Rubustness against Overvoltage by Testing the HVRT Capability of Wind Turbines Dipl.-Wirt.-Ing. Frederik Kalverkamp Division Manager Grid Integration.

Slides:



Advertisements
Similar presentations
Frankfurt am Main (Germany), June 6-9, 2011 Design and Implementation of an Innovative Telecontrol System in the Vattenfall Medium- Voltage Distribution.
Advertisements

Study of Wind Energy Penetration in the Iberian Peninsula RED ELÉCTRICA DE ESPAÑA 1 WIND POWER GENERATION Study of Wind Energy Penetration in the Iberian.
Frankfurt (Germany), 6-9 June 2011 Coordination between TSOs and DSOs – a necessity for system planning and operation Dr. Ralph Pfeiffer Amprion GmbH 1.
ACCIONA WINDPOWER WIND POWER PLANTS AND GRID INTEGRATION EXPERIENCE 2010 –Friday 23 th April Óscar Alonso Teresa Arlabán Alberto García Alejandro González.
Protection notice / Copyright noticeFor presentation in EWEC 2010 HVDC Solution for Offshore Wind Park Comprising Turbines Equipped with Full-Range Converters.
Dynamic VAR’s [D-VAR] What are D-VAR Devices? Dynamic VARs… Fully integrated modular STATCOM with proprietary 3X overload Instantaneously injects precise.
Power Systems Consulting and Software 4 March 2004 BWEA Conference: UK Offshore Wind 2004 Integration of Offshore Wind Farms into the Local Distribution.
1111Challenges for reliable offshore transformersTRANSFORMING YOUR NEEDS INTO SOLUTIONS Challenges for Reliable Offshore Transformers Dr. Jan.
Standardization Aspects in UHV Networks New Delhi, January 2009 Denis Dufournet Chairman IEC TC17 Member CIGRE WG A3-22.
Importance of advanced simulations of electrical system in wind turbines April 2010.
March 2006 Development and Test of a 5 kW Wind Turbine for Modular Autonomous Supply Systems Berthold Hahn Paul Kühn Institut für Solare Energieversorgungstechnik.
Review of progress and future work SQSS Sub Group 2 August 2006 DTI / OFGEM OFFSHORE TRANSMISSION EXPERTS GROUP.
Protection Against Transient Overvoltages
SINTEF Energy Research 1 Fault ride-through testing of wind turbines Presented by: Olve Mo Paper co-authors: John Olav Tande Leif Warland Kjell Ljøkelsøy.
ON DIMENSIONING LVDC NETWORK CAPACITANCIES AND IMPACT ON POWER LOSSES
Electrical Installation 2
Thomas DEGNER -DE- BETA SESSION 4b: Integration of RES+DG Barcelona May DISPOWER Distributed Generation with High Penetration of Renewable.
Barcelona– May 2003 CIRED’2003 Beta session 4a: Distributed Generation Controllability of DG helps managing Distribution Grids J. A. Peças Lopes
Frankfurt (Germany), 6-9 June 2011 ROSA – PT – S3 – 0249 EDP DISTRIBUTION AUTOMATION (r)EVOLUTION.
Frankfurt (Germany), 6-9 June 2011 GONZALEZ–CH–RIFS4–0182 OPERATIONAL STABILITY OF SHUNT CIRCUIT-BREAKER SYSTEMS IN UNGROUNDED MV NETWORKS WITH DISTRIBUTED.
1. Introduction 2. E-On Guidelines 3. Modelling 4. Controller Design 5. Simulation Results 6. Conclusion Voltage Regulator for Reactive Power Control on.
ECE 576 – Power System Dynamics and Stability Prof. Tom Overbye University of Illinois at Urbana-Champaign 1 Lecture 23: Renewable.
Electricity Research Centre, University College Dublin Wind turbine modelling for grid code analysis Alan Mullane & Mark O’Malley Electricity Research.
Voltage grid support of DFIG wind turbines during grid faults
Frankfurt (Germany), 6-9 June 2011 Smart Grid Protection in China Wu Guopei Guangzhou Power Supply Bureau Guangdong Power Grid, China.
GE Energy GE 2.x Zero Power Voltage Regulation Measurement Results Vincent Schellings.
SLIDE 1 ISSUES AND PRACTICAL EXPERIENCES WITH CONNECTION OF WIND FARMS TO WEAK AC NETWORKS June 2013 PRESENTED BY BABAK BADRZADEH.
Bock_DE_Session1_Block1_Question3 Barcelona May 2003 Nexans SuperConductors Dr. Joachim Bock Nexans SuperConductors D Huerth
Abram Perdana, Ola Carlson Dept. of Electric Power Engineering
Daudi Mushamalirwa Luanda June, 2014 Technical issues of the stability of small size electric systems composed of wind generators and conventional generating.
Frankfurt (Germany), 6-9 June 2011 M. Khederzadeh Power & Water University of Technology (PWUT) Tehran, IRAN. M.Khederzadeh – IRAN – RIF S3 – Paper 0066.
Frankfurt (Germany), 6-9 June 2011 Louise Jakobsen, Danish Energy Association – Denmark – Session 3 – Paper 0811 Louise Jakobsen, Danish Energy Association.
Electromagnetic Compatibility Test for CMS Experiment. Authors C. Rivetta– Fermilab F. Arteche, F. Szoncso, - CERN.
Delivering for 2020 TSO Facilitation of Renewables Studies EirGrid Customer Conference Jonathan O’Sullivan October 2009.
Investigating the Impact of Removing the Undervoltage Protection for Wind Turbines Presented by KHALED ALGHADHBAN Chalmers University of Technology School.
Department of Electrical and Electronic Engineering Ariel University Israel, Eilat, 2014 A. LIPSKY, N. MITEVA, E. LOKSHIN Frequency Response of Voltage.
Voltage Control Brad Calhoun Consultant, Sr. Trainer Spring 2016.
Full Converter Wind Turbine Operating under Weak Grid Conditions Daniel Mueller, Walter Kuehn Frankfurt University of Applied Sciences Germany 1.
TECHNICAL PAPER ON SIMULTANEOUS AC-DC POWER TRANSMISSION
EE 2353 HIGH VOLTAGE ENGINEERING Faculty Name :A.JAIBUNISHA Faculty Code : EE 58 Designation : LECTURER Department : EEE.
New prototype modulator for the European XFEL Project (DESY) Pulse Step Modulator (PSM) Technology for long pulse applications.
INSTITUTE OF POWER ENGINEERING GDAŃSK DIVISION Some Results of the Study „ Integration Possibilities of Wind Energy with the Polish.
© ABB Group October 1, 2016 | Slide 1 DynaPeaQ ® SVC Light ® with Energy Storage FACTS.
 The common type of wind power generators are squirrel cage induction generator (SCIG),doubly fed induction generator (DFIG)  For more secure and.
DRAFT Slides for Discussion - Standards, Reports and Recommendations
Graz University of Technology May 11th – 12th Maribor, Slovenia
Motor Protection Dr. Hendro Rijanto.
Agenda TSOG 8th November
Calvert City Power I, L.L.C. (“Calvert”) Purpose of Meeting
Transposition of European Network Codes
A Project Review On POWER QUALITY IMPROVEMENT IN GRID USING STATECOM
FACTS BY SVC, FLEXIBLE AC TRANSMISSION
Modular Multilevel Converter for Wind Energy Storage Systems
IG BASED WINDFARMS USING STATCOM
Analysis of the Amplitude and Frequencies of the Voltage Magnification Transients in Distribution Networks due to Capacitor Switching Mohamed Saied Electrical.
Hellenic Grid Code Requirements for Wind Farms Grid connection
& Transient Voltage Recovery Capacitors
Exam 2 Wednesday, Nov 16, 2016, 5-6:20pm
Electricity Distribution Network Design Training & Courses
Intelligent Power Module
Hellenic Grid Code Requirements for Wind Farms Grid connection
WP-1-P Georgia Tech Annual
Optimization of the Energy-Supply-Structure of modern Aircraft by using conventional power system technologies Dipl.-Ing. Ilir Purellku Electrical Power.
University of Ljubljana, Faculty of Electrical Engineering - Slovenia
Grid integration and stability of 600MW windfarm at Kriegers Flak
FREQUENCY CONTROL-THE UNEXPLOITED GOLD
Waleed Iftikhar Michel Mabano
Hellenic Grid Code Requirements for Wind Farms Grid connection
HIGH VOLTAGE ENGINEERING Presented By P.Sindhu Asst.Prof EEE Dept
National Institute of Wind Energy(NIWE)
Presentation transcript:

Rubustness against Overvoltage by Testing the HVRT Capability of Wind Turbines Dipl.-Wirt.-Ing. Frederik Kalverkamp Division Manager Grid Integration & System Analysis | FGH GmbH WindEurope Summit 2016, 27-29 September, Hamburg, Germany

Agenda Introduction and Motivation HVRT in Grid Codes Testing of HVRT Capability Experiences from Prototype Testing Conclusion FGH GmbH | Kalverkamp | WindEurope Summit 2016 | 28/09/2016

Introduction Current Situation of Fault-Ride-Through LVRT capability mandatory requirement for Power Generating Units (PGU) in grid codes Disconnection threatens grid stability LVRT testing equipment and procedures have been developed by FGH already in 2003 Internationally standardized about 10 years ago (IEC 61400-21) Today new challenges with further penetration of dispersed power generators Temporary overvoltage in high voltage systems New grid code developments and requirements 2015 in Germany: VDE-AR-N 4120 (110 kV) FGH GmbH | Kalverkamp | WindEurope Summit 2016 | 28/09/2016

Motivation Relevance of Overvoltage and HVRT Overvoltage due to Line capacities combined with load shedding or generation tripping Voltage recovery after fault clearance Difference in terms of Time duration (ms…min) Location and propagation Incident in Germany (2012) Capacitive voltage boost after 2ph fault with loss of 1.7 GW  HVRT capability reduces risk of generation tripping voltage in kV time FGH GmbH | Kalverkamp | WindEurope Summit 2016 | 28/09/2016

HVRT in Grid Codes First requirements can be found Result of incident: HVRT capability required in recent grid codes (comparable with LVRT 2003) In focus: VDE-AR-N 4120 specifies dynamic system support of PGUs with LVRT and HVRT capability Up to 130% Un for 100 ms and 125% Un until 60 s Reactive current injection (HVRT -> under-excited) HVRT in IT, RSA, AUS (discussed: USA, DK) European Network Code RfG with no requirement yet (!) Source: VDE 4120 FGH GmbH | Kalverkamp | WindEurope Summit 2016 | 28/09/2016

Testing of HVRT Capability Equipment design FGH development similar to LVRT setup Overvoltage with capacitive charging (Ferranti effect) Also add-on solution (redundant components) Modular layout, scalable and very flexible Max. design: 200% Un, 35 kV 10 MVA FGH GmbH | Kalverkamp | WindEurope Summit 2016 | 28/09/2016

Experiences in HVRT Testing Pilot Projects Testing of ENERCON WT with HVRT prototype testlab >100 tests, up to 140% Un Modified switching sequence to reach rectangular voltage shape, lower overshooting and transients Saturation effects of transformer cause distorted and limited secondary voltage (max.124% Un) Electrical design of the test circuit very crucial to avoid resonances or influences in ripple control  Adequate damping for mitigating resonances is important in system design and test preparation FGH GmbH | Kalverkamp | WindEurope Summit 2016 | 28/09/2016

Experiences in HVRT Testing Grid Code Compliance Behavior of wind turbine according to requirements no disconnection voltage distortion without influence adequate under- exited reactive current FGH GmbH | Kalverkamp | WindEurope Summit 2016 | 28/09/2016

Conclusion HVRT is crucial capability and subject to grid codes Justification due to high decentralization or system characteristics Compliance testing is needed HVRT testlabs available and successful in performance Appropriate setup design important to prevent grid repercussion Grid codes and testing guidelines shall take saturation effects of transformers into account Max. overvoltage, time duration, fault types Further investigation of technologies (DFIG) in terms of configuration and control strategies FGH GmbH | Kalverkamp | WindEurope Summit 2016 | 28/09/2016

Thank you for your attention! frederik.kalverkamp@fgh-ma.de www.fgh-gmbh.com |info@fgh-gmbh.com Visit our booth Pion r since 1921 FGH GmbH | Langstädtler | Company Presentation | Information Slides