Munters DOAS, Chilled Beams and VRV

Slides:



Advertisements
Similar presentations
Chapter 3. HVAC Delivery Systems
Advertisements

Environmental Controls I/IG Lecture 14 Mechanical System Space Requirements Mechanical System Exchange Loops HVAC Systems Lecture 14 Mechanical System.
HVAC 101 The Basics of Heating, Ventilation and Air Conditioning
Components of HVAC System
1Taylor Engineering, LLC Group Think Mark Hydeman, P.E., FASHRAE Taylor Engineering, LLC
Chilled Beam Presentation
Ceiling Radiant Cooling Panels as a Viable Distributed Parallel Sensible Cooling Technology Christopher L. Conroy, E.I.T. L. D. Astorino Companies, Pittsburgh.
Energy in Focus Energy Savings with Water Based Systems By Maija Virta Specialist of Indoor Environment Technology.
ASHRAE Presentation: VRF Overview Mitsubishi Electric Presenter: Phone number ©2011 Mitsubishi Electric& Electronics USA, Inc.
HVAC Systems Overview HVAC Overview - # 1 Tom Lawrence
Brett Graham Habegger Corporation Midwest Regional Sustainability Summit May 1, 2015.
Active beams versus VAV with Reheat Analysis of May 2013 ASHRAE Journal article Ken Loudermilk Vice President, Technology & Developement.
Refrigeration and Heat Pump Systems Refrigeration systems: To cool a refrigerated space or to maintain the temperature of a space below that of the surroundings.
Air Conditioning Systems
Important variables Water: Air: Conversion:
Announcements Midterm Project Prepare groups of 3 to 4 students You can submit the list at the end of next class Midterm Exam 03/09/10 - In class Exam:
Lecture Objectives: Finish with HVAC Systems Discuss Final Project.
N VAV system varies the air quantity rather than temperature to each zone n Single main duct is run from AHU n Branch duct are run from this main through.
A Trane Air Conditioning Clinic Psychrometry Air Conditioning Clinic TRG-TRC001-EN © American Standard Inc
Hilton Hotel at BWI Airport Nathan Patrick The Pennsylvania State University Architectural Engineering – Mechanical Option.
Learning, our way Daikin Europe, Consulting sales section1 Understanding Client’s Needs and best Daikin solution.
2003 ASHRAE Annual Meeting Kansas City Energy Conservation Benefits of a DOAS with Parallel Sensible Cooling by Ceiling Radiant Panels Jae-Weon Jeong Stanley.
Greenbriar East Elementary School Fairfax, Virginia Michelle L. Siano Mechanical Option Spring 2005 Senior Thesis.
Final Projects Grading criteria is posted on the course website Preliminary results are due Next Tuesday Final Project delivery on Monday Dec. 7 th –Final.
Announcement Course Exam November 3rd In class: 90 minutes long Examples will be posted on the course website.
Introduction to Energy Management. Week/Lesson 13 Control Strategies for Occupant Comfort.
Hamot Women’s Hospital Erie, PA Michael Galleher Mechanical Option l AE-Senior Thesis l April 12, 2011 l Advisor Dr. Jelena Srebric.
Lecture Objectives: Discuss the exam problems Answer question about HW 3 and Final Project Assignments Building-System-Plant connection –HVAC Systems.
Alexander Radkoff Mechanical Option | Spring 2014 Advisor: Dr. Stephen Treado 123 Alpha Drive Pittsburgh, Pennsylvania
Advanced Humidity Control. Energy Efficient Desiccant Based Dehumidification New class of desiccants that regenerate at lower temperatures Now able to.
A New (Rational) Way To Condition Air (and Save Energy) AEE, Philadelphia February 18 th 2016 Andrew Mongar, President, AirGreen LLC.
Michael Reilly, Jr. – Mechanical Option Advisor – James Freihaut, PhD & Dustin Eplee The Pennsylvania State University Nassau Community College Life Sciences.
HCB 3-Chap 19A: All-Air Systems_Single Zone 1 Chapter 19A: ALL-AIR SYSTEMS: SINGLE ZONE AND SINGLE DUCT Agami Reddy (July 2016) 1)Introduction and common.
Maria’s Restaurant Chapter 2 Section 9
Lecture Objectives: Discuss HW3 parts d) & e) Learn about HVAC systems
Maria’s Restaurant Chapter 2 Section 7
Technology in Architecture
HVAC EQUIPMENT: COOLING SOURCES (see Chapter 16)
Doug Jefferson, Business Development Engineer
David Anderson Mechanical Option
Grunenwald Science and Technology Building
Types of HVAC Technology Used in Business Establishments
Eastern Pennsylvania Laboratory Facility
Lecture Objectives: Discuss HW3 parts d) & e) Learn about HVAC systems
New Options for DryCool Products
Munters DH Systems for Hospital Applications
Indoor Pool Design and Dehumidification
Indoor Pool Design and Dehumidification
Lecture Objectives: Answer questions related to HW 4
Energy Efficiency in District Coiling System
Munters DOAS and Chilled Beams
Brian Wallingford, Applications Engineer
Chilled Beam Performance:
Cheryl Hughes Regional Sales Manager October 6, 2015
Variable Frequency Drive (VFD)
Engineering Presentation
HCB 3-Chap 19A: All-Air Systems_Single Zone
Presented by Scott McGinnis June 2012
Variable Refrigerant Volume
Munters Heat Exchangers DOAS Review: Cost to Operate & Energy Analysis
Frenger “Radiant” chilled beam performance at 1 Shelly St - Sydney
Lecture Objectives: Discuss HW4 parts
FBE03: Building Construction & Science
Professor of Architectural Engineering College of Engineering
Announcements Exam 1 Next Class (Thursday, March 14th):
Objective Revie the Cooling Cycle Learn about air distribution systems
Maria’s Restaurant Chapter 2 Section 7
Maria’s Restaurant Chapter 2 Section 9
Maria’s Restaurant Chapter 2 Section 8
Presentation transcript:

Munters DOAS, Chilled Beams and VRV Scott McGinnis Regional Sales Manager LEED Associate March 7, 2011

Overview Chilled Beams and Variable Refrigerant Volume Systems Moisture Control Equipment

Why the Shift to Beams and VRV? 42” Duct 2” Pipe 5/8” Refrigerant Pipe – All move the same amount of energy.

Active Chilled Beams

Reasons For Chilled Beam

Reasons For Chilled Beam

Reasons For Chilled Beam

Variable Refrigerant Volume (or Flow) VRV Single outdoor unit Multiple indoor units Extra Long Piping runs Variable Capacity Modulation Indoor units fit zoning needs Low Noise Environment Architectural – (design & savings) Individual control Temperature set point Fan speed Mode (cool, dry, fan or heat) Complete variable capacity modulation, based on load requirement.

Central A/C System VRV System Cooling tower Outdoor unit Outdoor unit Pump Water piping Indoor unit Refrigerant piping VAV Boxes Valves Pump AHU Remote controller For cooling For heating

Perfect Team Chilled Beams must have DOAS Unit to Prime the System Chilled Beams are Sensible only devises, no latent capacity Chilled Beams run 58-60°F water thru pipes in each room, NO DRAIN PAN VRV Systems need DOAS Systems As in all DX systems, most efficient when only doing sensible cooling only VRV-ness of the system wants to unload when T-Stat is met

Calculating building moisture load is more important Size the DOAS to handle ALL the internal latent load Prevents chilled beams from sweating #1 fear of design engineers I have spoken with You make quell that fear with Munters Provides proper space %rh Allows VRV systems to operate at most efficient Prevents condensation within AHUs Mold grown Maintenance of wet coils, etc… Proper space %rh

Calculating building moisture load is more important

Typical Buildings & DOAS Designs (does not handle the indoor humidity load) Space Served Dew Point Control Meeting Space Single 51-55 F Loose Grocery Store 48-52 F Medium Pharmaceutical 49-56 F Tight Hotel / Condo. Multiple 54–56 F Office 52-55 F Classrooms Healthcare Depends 42-52 F

How dry does the OA need to be? ASHRAE shows how to calculate how DRY the OA needs to be in order to control space moisture If you want to maintain 75°F at 50%rh, then the space is at 55°F dewpoint You need to deliver air drier than 55°F dewpoint

Use the Correct OA Condition 106 gr/# 131 gr/#

Internal People Load vs Ventilation QL = 1 person = 200 btu/per Ventilation Required 15 CFM per Person Capacity What dewpoint air at 15 cfm will absorb all the moisture given off by a person sitting at rest?

Math Ventilation Air: 15 cfm x 30 students = 450 (6,000 + 3,050*) btuh = 450 x .68 x Delta Grains 9,050 = 306 x Delta Grains 9,050 / 306 = 30 gr/# Dewpoint of 450 cfm OA to achieve: 75°F/50% = 35°F 75°F/55% = 41°F 75°F/60% = 48°F Lower than the past The Munters Story Munters Products *3,050 = Simple Formula for infiltration for standard classroom

Conventional Options Coil Tonnage is large for lower dew points

What to offer with VRV systems Because VRV systems are already packaged DX, it makes sense to stick with that method DryCool DryCool ERV 3 Fan DryCool – ERV 1500 – 16,000 cfm capacities Determine Airflow and Delivered Gr/#

DryCool Standard No energy recovery Low dew points Retrofits and smaller projects

DryCool ERV Energy recovery Indoors without remote ACCU

The Hammer: 3 Fan DryCool ERV 75°F/40.3 dp 75°F/56 dp 81°F/61.5 dp 53°F/53 dp 7,000 cfm and 20 tons 93°F/68°F dp

Benefits of DryCool Control the space moisture, and thus %rh Allow VRV system to operate sensible only. Most cost efficient way to run Dry coils Dry drains May be able to downsize FCU or DX coil rows/fpi Decrease PD Decrease First Cost Reduce Refrigerant tons DryCool system offers highest EERs of any DOAS Reduced Operating costs

What to offer with chilled beams Chilled beams want 58-60°F water in the coils DOAS needs low dew point, Thus typically uses a coil with low chilled water temps; 42-45°F EWT Is there an advantage of using just 60°F water in the DOAS? 2x ? 42°F to DOAS 60°F to Chilled Beams

This 45gr/# delivered system requires a chilled water coil delivering 52.7°F dry bulb air: EWT = 45°F Why use 45°F water for this unit and 60°F for chilled beams?

Chiller Efficiency Big difference between 42°F water and 60°F water

Chiller Efficiency Big difference between 42°F water and 60°F water 42F Chiller 32% Lower operating cost 60F Chiller

How to use DryCool process to benefit? If possible, use the DryCool ERV or 3 Fan DryCool No need to run chilled water to the DOAS Delete Pumps, Piping, Piping Insulation and such to unit Down size chiller plants for just the chilled beams and keep them at 60°F water

Total tons: CW (56) + DX (84) + Post (13) = 153 tons 65°F/80Gr 60°F 82°F/80Gr 69/44Gr After E Wheel 56°F/61Gr Dry Air Total tons: CW (56) + DX (84) + Post (13) = 153 tons Semco was at 156 tons but required 45°F chilled water

Semco 182”w x 146”h x 448” L 37,000 cfm

Passive DH depends on what is uncontrolled Short tonnage if RA %rh is out of control 50% rh 60% rh

Plan of action for chilled beam or VRV Help calc latent loads People, infiltration, permeance Discuss that DOAS equipment should take care of entire latent load Sell DryCool process: We drive the moisture out of the DH wheel VRV, all packaged DX is similar, less energy Chilled beams Show benefits of one simple chiller plant with 58-60F water By using all package DX By using Hybrid of Chilled Water and DX with DryCool Use a standard product if possible Quicker selection Better price points Talk to factory about custom version to meet the engineers and owners needs Discharge air temps, control Layouts Plates vs. wheels, etc.

Point engineers to the fact that most of our competition is the baseline.