Minute Drill #9: Special Occupancies
Fire Door Inspections Qualified Training
Compressed Gases.
East Carolina University Compressed Gas Safety Training Program
درس ایمنی در آزمایشگاه مدرس: ماندانا امیری پاییز 94- جلسه سوم.
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE
Electrical Safety Standards
Maintenance Apart from safety, maintenance is needed to keep plant in an acceptable condition. Maintenance of this kind must be reviewed on an economic.
Smitty’s Two Minute Drill #1: Feeders and Branch Circuits
General Requirements of NFPA 101
Fire Alarm Tech Practice Test # 16 NICET
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE
Safety Meeting Topics Standby Generator Safety
Day 2 Training - Technical
Module 4: Storage and Dispensing Locations
Electrical components and systems
Parker domnick hunter. Safety of Electrical and
Two Minute Drill – Residential 3
Biosco: MV/LV prefabricated substations IEC Presentation of the standard Safety is a choice.
Automotive Engines Theory and Servicing
CR-GR-HSE-419 Safety of excavation works
Presentation transcript:

THUM Adapter Impact on Hazardous Area Classification Strategies for THUM Adapter Installation

Companies Separate Hazardous Areas of a Plant Based on Risk Class I, Div 2 Area IEC Zone 2 Hazardous gases are only present under fault conditions Unclassified Area Hazardous gases are not present Class I, Div 1 Area IEC Zones 1 and 0 Hazardous gases may be present under normal operating conditions Companies separate hazardous areas of a plant based on risk. Our customers do this and are very familiar with these terms. When talking to the customer, it is important to make sure that you are grounded in the same terms when you discuss approvals for the THUM. Unclassified areas are areas where hazardous gases are not present. Typically, 25 to 50 percent of their measurement devices are here. IEC Zone 2 areas are areas where hazardous gases are only present under fault conditions. An example of this is the space around a tank. In most cases, gases will not be present here but if there were a leak in the tank, the gases could be present in this fault condition. This area accounts for 50 to 75 percent of customer measurement devices. IEC Zone 1 or 0 areas are areas where hazardous gases may be present under normal operating conditions. An example of this is vents that are on tanks. These areas are more restricted and customers try to keep these areas to a minimum. As such, they are typically less than 5 percent of measurement devices. Bottom Line: Customers want to limit Div 1 areas due to safety and environmental concerns

What is the Difference Between Intrinsic Safety and Explosionproof Ratings The energy stored in a device is incapable of causing the ignition of a flammable atmosphere An IS barrier is needed between the power supply and the device Depending on specific rating, suitable for Div 1 and 2 as well as Zones 0, 1, and 2 Explosionproof / flameproof If a hazardous gas is ignited, the explosion is contained within an enclosure Typically, wiring is in rigid metal conduit or rugged cable which is sealed at the device and at the Div or Zone boundaries Suitable for Div 1 and 2 as well as Zones 1 and 2. Not generally suitable for Zone 0 Division IEC Div 1 Zone 0 Zone 1 Div 2 Zone 2 Unclassified Unclassified

THUM Can Connect to Any Device With Some Limitations Class I, Div 2 Area IEC Zone 2 Install THUM on any device that has a compatible Div. 2 rating. Unclassified Area Install THUM on any device Class 1, Div 1 Area IEC Zone 1 / 0 Install THUM on any device that has a compatible intrinsic safety rating or remotely, connect to any device that has an explosion proof rating The THUM adapter can connect to most devices. There are some limitations on how the THUM adapter can be installed based on the approvals area and rating of the wired device. In an unclassified area, you can install the THUM on any device. In Class 1 Div 2 or IEC Zone 2 areas, you can install the THUM on any device that has a compatible Div 2 or Zone 2 rating. In Class 1 Div 1 or IEC Zone 1 or 0 areas, you can either install the THUM on any device that has a compatible intrinsic safety rating or you can remotely connect the THUM to any device that has an explosion proof rating. In this case, you would wire the THUM outside of the IEC Zone 1 or 0 area. We will now look at each case a little more in depth.

Unclassified Area Mounting Options Special Requirements Direct or Remote mount Special Requirements None In an unclassified area there are no special requirements for mounting the THUM adapter. It can be both direct or remote mounted. Power Supply

Div 2 / Zone 2 Area – Typical Method Hazardous Area Div 2 Unclassified Area Power Supply Conduit In a div 2 or Zone 2 the THUM adapter can be either direct or remote mounted. Standard Div 2 / Zone 2 wiring methods must be followed. These typically include conduit or armored cable. If the THUM is remote mounted the wiring between the THUM and the device also needs to use standard Div 2 / Zone 2 practices. You must also ensure that the wired device has the appropriate Div 2 / Zone 2 ratings. Mounting Options Direct or Remote mount Conduit Seal Special Requirements Use standard Div 2 / Zone 2 wiring methods e.g. conduit, armored cable

Div 1 / Zone 1 Area – THUM Outside Hazardous Area Method #1 Hazardous Area - Div 2 Unclassified Area Hazardous Area Div 1 Unclassified Area Power Supply Conduit Seal Conduit Seal Conduit Seal For Div 1 or Zone 1 Areas where the wired device is using explosion proof or flameproof approvals the THUM adapter needs to be remotely mounted outside of the Div 1 or Zone 1 area. The THUM adapter can be mounted in either a Div 2 / Zone 2 or an unclassified area. The wiring between the THUM adapter and the wired device needs to be standard Div 1 Zone 1 wiring. There also needs to be a conduit seal between the THUM adapter and the wired device. Mounting Options Remote mount only Conduit Seal Special Requirements Use standard Div 1 / Zone 1 wiring methods into and out of hazardous area e.g. conduit with seal, armored cable, etc Conduit seal locations may vary based on installation and local requirements

Div 1 / Zone 1 Area – THUM Outside Hazardous Area Method #2 Hazardous Area - Div 2 Unclassified Area Hazardous Area Div 1 Unclassified Area Power Supply For Div 1 or Zone 1 Areas where the wired device is using explosion proof or flameproof approvals the THUM adapter needs to be remotely mounted outside of the Div 1 or Zone 1 area. The THUM adapter can be mounted in either a Div 2 / Zone 2 or an unclassified area. The wiring between the THUM adapter and the wired device needs to be standard Div 1 Zone 1 wiring. There also needs to be a conduit seal between the THUM adapter and the wired device. Conduit Seal Conduit Seal Conduit Seal Mounting Options Remote mount only Conduit Seal Special Requirements Use standard Div 1 / Zone 1 wiring methods into and out of hazardous area e.g. conduit with seal, armored cable, etc Conduit seal locations may vary based on installation and local requirements

Div 2 / Zone 2 Area – Explosionproof/ Flameproof device THUM remains in Hazardous Area Method Unclassified Area Power Supply Conduit Seal Conduit Seal Conduit Seal Sometimes devices that are only explosionproof or flameproof rate get installed into a Div 2 or Zone 2 area. In these cases the THUM adapter will need to be remote mounted. Since the THUM adapter is Div 2 and Zone 2 rated it does not need to be removed from the Div 2/ Zone 2 area. The wiring that is used will need to meet Div 1 / Zone 1 approvals. A conduit seal will need to be installed between the THUM adapter and wired device. Mounting Options Remote mount only Special Requirements Use standard Div 1 / Zone 1 wiring methods e.g. conduit with seal, armored cable, etc Conduit seal locations may vary based on installation and local requirements

THUM installation rules Above is a chart to help determine the installation requirements for the THUM adapter. Select the column that matches your installation the best and under THUM installation requirements you determine the requirements. “Transmitter protection” refers to the type of protection that wired device carries. These include explosion proof and Intrinsic Safety. “Environment” is the Class or Zone that the wired device is located in. These are either Div 1, Div 2, Zone 0, Zone 1, or Zone 2. “Transmitter Label” refers to the approvals that are called out on the wired devices labels. Some wired devices that are either Explosion proof or Flame proof also carry Div 2 approvals. An easy place to find the approvals that the wired device has is on its labels. “Transmitter Installation” refers to how the transmitter was installed. In some cases devices that are located in a Div 1 or Zone 2 environment may be installed according to Div 1 or Zone 1 requirements. “THUM Installation Requirements” are the requirements that you will need to follow to install a THUM adapter onto a wired device in the selected column. If it says Attach directly the THUM adapter can be remotely mounted.

Summary THUMs can be attached to just about any device Device ratings may require additional considerations Most customers already have similar solutions in place If you have questions about a specific application, call your support personnel Note The information contained in this document is provided for informational purposes only. The installation and operations of electrical equipment must be in accordance with local and national codes and regulations that apply to your facility and satisfy the authorities that have jurisdiction for your location. For installations in the U.S., refer to the National Electrical Code© NFPA 70. By using direct and remote mounting the THUM adapter can be connected to almost any device. In certain hazardous areas there may need to be additional considerations such as remote mounting and using approved wiring methods. Most of our customers already have similar solutions for many of these cases installed. Remember that there are many different local and national regulations that can apply to facilities. Customers tend to have resources at their facilities that now the local and national regulations that apply to their facilities, and how their site meets these regulations. The information in this document is for informational purposes only.