Models Alféa Excellia mono 11 kW 14 kW On the wall Présentation rapide de la gamme Alféa Cascade Mono Alféa Excellia Tri 11 kW 14 kW 16kW On the wall Tri
Combination Application : flow 60°C thermodynamique Floor Heating Radiators low T°C or fan coil DHW preperation Devices in cascade 2 3 Alféa Excellia mono 11 14 Alféa Excellia tri 16 Performances kW 16-20 20-26 26-32 32-39 39-48
REGULATOR ACCESSORIES Optional equipements REGULATOR ACCESSORIES Remote control T75 or T78 (wireless) Slave kit Cascade Kit Master: Connectors + Flow cascade Sensor Room sensor T55 or T58 (wireless) Controller kit for 2° circuit Or Swimming pool
HYDRAULIC ACCESSORIES Optional equipements HYDRAULIC ACCESSORIES Option Boiler kit Option Swimming pool Option DHW Option management mixing valve
Installation
2 Alféa Outside sensor Master Slave or Flow cascade sensor Option
Controller
3 Alféa Outside sensor or Flow cascade sensor Option
Alféa + Boiler Outside sensor Slave Master or Flow cascade sensor Option
Electric box
Alféa + DHW DHW DHW Kit Outside sensors Alféa 2 Slave Alféa 1 Master Flow cascade sensor Option DHW DHW Kit or
Alféa + DHW DHW DHW Kit Outside sensor Slave Master Flow cascade sensor Option DHW Kit or
Alféa + DHW DHW Outside sensor Alféa 1 Master Alféa 2 Slave Flow cascade sensor Option
Setting
Setting Paramètre 5700 : Start up level (installor) (I) Configuration 7 : PAC Master. Configuration 8 : PAC slave (Type A installation). Configuration 9 : PAC slave (Type B or C installation) Paramètre 6600 : Specialist level (Engeneer) (S) 1 : PAC Master. 2 : PAC slave 2. 3 : PAC slave 3.
Setting Type A installation Paramètre 5700 : Start up level (installor) (I) Configuration 7 : PAC Master. Configuration 8 : PAC slave (installation type A). Paramètre 6600 : Specialist level (Engeneer) (S) 1 : PAC Master. 2 : PAC Slave 2. 3 : PAC Slave 3. Master parameter : for 1 heating circuit 5710 : Heating Circuit 1 : Off. 5715 : Heating Circuit 2 : On.
Setting Type A installation Slave Parameters : For 1 heating circuit 5710 : Heating Circuit 1 : off. 5715 : Heating Circuit 2 : off. Slave Parameters : For DHW 5731 : Diverter Valve. For 2 or 3 heating circuits : connect to the slave 5710 : Heating Circuit 1 : On. 5715 : Heating Circuit 2 : Off. To manage a boiler or swimming pool : Connect to the Master
Setting Type B installation Paramètre 5700 : Start up level (installor) (I) Configuration 7 : PAC Master. Configuration 9 : PAC slave (installation type B). Paramètre 6600 : Specialist level (Engeneer) (S) 1 : PAC Master. 2 : PAC Slave 2. 3 : PAC Slave 3. Master parameter : for 1 heating circuit 5710 : Heating Circuit 1 : Off. 5715 : Heating Circuit 2 : On.
Setting Type B installation Slave Parameters : For 1 heating circuit 5710 : Heating Circuit 1 : off. 5715 : Heating Circuit 2 : off. Slave Parameters : For DHW 5731 : Diverter Valve. For 2 heating circuits : connect to the Master 5710 : Heating Circuit 1 : On. 5715 : Heating Circuit 2 : On. To manage a boiler : Connect to the Master To manage swimming pool : Connect to the Slave
Setting Type C installation Master and Slaves parameter : Same type B Slave Parameters : For DHW 5731 : Load pump.