SmartLetLoose/ONE Fire Extinction Board
Extinction Board Wiring SmartLetLoose/ONE Extinction Board Wiring SmartLine panel
Extinction Board Wiring SmartLetLoose/ONE SmartLight panel
Balance MAN-EXT terminals with a 47kΩ resistance Initial Wirings SmartLetLoose/ONE Initial Wirings Balance MAN-EXT terminals with a 47kΩ resistance Balance STOP_EXT terminals with a 47kΩ resistance Balance PRESS terminals with a 47kΩ resistance
If terminals aren’t balanced panel displays: Initial Wirings SmartLetLoose/ONE Initial Wirings If terminals aren’t balanced panel displays: Fault 01/03 Open I/O ManualExtinguish Extin.module Fault 02/03 Open I/O Lock extinguish Extin.module Fault 03/03 Open I/O Pressure switch Extin.module
Balance PRE-EXT terminals with a 47kΩ resistance Initial Wirings SmartLetLoose/ONE Initial Wirings Balance PRE-EXT terminals with a 47kΩ resistance Balance RELEASED terminals with a 47kΩ resistance
If terminals aren’t balanced panel displays: Initial Wirings SmartLetLoose/ONE Initial Wirings If terminals aren’t balanced panel displays: Fault 01/02 Open I/O Pre-extinguish Extin.module. Fault 02/02 Open I/O Released Extin.module
SmartLetLoose/ONE Electrovalve Wiring 24V Electrovalve
If terminals aren’t connected panel displays: Electrovalve Wiring SmartLetLoose/ONE Electrovalve Wiring If terminals aren’t connected panel displays: Fault 01/01 Open I/O Valve output Extin.module
SmartLetLoose/ONE Manual Extinguish Connect a callpoint or a generic NO contact to have a manual Extinguish input NO contact 15kΩ resistance 47kΩ resistance
SmartLetLoose/ONE Stop-Extinguish Connect a callpoint or a generic NO contact to have a manual Stop-Extinguish input NO contact 15kΩ resistance 47kΩ resistance
it can activate a device (eg a led) Stop-Extinguish SmartLetLoose/ONE Stop-Extinguish If fire extinguishant system has been stopped, “R” terminal closes to GND: it can activate a device (eg a led) Device +24V - +
A generic NO contact connected to PRESS teminals can be used as: Pressure Switch SmartLetLoose/ONE Pressure Switch A generic NO contact connected to PRESS teminals can be used as: - Supervisory: to monitor gas pressure - From pressure: to confirm that gas cylinders are empty - From flow detector: to confirm that gas has be released NO contact 15kΩ resistance 47kΩ resistance
SmartLetLoose/ONE Pre-Extinguish PRE-EXT output (terminals 10-11) is activated on Pre-Extinguish: it can activate some devices 47 kΩ End of Line resistance on the last device
Pre-Extinguish SmartLetLoose/ONE Fault 01/01 Short I/O Pre-extinguish Extin.module If panel displays “Short I/O Pre-Extinguish” it will need connect a diode in series (if devices haven’t it) 47 kΩ End of Line resistance on the last device
SmartLetLoose/ONE Released RELEASED output (terminals 12-13) is activated when gas extinguishant is released: it can activate some devices. 47 kΩ End of Line resistance on the last device
Released SmartLetLoose/ONE Fault 01/01 Short I/O Released Extin.module If panel displays “Short I/O Released” it will need connect a diode in series (if devices haven’t it) 47 kΩ End of Line resistance on the last device
Extinction Board Configuration SmartLetLoose/ONE Extinction Board Configuration Extinction Board have to be configured from panel
Extinction Board have to be configured from panel Extinction Board Configuration SmartLetLoose/ONE SmartLine Panel Enable panel programming phase Extinction Board have to be configured from panel
Extinction Board have to be configured from panel Extinction Board Configuration SmartLetLoose/ONE SmartLine Panel Control Panel IN PROGRAMMING Ver: 2.03 01/01/12 17:45 Settings Disablement Maintenance Programming Configuration Progr. Zone Progr. Output Progr. Timer Extinction Board have to be configured from panel Acquire int.bus Acquire ext.bus Current Devices Extin.module O Expansion O Ok to execute Current Devices Extin.module 1 Expansion O Ok to execute
Extinction Board have to be configured from panel Extinction Board Configuration SmartLetLoose/ONE SmartLight Panel Enable panel programming phase Extinction Board have to be configured from panel
Extinction Board have to be configured from panel Extinction Board Configuration SmartLetLoose/ONE SmartLight Panel Panel IN PROGRAMMING Ver: 2.02 01/01/12 17:45 Settings Disablement Maintenace Programming Configuration Progr.Point Progr.Zone Progr. Timer Extinction Board have to be configured from panel Loop Bus Extinguish board O Smart Level O Repeater O Ok to continue Extinguish board 1 Smart Level O Repeater O Ok to continue
SmartLetLoose/ONE Programming Enable panel programming phase Extinction board is programmed the same way both from SmartLine panel and from SmartLight panel
Programming SmartLetLoose/ONE Control Panel IN PROGRAMMING Ver: 2.03 01/01/12 17:45 Settings Disablement Maintenance Programming Progr. Output Progr. Timer Progr. Holiday Extinguish YES: Zone activates extinguish commands NO: Zone doesn’t activate extinguish commands Zone mask: Zone 01 YES Zone 02 YES Zone 03 YES At least 1: The extinguishant gas release will activate if at least one of the selected zones go into alarm status At least 2: The extinguishant gas release will activate if at least two of the selected zones go into alarm status All zones: The extinguishant gas release will activate if all selected zones go into alarm status Mode: At least 2
Programming SmartLetLoose/ONE Control Panel IN PROGRAMMING Ver: 2.03 01/01/12 17:45 Settings Disablement Maintenance Programming Progr. Output Progr. Timer Progr. Holiday Extinguish Zone mask: Zone 01 YES Zone 02 YES Zone 03 YES Do not confirm: extinguishment module doesn’t await confirmation Wait for press.: extinguishment module awaits confirmation from pressure switch Wait for flow: extinguishment module awaits confirmation from flow detector Confirm exting. Do not confirm
Programming SmartLetLoose/ONE Control Panel IN PROGRAMMING Ver: 2.03 01/01/12 17:45 Settings Disablement Maintenance Programming Progr. Output Progr. Timer Progr. Holiday Extinguish Zone mask: Zone 01 YES Zone 02 YES Zone 03 YES Supervisory: PRESS input monitors gas pressure From pressure: PRESS input confirm that gas cylinders are empty From flow det.: PRESS input confirm that gas has be released Pressure switch Supervisory
SmartLetLoose/ONE Pre-extinction time Extinguish time Programming SmartLetLoose/ONE Control Panel IN PROGRAMMING Ver: 2.03 01/01/12 17:45 Settings Disablement Maintenance Programming Progr. Output Progr. Timer Progr. Holiday Extinguish Pre-extinction time T.pre-extinct 00 min. 10 sec Zone mask: Zone 01 YES Zone 02 YES Zone 03 YES Extinguish time T. extinguish 00 min. 02 sec If it is undefined, valve switch will be open until reset T. extinguish Pressure switch Supervisory Manual Pre-extinction time T. pre-ext. man 00 min. 00 sec Other programming Delay between valve switch activation and confirmation T.Confirm ext. 00 min. 05 sec Pause between one gas discharge and another in the event of non-confirmation T.Gap discharge 00 min. 05 sec
SmartLetLoose/ONE Advanced Programming - Lock extinguish when the room has open doors SmartLine Panel
Connect the series of NC doors contact between “I/O” and “-” terminals Advanced Programming SmartLetLoose/ONE Connect the series of NC doors contact between “I/O” and “-” terminals
SmartLetLoose/ONE “Stop Extinction” “”Swap Alarm-Fault bands” Advanced Programming SmartLetLoose/ONE “Stop Extinction” “”Swap Alarm-Fault bands” Program I/O Line as “Extinction control Input”
SmartLetLoose/ONE Programming from panel Advanced Programming SmartLetLoose/ONE Programming from panel Control Panel IN PROGRAMMING Ver: 2.03 01/01/12 17:45 Settings Disablement Maintenance Programming Configuration Progr. Zone Progr. Output Progr. Timer - Lock extinguish when the room has open doors 01 <Zone 01 02 <Zone 02 03 <Zone 03 04 <Zone 04 10 min. 00 sec. Filter time 30 Detection line I/O line SmartLine panel Program “I.EXTINGUISH” <Zone 01> I.EXTINGUISH Disable exting. NC input NO
Program “Lock extinguish” Advanced Programming SmartLetLoose/ONE Control Panel IN PROGRAMMING Ver: 2.03 01/01/12 17:45 Settings Disablement Maintenance Programming Configurazione Progr. Zone Progr. Uscite Progr. Timer - Lock extinguish when the room has open doors 01 <Zone 01 02 <Zone 02 03 <Zone 03 04 <Zone 04 10 min. 00 sec. Filter time 30 Detection line I/O line SmartLine panel <Zone 01> I.EXTINGUISH Lock extinguish NC input NO Program “Lock extinguish”
SmartLetLoose/ONE - Lock extinguish when the room has open doors Advanced Programming SmartLetLoose/ONE Control Panel IN PROGRAMMING Ver: 2.03 01/01/12 17:45 Settings Disablement Maintenance Programming Configurazione Progr. Zone Progr. Uscite Progr. Timer - Lock extinguish when the room has open doors 01 <Zone 01 02 <Zone 02 03 <Zone 03 04 <Zone 04 10 min. 00 sec. Filter time 30 Detection line I/O line SmartLine panel <Zone 01> I.EXTINGUISH Lock extinguish NC input YES Program “NC input YES”