‘YGFC’ FAN COIL UNITS NEW PRODUCTS - 2006
YGFC FAN COIL UNIT FACTORY LOCATED IN GUANGZHOU, CHINA CERTIFICATION CAPACITY = 300,000 UNITS/YEAR = 1,000 UNIT/DAY! CERTIFICATION ISO 9001:2000, GB/T 19002:2000 CERTIFIED FACTORY GB/T 19232:2003 CERTIFIED TEST LAB (ONLY 2 IN CHINA)
YGFC FAN COIL UNIT FEATURES CE (TUV) CERTIFIED TESTING CONFIGURATION: CONCEALED, CABINET, HORIZONTAL, VERTICAL COIL: 2 CHOICES, CONVENTIONAL OR DISTRICT COOLING 10 SIZES (70-600 L/S, 1-15KW COOLING) DRAIN PAN: DIE-FORMED, ANTI-RUST PAINTED, INSULATED MOTORS: DIRECT DRIVE, THERMAL PROTECTION, BALL BEARING TESTING COIL PRESSURE TESTED AT 2400 KPA MOTOR TESTED FOR EARTH LEAK AND CURRENT
YGFC FAN COIL UNIT SPECIFICATION 3 OR 4 ROW COIL, WORKING PRESSURE 1600kPa FILTER: 6mm NYLON 1mm GALV.STEEL CASING FOR ADDED NOISE REDUCTION INSULATED PAINTED DRAIN PAN 10mm COATED FIBREGLASS INSULATED FAN DECK & COIL SECTION
YGFC FAN COIL UNIT OPTIONS CASING: FULLY POWDER COATED FILTER: 25 MM ALUMINUM FINS: HYDROPHILIC, EPOXY COAT, COPPER STAINLESS STEEL DRAIN PAN MOTORS: IP 23 AS STANDARD, 42 & 54 AS OPTION 6mm CLOSED CELL INSULATED RETURN PLENUM, ELECTRIC HEATER
YGFC FAN COIL UNIT ADVANTAGES CHOOSE FROM 10 MODEL SIZES TO MATCH ROOM NEED LOW HEIGHT (250MM) SUITABLE FOR TOWER BLOCKS WHISPER-QUIET OPERATION RESISTANCE TO CORROSION ADAPTABILITY TO STANDARD OR DISTRICT COOLING APPLICATION
YGFC FAN COIL UNIT ADVANTAGES EASE OF MAINTENANCE LOW RISK OF LEAKS FROM DRAIN PAN AND COIL CONNECTIONS LOW RISK OF BEARING WEAR LONGER MOTOR LIFE – LONGER UNIT LIFE! ECONOMICAL LIFE CYCLE
DISTRICT COOLING Definition Produce chilled water at a central plant Distribute to buildings for AC needs Charge subscribers based on actual usage Benefits Diversity reduced capacity, reduced cost Large size $/Ton, 11kV, eff systems & eqpt, life Containment maintenance (AC vs WC), noise Cogeneration and use of waste energy
DISTRICT COOLING WHERE City Centers: large buildings & loads, premium space Airports: large buildings & loads, continuous operation Industrial Centers: many process loads, reliability DESIGN Low flow (1.5 gpm/ton) high ΔT, small pipes & pumps Low supply chilled water temperature smaller AS Check for laminar flow in FCU poor cooling Reynolds number > 4000 Ensure appropriate ΔT on airside of heat exchanger
YGFC FAN COIL UNIT POINTS TO NOTE! THIS IS A ‘HIGH VOLUME’ PRODUCT - SIMPLE SPECIFICATION ALLOWS LOW COST & SPEEDS UP LEAD TIMES TARGET LOW END SPEC. PROJECTS, AND SALES TO DISTRIBUTORS AND END USERS LESS RANGE OF OPTIONS & SQ’S WHEN COMPARED TO ‘EUROPEAN’ FCU’S FCU CASING NOT THE MOST ATTRACTIVE! ARE YOU ABLE TO ORDER & HOLD STOCK UNITS??
YGFC FAN COIL UNIT POINTS TO NOTE! THERMOSTATS & CONTROLS AVAILABLE FROM ASIA PACIFIC ARE NOT CE CERTIFIED VALVES ARE NOT FACTORY FITTED FILTER REMOVAL ON CEILING CONCEALED UNIT IS DIFFICULT AS IT REQUIRES SCREW REMOVAL EUROVENT CERTIFICATION WILL BE MADE LATE 2006
YGFC SOFTWARE YORK DESIGNED, INDEPENDENT OF YORKWORKS
- GENERATES TECHNICAL SCHEDULES… YGFC SOFTWARE - GENERATES TECHNICAL SCHEDULES… - GENERATES WORKS ORDER
YGFC SOFTWARE ALSO GENERATES… OPTIMUM FCU CONTAINERISATION FOR SHIPPING CATALOGUE DATA SHEETS & TECHNICAL SPECIFICATIONS PRICE SUMMARY
WHO TO CONTACT…. TECHNICAL James Long (james.long@yorkna.com.cn), DOCUMENTATION Alan Hinton (alan.hinton@uk.york.com) PRICING SQ’S & SQ PRICING James Long (james.long@yorkna.com.cn), c.c. to Alan Hinton (alan.hinton@uk.york.com) ORDERS Jackey Que (jackey.que@yorkna.com.cn), c.c to James Long (james.long@yorkna.com.cn) SHIPPING Erica Wang (erica.wang@yorkna.com.cn) WARRANTY Ding yue (ding.yue@yorkna.com.cn), c.c to Kevin Lau (kevin.lau@yorkna.com.cn) SOFTWARE