Regulators Indices on Power Quality DNO Argentinean common experiences are: There are 3 quality levels fixed by the regulator and control stages more complexes with time Voltage continuity (sustained interruptions) Voltage quality (voltage level and disturbances) Commercial quality (meter readings, claims, etc.) DNO are responsible ($) for problems from TNO
Voltage Continuity (Interruptions) Stage 1: average indices based on nominal kVA from interrupted MV/LV transformers (LV level excluded). ENS compute easily. A global fine as function of ENS, returned to all customers. Stage 2: tracking of all interruptions (coming from HV, MV or LV systems) on each individual customer. ENS determination very complex. Monetary refund calculated separately for each customer.
STANDARD DEMAND PROFILE CUSTOMER’S ANUAL BILLING ENS & PENALTIES (VOLTAGE CONTINUITY) HOURS CUTS LIMIT TIME LIMIT NUMBER OF CUTS STANDARD DEMAND PROFILE ENERGY NOT SUPPLIED CUSTOMER’S ANUAL BILLING (kWH billed in the last year) 1 AE (kWh) 24 ENS FOR EACH CLIENT $ TO THE CLIENT’S ENERGY BILL ENS VALUE:1.40 TO 2.71 $/kWh
Voltage Quality Voltage Level: At customer level – more strict that EN 50160 (± 5 % on underground network, 97 % of recording time (7 days)). Limits change on overhead and rural networks. Fine as function of a complex calculation of delivery energy. Voltage Disturbances: Flicker and Harmonics control. Sophisticated and expensive recorders. Must be registered till the 40th harmonic and the kWh linked to each harmonic to calculate fines.
VOLTAGE LEVELS PENALTIES SCHEMA + 7 % + 6 % + 5 % V Vn - 5 % - 6 % - 7 % I
VOLTAGE LEVEL PENALTIES — PENALTY ($/kWh) — Max. Rate (0.105 $/kWh) — Min. Rate (0.027 $/kWh)