Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 OFA200 Overview Application area MultiJet, UltraOil, Oil- and Gas fan burner (1- and 2-Stage, modulating) Introduction 2014 with TTE Supplier Adlos, Balzers (FL) © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Instalation situation All MultiJet and UltraOil <50 © Hoval / Nov-18 Hoval
Instalation situation UltraOil from 50kW © Hoval / Nov-18 Hoval
Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 Layout © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 Fixe I/Os (Config) WF Boiler sensor PW Water pressure sensor (ON/OFF) RS485 Communication to conroller Netz Power supply SK1 Condensation lifting-station SK2 Emergency-stop switch SK3 Fire protection switch SK4 STB / ATB SK5 Water pressure switch BR1 / BR2 Burner connection Y4 Additional air flap Y6 Main gas-valve/Oil magnetic-valve © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Status overview FA-Status 0 Passive state WEZ = OFF 1 Demand operable 2 WEZ locked (WEZ lock or AT lock activ) 3 Leadtime Oil-/Gas magnetic valve, mainpump/ shut-off device (Y6 ,Y10) 4 Leadtime fluegas flap/ additional air flap (feedback expected) 5 Clearance to start the boiler (ST1) 6 Stage 1 ON 61 Demand operable step 2 7 Stage 2 ON (only at 2 stage WEZ) 8 Stage 1 ON, Stage 2 locked (at lock WEZ ST2) 9 ON, start time modulation (only for modulating burners) 10 ON, free modulation (only for modulating burners) 11 OFF, follow-up time Oil-/Gas magnetic valve or shut-off device (Y6) 12 Follow-up time main pump (Y10) 13 WEZ blocked 14 WEZ locked 15 S3 Error 16 Locking external © Hoval / Nov-18 Hoval
Schaltfolge © Hoval / Nov-18 Hoval
Parameter overview OFA 200 Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 Parameter overview OFA 200 Information tree Information Counter Error Parameter tree Config System Burner Main pump Water pressure Thermostat External Relay test Matching © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Adjustable I/Os (Config) Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 Adjustable I/Os (Config) WEZ Type OFF 1: One-stage WEZ 2: Two-stage WEZ 3: Modulating WEZ VA1 1: Main pump 2: Parallel WEZ-clearance 3: Thermostat operation 4: Operating indication 5: Error output VA10V (PWM) AUS 1: WEZ Output Set 2: WEZ Output Actual 3: WEZ Temperature Set 4: WEZ Temperature Actual 5: Main pump (Modulation) VA2 OFF 1: Main pump 2: Parallel WEZ-Clearance 3: Thermostat operation 4: Operating indication 5: Error output © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Adjustable I/Os (Config) Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 Adjustable I/Os (Config) AGF OFF 1: Flue gas sensor 2: Information sensor 3: Boiler sensor 2 4: Return sensor 5: WEZ-lock 6: Stage lock Stage 2 VE1 Characteristic curve WF KTY PT1000 Characteristic curve AGF Characteristic curve VE1 © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 Information STATUS FLOW WF FLOW 2 WF-2 RETURN RL FLUE GAS AGF WATER PRESSURE WD TEMPERATURE INFO 10V OUTPUT MAIN PUMP HP-ASP VALVE SK1 SK2 SK3 SK4 SK5 LOCK-WEZ VE- LOCK-ST2 VE- THERMOSTAT VA- BR1 BR2-OPEN BR2-CLOSED VERSION © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 Counter + Error Count Operation time and starts of Stage 1 and Stage 2 Operation time and of modulation >50% and =<50% Memorize of 25 errors with 7 values each Sequence number Error code Date Time Operating status WF temperature VE1 temperature AGF temperature © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 System Resets of WE, counter and errors Adjunstment operation-hour counter OFF: without count 1: Count at feedback / demand 2: Count only at feedback WEZ (depending boiler type) 3: Count only with feedback signal Characteristig error output 1: Locking 2: Locking, Blocking 3: Locking, Blocking, Warning Priorisation Set value 1: Heating circuit 2: Hot water 3: Always the higher © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 Burner Minimum set value Maximum set value Emergency operation at bus failure OEM maximum temperature Temperature gradient (WF) K/min Lock time Number till locking Minimum running time AT-Lock Adjunstments sensor operating mode 1: Signal of KS / UB, Stages OFF 2: UB without error message (Burner OFF) 3: UB / KS warning message with clearance © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 Burner Start-up differential to release operating point 1 Release operating hysteresis 1 Functions stage 2 Start-up differencial to release operating point 2 Release operating hysteresis 2 Stage 2 time-out at heating Stage 2 time-out at hot water Stage 2 hot water loading Delayed Complete blocked Stage 2 AT-Lock © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Burner © Hoval / Nov-18 Hoval
Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 Burner Modulation Start output Start time Running time Output minimal Output maximal PI-K - increase PI-n – reset time PI-Ta – scan time Magnetic valve Opening time Close time AGF functions STB Block time and –temperature Flue gas /additional air monitoring Feedback burner (B4/B5) © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 Main pump Lead / stopping time Operating mode 1: Boiler output 2: dT-Control (WF to RLF/WF2) Example main pump controlled by boiler output: Par. 33796 1.5V OFF voltage Par. 33797 2.5V Min. voltage (1) Par. 33798 25% Output value at min. voltage(1) Par. 33799 10.0V Max. voltage(2) Par. 33800 100% Output value at max. voltage (2) Par. 33809 100Hz PWM frequency © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 Main pump Example main pump controlled by boiler output : Par. 33801 25% Start-up output Par. 33802 5Min. Start time dT Regulation Par. 33803 2%/K PI-Regulation K-Increase Par. 33804 180Sec. PI-Regulation Tn-Reset time Par. 33805 20Sec. PI-Regulation Ta-Scan time Par. 33806 1 Priority dT Hzg. Par. 33807 20K dT Heating Par. 33808 20K dT Hot water Par. 33796 1.5V OFF voltage Par. 33797 2.5V Min. voltage (1) Par. 33798 25% Output value at min. voltage (1) Par. 33799 10.0V Max. voltage (2) Par. 33800 100% Output value at max. voltage (2) Par. 33809 100Hz PWM Frequency © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Water pressure and Thermostat Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 Water pressure and Thermostat Water pressure Warning min. Blocking min. Warning max. Blocking max. Locking max. Time delay till error Thermostat function (VA1 / VA2) Sensor input Set value Switching differential © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 External Adjustment for 0-10V output Example set temperature: Par. 34574 10°C Min. temperature (1) Par. 34575 1.0V Min. voltage (1) Par. 34576 90°C Max. Temperature (2) Par. 34577 9.0V Max. voltage (2) Par. 34578 4.0V Min. voltage Par. 34579 9.0V Max. voltage © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 External Adjustment for 0-10V output Example set output (1/2 stage): Par. 34561 0V WEZ – OFF Par. 34562 5V WEZ – 1.Stage ON Par. 34563 10V WEZ – 2. Stage ON © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 External Adjustment for 0-10V output Example set output (modulating): Par. 34564 1% Min. output (1) Par. 34565 0.1V Min. voltage (1) Par. 34566 100% Max. output (2) Par. 34567 9.0V Max. voltage (2) Par. 34568 4.0V Min. voltage Par. 34569 9.0V Max. voltage © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 External Adjustment for 0-10V output Example actaul temperature: Par. 34580 0°C Min. temperature (1) Par. 34581 0,0V Min. voltage (1) Par. 34582 120°C Max. temperature (2) Par. 34583 10.0V Max. voltage (2) © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 External Adjustment for 0-10V output Example actual output: Par. 34570 0% Min. output (1) Par. 34571 0,0V Min. voltage (1) Par. 34572 100% Max. output (2) Par. 34573 10.0V Max. voltage (2) © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval
Hoval Steuerung/Regeltechnik/Software - Verkäufertagung 2011 15.11.2018 Relaistest + matching Relay test Relay test active BR1 BR2 – open BR2 – close Valve (Y6) VA1 VA2 VA10V PWM Matching WF AGF VE1 PW © Hoval / Nov-18 Hoval Steuerung/Regeltechnik/Software © Hoval