Grid feeding monitoring relay

Slides:



Advertisements
Similar presentations
Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.
Advertisements

HYDRAULICS & PNEUMATICS
Getting Started Product Description Setting Parameters How does it work Wiring Diagram.
©2011, The McGraw-Hill Companies, Inc. Chapter 4.
Graphic Symbol Location 1. DIN Terminal X52 The machine is powered by electricity using copper cable with 5 wires (3 phase wires + neutral wire +
Startup Training – TPS3 15. Siemens TPS3 Startup Training 2 Topics Covered  Visual Inspections  Verify environmental requirements are met  TPS3 15.
Copier Jam Detector Design Problem
Chapter 7 SYSTEM PROTECTION
DEMONSTRATION FOR SIGMA DATA ACQUISITION MODULES Tempatron Ltd Data Measurements Division Darwin Close Reading RG2 0TB UK T : +44 (0) F :
Industrial Machine Control
FG Wilson Access 4000 Control Panel
Electrical Distribution Training
Burners TRAining CEntre. RESIDENTIAL GAS BURNERS R D B R D B series GOALS: KEEP STRONG OUR POSITION ON RESIDENTIAL GAS BURNERS DEDICATED TO OEM’s MARKET.
GCS 300 System Operation Application – Level 1.
Current operation (black keys) Descriptions Parameter / protection setting (blue keys) Main points to remember A B C D ? SEPAM UMIs SEPAM UMI OPERATION.
Date: File:PRO1_12E.1 SIMATIC S7 Siemens AG All rights reserved. Information and Training Center Knowledge for Automation Troubleshooting.
Service Section Technical Training December 2005.
Main contacts closed – RED Colour with ON
SmartMQn Motor Protective Functions Ken Jannotta Jr. Horner APG, LLC.
Puissant Panel User Training Esc.. 09:11:35 ACTIVE # * 3 6 RESET SYSTEM CLEAR DISPLAY TEST DISPLAY SILENCE BUZZER ESCAPE ENTER SILENCE.
Zones 1 to 8 Siren Keypad Power 12V Data and clock By default: Zone 1 Entry Exit 2 Follower 3 Instant 4 Instant 5 Instant 6 Instant 7 Instant 8 Panic.
USER GUIDE TEMPERATURE CONTROLLER TR-2006 Hot runner temperature controller ShenZhen TanRex Electronic Co.ltd.
BUILDING LOAD NORMAL OPERATION 1. ATS are in normal position connected to utility source 2. All generator set paralleling circuit breaker open.
shift to the Test Mode (Forced Operation).
Presented by Under the esteemed guidance of D.GANGADHAR REDDY, M. Tech. Asst. Prof., EEE Department UNIVERSAL COLLEGE OF ENGINEERING & TECHNOLOGY AUTO.
Electrical Configuration and System Protection
Lecture 10: Programmable Logic Controllers
Protection and Relay Schemes
Automatic Transfer Switches
THREE PHASE FAULT ANALYSIS WITH AUTO RESET ON TEMPORARY FAULT AND PERMANENT TRIP OTHERWISE Submitted by:
Grounding.
Interconnect Protection of Dispersed Generators
AUTOMATIC STREET LIGHT CONTROL USING LDR
Wireless Relay HDL-MPR01-RF.18.
Blower-/Fan Coil-Actuator
TPS - Thyristor Power Supply for Resistive/Inductive Loads
Drives Training Foils Encoder Module Installation
DESCRIPTION AND GUIDE TO OPERATIONS
Wireless Relay HDL-MPR02-RF.18.
GROUND-FAULT GROUND-CHECK MONITOR
Presented by: LADWP November 14, 2017
FEEDER PROTECTION UNIT
MPU-16A / FPU-16 TEST UNIT TUTORIAL
The D.C. Scout Battery Distribution System Ground Locator
HVI HIPOT TEST SET Pft sERIES.
Module 1: System Overview
Programming Timers.
Chapter 7 System Protection
ET 438B Sequential Control and Data Acquisition
ELECTRICAL POWER-II Electrical engineering sixth semester
PLC’s Are ... Similar to a Microcontroller: Microprocessor Based
Peter van Oirsouw (Phase to Phase)
Agenda Introduction of Protective Relays
Interconnection of AES With The Grid
Flotection: Building Main Shutoff System
Copier Jam Detector Design Problem
Digital Chart Recorder Operation
Customer Presentation
Universal Dim Actuator UD/S
Training Module Introduction to the TB9100/P25 CG/P25 TAG Customer Service Software (CSS) Describes Release 3.95 for Trunked TB9100 and P25 TAG Release.
Model Output Current Battery Life BATPSU VDC 2A 1.2Ah BATPSU VDC 2.3Ah
Instructional presentation
Switching & Controlling LoB
Accelerator PSS Radiation Monitoring
6. USING THE TDR200 IN ANALOGUE MODE
Electrical components and systems
easYgen-3000XT Series Training
easYgen-3000XT Series Training
Presentation transcript:

Grid feeding monitoring relay Presentation STO/ EPR Grid feeding monitoring relay CM-UFD.M33

Grid feeding monitoring relay CM-UFD.M33 Characteristics UL approval (in preparation) Multiline, backlit LCD display Password setting protection 3 c/o (SPDT) contacts 3 control inputs, e.g. feedback signal, remote trip Monitoring of voltage and frequency in single- and three phase mains Loss of mains detection (vector shift & ROCOF) Completely free adjustable Application: The CM-UFD.M33 is a grid feeding monitoring relay, with the purpose to disconnect the power generation such as photovoltaic systems, wind turbines, block-type thermal power stations system from the grid by tripping the coupling switch. It monitors the voltage and frequency in the grid and will disconnect the distributed generation whenever the measured values are not within the range of the adjusted thresholds. The alarm is indicated by LED and the corresponding plain text message is shown on the display. Operating mode: The CM-UFD.M33 can be set up to monitor single- and three-phase mains (2-wire, 3-wire as well as 4-wire AC systems). The unit is configurable by front-face push buttons. A display with the corresponding menu enables the selection of pre-settings as well as the precise adjustment of the different threshold values and corresponding delay times. Furthermore, the display visualizes the measured values and states clearly. It shows the user all information about operational states on the display together with the front-face LEDs. The CM-UFD.M33 provides 3 output relays and 3 control inputs. Output contacts R1 and R2 could be used for disconnection of the decentralized electrical energy source from the public grid. The corresponding feedback signals from the external contacts are monitored via the control inputs Y1-Y0 and Y2-Y0 (Y2-Y0 is disabled by default, If 2 switching devices necessary. Input contact Y2-Y0 have to be enabled). The third output contact R3 can also be used for the closing command of a motor drive for circuit breaker or as signalization of the output relay R1 and R2. The additional control input Y3-Y0 allows to or to trip the grid feeding monitoring relay from remote (remote trip). With the input Y3-Y0 it is also possible to suppress input Y1-Y0, input Y2-Y0, both together or the vector shift detection. © ABB Group September 16, 2018

Grid feeding monitoring relay CM-UFD.M33 Legend - Front view with operating controls Display Measured values Status of output relays (in this case R3 is de-energized) Status of control inputs (in this case Y3-Y0 is open) Indication of operational states with LEDs U/T: green LED - Status indication control supply voltage and timing Control supply voltage applied Time delay is running F: red LED - Fault message Operating buttons Display: Status of output relays: The relays with a black backcloth are energized and the relays without a backcloth are de-energized (in this case R3 is de-energized) Status of control inputs: The control inputs with a black backcloth are closed and the control inputs without a backcloth are open (in this case Y3-Y0 is open) Operating buttons: Back light of the display switches off automatically after an adjustable duration. With a dark display, press any button to light it up again. ESC > 3 s: Test function ESC: leave the menu/submenu, move to the previous digit or cancel the change, > 1 s cancel the change Arrow buttons: next measurement display, select the submenu/parameter, change the parameter, > 1 s scroll OK: menu, enter the submenu/parameter, move to the next digit or confirm the change, > 1 s confirm the change © ABB Group September 16, 2018

Grid feeding monitoring relay CM-UFD.M33 Control input 1, (e.g. feedback loop for switching device 1) Control input 2, (e.g. feedback loop for switching device 2) Control input 3 (e.g. remote trip) Switching device 1 of a section switch Switching device 2 of a section switch Inverter(s) / Generator(s) Transformer (if applicable) Public grid Application example: In this case the grid feeding monitoring relay CM-UFD.M33 is a monitoring relay, with the purpose to disconnect the power generation such as photovoltaic systems, wind turbines, block-type thermal power stations system from the grid by tripping the coupling switch. It monitors the voltage and frequency in the grid and will disconnect the distributed generation whenever the measured values are not within the range of the adjusted thresholds. The alarm is indicated by LED and the corresponding plain text message is shown on the display. The picture shows only an example of a possible application. Other variants of the section switch (e.g. circuit breaker) are possible. September 16, 2018

Grid feeding monitoring relay CM-UFD.M33 Basic protective functions Overvoltage protection (10-min average value) >UAV Overvoltage protection >U1, >U2 Undervoltage protection <U1, <U2 Overfrequency protection >F1, >F2 Underfrequency protection <F1, <F2 Vector shift protection ROCOF (Rate of change of frequency df/dt) Basic protective functions If control voltage is applied, all phases are present and the switch-on conditions for voltages and frequency are fulfilled, output relays R1 and R2 energize synchronously after the adjustable switch-on delay. If a measured value exceeds or falls below the adjustable threshold (overvoltage, undervoltage, overfrequency, underfrequency, vector shift or ROCOF), R1 and R2 de-energize after the adjustable tripping delay. As soon as the measured value returns to the tolerance range - taking into account an adjustable hysteresis – and all further switch-on conditions are fulfilled, R1 and R2 re-energize. Vector shift detection This function can be used to detect a possible loss of mains (islanding). It is disabled by default and can be manually enabled in the menu. Through zero crossings the device detects the vector shift of mains voltage and de-energizes output relays R1 and R2 immediately if the shift exceeds the adjustable threshold e.g. 10 °. Only after the set error time the switch-on conditions will be evaluated in order to start an auto reconnection. ROCOF (Rate of change of frequency df/dt) This function is a further variant to detect of a loss of mains (islanding). If a loss of mains is not detected, the decentralized generator remains connected within the islanded network and might become out of synchronism with the total grid. Therefore a later restoration of the grid supply could lead to damage of the decentralized generator and other devices within the islanded network. The monitoring function ROCOF is disabled by default. It can be manually enabled in the menu. The grid feeding monitoring relay detects voltage zero crossings over an adjustable number of cycles in order to calculate the rate of change of frequency. If the ROCOF exceeds the adjustable threshold e.g. 1 Hz/s, output relays R1 and R2 de-energize after the corresponding tripping delay. Only after the set error time the switch-on conditions will be evaluated in order to start an auto reconnection. © ABB Group September 16, 2018

Grid feeding monitoring relay CM-UFD.M33 Loss of Mains Loss of Mains (or islanding) occurs when part of the public utility network (incorporating generation) loses connection with the rest of the system. If LOM is not detected the generator could remain connected, causing a safety hazard within the islanded part of the network. © ABB Group September 16, 2018

Grid feeding monitoring relay CM-UFD.M33 Rate-Of-Change-Of-Frequency (ROCOF) The ROCOF method is based on the local measurement of the generator voltage and estimation of the rate of change of frequency. The measured rate of change of frequency is compared with a preset threshold. The rate of change of frequency following an LOM event is directly proportional to the amount of active power imbalance between local load and the generator output. © ABB Group September 16, 2018

Grid feeding monitoring relay CM-UFD.M33 Vector shift (VS) The relay measures voltage phase changes in consecutive cycles (or half cycles) and compares the value with the preset threshold. Zero crossing VS is very fast in comparison to other methods such as ROCOF VS is not sensitive to rate of change of frequency © ABB Group September 16, 2018

Grid feeding monitoring relay CM-UFD.M33 Additional functions 3 control inputs for multiple functions Interrupted neutral detection Test function Flexible switch-on conditions Password protection Automatic reconnecting attempts Error memory Control inputs Y1-Y0, Y2-Y0 Both control inputs Y1-Y0 und Y2-Y0 are used as feedback contacts for the 2 switching devices of the section switch. The current status of the switching devices is monitored by the grid feeding monitoring relay. The working principle of the control inputs can be configured as “normally closed”, “normally open”, “auto detection” or completely “disabled”. A failure in the feedback loop has to be removed manually on the device. Y2-Y0 is disabled by default, If 2 switching devices necessary. Input contact Y2-Y0 have to be enabled. Control input Y3-Y0 The function of control input Y3-Y0 can be configured as “remote trip”, “suppress Y1”, “suppress Y2”, “suppress Y1/Y2” or “suppress vector shift”. Working principle of the control input can be configured as “normally open”, “normally closed” or completely “disabled”. Test function The test function can be used to simulate an error in the installation. This way, the delay times of the feedback loops can be determined. A feedback loop includes the output relay, the corresponding switching device and the feedback contact. The test function can be started by pressing the ESC button for 3 seconds. The output relays R1 and R2 de-energize immediately and the CM-UFD.M33 gets feedback signals from the section switch through control inputs Y1-Y0 and Y2-Y0 respectively. The time intervals from de-energizing both output relays to receiving both feedback signals is shown on the display. Return to the menu is realized by confirming with the OK button. Switch-on conditions In order to switch on the section switch after having applied control supply voltage or after a fault, the voltages as well as the frequency must stay within the set tripping thresholds during the switch-on delay. This window of voltage and frequency can be further restricted in the menu “Switch-on conditions”. If one parameter leaves the window, the switch-on process is interrupted. When all parameters fulfill the switch-on conditions again, the switch-on delay restarts. If the function “Short interruption” is enabled in the menu “Switch-on conditions” -> “Switch-on delay”, the switch-on delay will be reduced to 5 s in case of a short interruption of < 3 s. Password Every CM-UFD.M33 is delivered with the same default password for protection of its settings. In order to protect the device from unwanted changes, the password must be changed and the password protection must be enabled. With enabled password protection you can view the parameters, modifications are only possible after having entered the password. If the input password is correct, the protection will be disabled until you leave the menu. The parameters “language”, “switch-off delay” and “contrast” are not password protected. Automatic reconnecting attempts If an error occurs at feedback loop Y1-Y0 or Y2-Y0 (e.g. undervoltage release because of a lightning strike), 0…3 automatic reconnecting attempts will be carried out, taking into account the switch-on conditions. Therefore a temporary feedback error has not to be handled manually. The relevant error in the feedback loop is stored in the error list. Error memory The last 99 events that caused tripping of the grid feeding monitoring relay, as well as any interruption of the control supply voltage, will be recorded by the device. The type of error as well as the time stamp is recorded in the internal error list, accessible via the menu “Error memory”. The list is stored in a non-volatile memory which can be reset by the user. © ABB Group September 16, 2018

Grid feeding monitoring relay CM-UFD.M33 References [as indicated in this report] [1] Dr. Campbell Booth, Loss of mains protection Control inputs Y1-Y0, Y2-Y0 Both control inputs Y1-Y0 und Y2-Y0 are used as feedback contacts for the 2 switching devices of the section switch. The current status of the switching devices is monitored by the grid feeding monitoring relay. The working principle of the control inputs can be configured as “normally closed”, “normally open”, “auto detection” or completely “disabled”. A failure in the feedback loop has to be removed manually on the device. Y2-Y0 is disabled by default, If 2 switching devices necessary. Input contact Y2-Y0 have to be enabled. Control input Y3-Y0 The function of control input Y3-Y0 can be configured as “remote trip”, “suppress Y1”, “suppress Y2”, “suppress Y1/Y2” or “suppress vector shift”. Working principle of the control input can be configured as “normally open”, “normally closed” or completely “disabled”. Test function The test function can be used to simulate an error in the installation. This way, the delay times of the feedback loops can be determined. A feedback loop includes the output relay, the corresponding switching device and the feedback contact. The test function can be started by pressing the ESC button for 3 seconds. The output relays R1 and R2 de-energize immediately and the CM-UFD.M33 gets feedback signals from the section switch through control inputs Y1-Y0 and Y2-Y0 respectively. The time intervals from de-energizing both output relays to receiving both feedback signals is shown on the display. Return to the menu is realized by confirming with the OK button. Switch-on conditions In order to switch on the section switch after having applied control supply voltage or after a fault, the voltages as well as the frequency must stay within the set tripping thresholds during the switch-on delay. This window of voltage and frequency can be further restricted in the menu “Switch-on conditions”. If one parameter leaves the window, the switch-on process is interrupted. When all parameters fulfill the switch-on conditions again, the switch-on delay restarts. If the function “Short interruption” is enabled in the menu “Switch-on conditions” -> “Switch-on delay”, the switch-on delay will be reduced to 5 s in case of a short interruption of < 3 s. Password Every CM-UFD.M33 is delivered with the same default password for protection of its settings. In order to protect the device from unwanted changes, the password must be changed and the password protection must be enabled. With enabled password protection you can view the parameters, modifications are only possible after having entered the password. If the input password is correct, the protection will be disabled until you leave the menu. The parameters “language”, “switch-off delay” and “contrast” are not password protected. Automatic reconnecting attempts If an error occurs at feedback loop Y1-Y0 or Y2-Y0 (e.g. undervoltage release because of a lightning strike), 0…3 automatic reconnecting attempts will be carried out, taking into account the switch-on conditions. Therefore a temporary feedback error has not to be handled manually. The relevant error in the feedback loop is stored in the error list. Error memory The last 99 events that caused tripping of the grid feeding monitoring relay, as well as any interruption of the control supply voltage, will be recorded by the device. The type of error as well as the time stamp is recorded in the internal error list, accessible via the menu “Error memory”. The list is stored in a non-volatile memory which can be reset by the user. © ABB Group September 16, 2018