Regulations (Standards - 29 CFR) Flammable and Combustible liquids
Advertisements

Flammable and Combustible Liquids
BLR’s Safety Training Presentations
Understanding Its Causes
Flammable and Combustible Liquid & Compressed Gas Handling and Storage
Hazardous Materials Subpart H.
29 CFR 1910 Subpart H Hazardous Materials Presenter Roberto Dickinson OSHA Training Institute Instructor.
1926 Subpart J Establishes the requirements for welding and cutting in the construction industry Establishes requirements for equipment, fire protection,
How would you explain this on the 3394? If Fire Erupts on YOUR Boat If Underway, stop the boat Have everyone who is not wearing a PFD put one on Position.
PROPERTIES OF FLAMMABLE MATERIALS. Flammability Flammable Flammable –Capable of being ignited and of burning –Synonymous with combustible.
Fire Protection and Prevention New England Roofing Industry Partnership.
© BLR ® —Business & Legal Resources What’s the Big Deal? Flammable and combustible liquids: Are easily ignited and ignite with explosive force Burn.
Fires and Explosions.
Safe Handling of Flammable and Combustible Liquids
Spray Finishing Operations/Spray Booth March 9, 2009.
1 Flammable and Combustible Liquids INSY 3020 Spring 2006.
Flammable and Combustible Liquids. Flammable liquids Class I - liquids have flashpoints below 100 degrees F, with vapor pressures not exceeding 40 psia.
Fire Triangle In order to understand how fire extinguishers work, you first need to know a little bit about fire. Four things must be present at the same.
Liquid Fuel Safety Cummins Southern Plains, Ltd..
Laboratory Safety-Flammable Liquids Flammable Liquids and Fire Codes for Laboratories.
FLAMMABLE AND COMBUSTIBLE LIQUIDS
Copyright © Flammable & Combustible Liquids.
Standard 29 CFR Part Flammable & Combustible Liquids.
Patrick Thornton, SNS/FPE June 9, 2008
WFU Explore this site Turn in Safety “Quiz” by Monday. Must make an 80%.
Flammable and Combustible Liquids
NFPA 31 Standard for the installation of Oil- Burning Equipment
Flammable and Combustible Liquids Presented by Martina Schmeling Adapted From OSHA.
HAZARDOUS MATERIALS. OSHA Office of Training and Education - Revised by TEEX 12/05/07 2 Terminal Objective Describe the hazards and requirements of working.
2 Subpart H - Hazardous Materials ( ) Sources of ignition - Precautions Standard: Spray areas – Free from combustible residue Class.
Fire Safety. Fire Safety Introduction Fires ravage 28,000 industrial facilities each year, causing $596 million in direct property damage. Ninety percent.
Fire Prevention for Construction. Four classes of fires  A, B, C, and D 1a.
Safety Training Presentation
Hazardous Materials Subpart H. Subpart H Standards Compressed Gases Acetylene Hydrogen Oxygen Nitrous Oxide Flammable.
3.7.3 Student Book © 2004 Propane Education & Research CouncilPage Identifying Safe Handling Practices for Flammable and Combustible Liquids Injecting.
Hazardous Materials Subpart H. Subpart H Standards Compressed Gases Acetylene Hydrogen Oxygen Nitrous Oxide Flammable.
Flammable and Combustible Liquids. Introduction !The two primary hazards associated with flammable and combustible liquids are explosion and fire !Safe.
FLAMMABLES. 1. PROPERTIES OF FLAMMABLES Combustion (redox) reactions Solids, gases, most commonly liquids Fire Tetrahedron Ignition sources External-
Hazardous Materials CFR Safety & Health Consultation.
Spray Booths Follow safe operating instructions. Spray-finishing operations  Organic materials  Inorganic materials  Dispersed form  Deposited to.
FLAMMABLE AND COMBUSTIBLE LIQUIDS 1 Bureau of Workers’ Comp PA Training for Health & Safety (PATHS) OSHA 29CFR PPT
Subpart F - Fire Protection & Prevention ( ) Flammables/combustibles - Approved containers Fire protection program/equipment 2A fire extinguishers.
Flammable and Combustible Liquids Standard 29 CFR Part City of Council Bluffs Presented by: SilverStone Group © 2006, 2012 Zywave, Inc. All rights.
29 CFR Subpart G Related Terminal Operations and Equipment.
Flammable Liquids Directorate of Training and Education
Safe Handling of Flammable and Combustible Liquids.
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection.
Means of Egress and Fire Protection
Fire Loss Control - Basic Elements
Welding, Cutting and Brazing
“Portable Fire Extinguishers Safety”
Safe Handling of Flammable and Combustible Liquids
Flammable and combustible liquids
Approval Sheets.
Flammable and Combustible Liquids
Fire protection and prevention
Chemical Transfer.
East Carolina University Compressed Gas Safety Training Program
مایعات قابل اشتعال و احتراق پذیر
Fire Prevention Safety Department
Non-compatible chemicals
Flammable & Combustible Liquids
Safe Handling of Flammable and Combustible Liquids
Flammable and Combustible Liquids
Flammable and Combustible Liquids
Spray Booths Follow safe operating instructions
Flammable and Combustible Liquids
Flammable and Combustible Liquids
Presentation transcript:

Hazardous Materials Subpart H

Subpart H Standards 1910.101 Compressed Gases 1910.102 Acetylene 1910.103 Hydrogen 1910.104 Oxygen 1910.105 Nitrous Oxide 1910.106 Flammable and Combustible Liquids

Subpart H Standards 1910.107 Spray Finishing using Flammable and Combustible Materials 1910.108 Dip Tanks containing Flammable and Combustible Liquids 1910.109 Explosives and Blasting Agents

Subpart H Standards 1910.110 Storage and Handling of Liquefied Petroleum Gases 1910.111 Storage and Handling of Anhydrous Ammonia 1910.119 Process Safety Management of Highly Hazardous Chemicals 1910.120 Hazardous Waste Operations and Emergency Response

Subpart H Standards 1910.123 Dipping and coating operations: Coverage and Definitions 1910.124 General Requirements for Dipping and Coating Operations

Subpart H Standards 1910.125 Additional Requirements for Dipping and Coating Operations that use Flammable or Combustible Liquids 1910.126 Additional Requirements for Special Dipping and Coating Operations

Definitions Hazardous Chemical Occupational Safety & Health Act (OSHA) term that denotes any chemical that would be a risk to employees if exposed in the work place

Definition Highly Hazardous Chemical OSHA term that denotes any chemical that would posses toxic, reactive, flammable or explosive properties

Flammable and Combustible Liquids 1910.106

Definitions Aerosol Aerosol shall mean a material which is dispensed from its container as a mist, spray, or foam by a propellant under pressure

Definitions Approved Approved shall mean an approved or listed by a national recognized testing laboratory Such as: Underwriters Laboratories (UL) or Factory Mutual (FM)

Definitions Boiling Point Boiling point shall mean the boiling point of a liquid at a pressure of 14.7 pounds per square inch absolute (psia). The pressure is equivalent to 760 millimeters of mercury (760 mm Hg) Liquid changes into a vapor

Definitions Boiling Point At temperatures above the boiling, the pressure of the atmosphere can no longer hold the liquid in the liquid state and bubbles begin to form. The lower the boiling point, the greater the vapor pressure at normal ambient temperatures and consequently the greater the risk.

Definitions Container Container shall mean any can, barrel, or drum

Definitions Closed Container Closed container shall mean a container so sealed by means of a lid or other device that neither liquid or vapor will escape from it at ordinary temperatures

Definitions Fire Area Fire area shall mean an area of a building separated from the remainder of the building by construction having a fire resistance of at least 1 hour and having all communicating openings properly protected by an assembly having a fire resistance rating of at least one hour.

Definitions Flash Point Flash point means the minimum temperature at which a liquid gives off vapor within a test vessel in sufficient concentration to form an ignitable mixture with air near the surface of the liquid. The flash point is normally an indication of susceptibility to ignition.

Definitions Combustible Liquid Combustible liquid means any liquid having a flash point at above 100°F (37.8 °C). Combustible liquids are divided into two classes: Class II Class III

Definitions Class II Liquids Class II liquids shall include those with a flash point at or above 100°F (37.8°C) and below 140°F (60°C)

Definitions Class III Liquids Class III liquids shall include those with flash points at or above 140°F (60°C). Class III are divided into two classes: Class IIIA Class IIIB

Definitions Class IIIA Liquids Class III liquids shall include those with flash points at or above 140°F (60°C) and below 200°F (93.3°C)

Definitions Class IIIB Liquids Class IIIB liquids shall include those with a flash point at or above 200°F (93.3°C). This section does not regulate Class IIIB liquids.

Definitions NOTE: When a combustible liquid is heated to within 30°F (16.7°C) of its flash point, it shall be handled in accordance with the requirements for the next lower class of liquids

Definitions Flammable Liquid Flammable liquid means any liquid having a flash point below 100 °F (37.8 °C) Flammable liquids shall be known as Class I liquids

Definitions Class I liquids are divided into three classes: Class 1A Class 1B Class 1C

Definitions Class 1A Class 1A shall include liquids having flash points below 73 °F (22.8°C) and having a boiling point below 100 °F (37.8°C) Examples: Ethyl Ether, Isopropyl Chloride, Pentane

Definitions Class 1B Liquids Class 1B shall include liquids having flash points below 73°F (22.8°C) and having a boiling point at or above 100°F (37.8°C) Example: Acetone, Gasoline, Toluene

Definitions Class 1C Class 1C shall include liquids having flash points at at or above 73°F (22.8°C) and below 100°F (37.8°C) Examples: Amyl Alcohol, Naphtha, Xylene

Flash Point IIIA II IC IA IB Boiling Point 200°F Combustible Flammable Flash Point < 100°F 73°F IA IB 100°F Boiling Point

Definitions Portable Tank Portable tank shall mean a closed container having a liquid capacity over 60 U.S. gallons and not intended for fixed installation

Definitions Safety Can Safety can means an approved container, of not more than 5 gallons capacity, having a spring-closing lid and spout cover and so designed that it will safely relieve internal pressure when subject to fire exposure

Definitions Vapor Pressure Vapor Pressure is a measure of a liquid’s propensity to evaporate. The higher the vapor pressure, the more volatile the liquid and, thus, the more readily the liquid gives off vapors

Flammable (Explosive) Limits Flammable Range The range of a combustible vapor or gas-air mixture between the upper and lower flammable limits. Also, known as the “explosive range.”

Flammable (Explosive) Limits Lower Flammable Limit The lowest concentration at which a combustible gas forms a flammable mixture. Below the LFL there is too little combustible fuel to sustain a flame. Also, known as “Lower Explosive Limit or LEL.”

Flammable (Explosive) Limits Upper Flammable Limit The highest concentration at which a combustible gas forms a flammable mixture. Above the UFL there is too little oxygen to sustain a flame. Better known as “too rich” to burn. Also, known as “Upper Explosive Limit or UEL.”

Flammable (Explosive) Limits Hazardous Material LFL UFL Butane 1.9 8.5 Ethylene Oxide 3.0 100.0 Gasoline 1.4 7.6 Hydrogen 4.0 75.0 Isopropyl Alcohol 2.0 12.7 Propane 2.1 9.5

Flammable and Combustible Liquids This presentation is designed to assist trainers conducting OSHA 10-hour General Industry outreach training for workers. Since workers are the target audience, this presentation emphasizes hazard identification, avoidance, and control – not standards. No attempt has been made to treat the topic exhaustively. It is essential that trainers tailor their presentations to the needs and understanding of their audience. This presentation is not a substitute for any of the provisions of the Occupational Safety and Health Act of 1970 or for any standards issued by the U.S. Department of Labor. Mention of trade names, commercial products, or organizations does not imply endorsement by the U.S. Department of Labor.

Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and storage of flammable liquids requires the use of approved equipment and practices per OSHA standards 29 CFR 1910.106

Classes of Some Flammable Liquids Common Name Flash Point (oF) CLASS IA CLASS IB CLASS IC Ethyl Ether -49 Gasoline -45 Methyl Ethyl Ketone 21 Toluene 40 Xylene 81-115 Turpentine 95 Other common flammable and combustible liquids and their flash points are shown below: Flash Point (oF) CLASS IA Pentane < -40 CLASS IB Acetone 0 VM&P Naptha 20-45 (Typical) Ethyl Alcohol 55 CLASS IC Mineral Spirits 85-110 CLASS II Fuel Oils 100-130 Kerosene 110-150 CLASS III Ethylene Glycol 232

Program Components Control of ignition sources Proper storage A good plan for safe use of flammable and combustible liquids contains at least these components: Control of ignition sources Proper storage Fire control Safe handling

Sources of Ignition Open flames Smoking Static electricity Must take adequate precautions to prevent ignition of flammable vapors. Some sources of ignition include: Open flames Smoking Static electricity Cutting and welding Hot surfaces Electrical and mechanical sparks Lightning 1910.106(e)(6)(i)

Static Electricity Generated when a fluid flows through a pipe or from an opening into a tank Main hazards are fire and explosion from sparks containing enough energy to ignite flammable vapors Bonding or grounding of flammable liquid containers is necessary to prevent static electricity from causing a spark Static electricity can be generated by the contact and separation of dissimilar materials. For example: belts and pulleys, tires and the road, fluid flow through a pipe, agitation and mixing of fluids, and splash filling of flammable liquids. For more information, see NFPA 77, Static Electricity. One of the primary means of reducing the hazard of static electricity when transferring flammable liquids into/from containers is through the use of bonding and grounding, which is discussed in this program.

Industrial Plants – Grounding Class I liquids shall not be dispensed into containers unless the nozzle and container are electrically interconnected

Bonding Physically connect two conductive objects together with a bond wire to eliminate a difference in static charge potential between them Must provide a bond wire between containers during flammable liquid filling operations, unless a metallic path between them is otherwise present 1910.106(e)(6)(ii) Both objects bonded share the same charge and have no potential difference, BUT there still is a potential difference between the conductive objects and ground. Thus, there is danger of a spark from one of the conductive objects to grounded objects.

Grounding Eliminates a difference in static charge potential between conductive objects and ground Although bonding will eliminate a difference in potential between objects, it will not eliminate a difference in potential between these objects and earth unless one of the objects is connected to earth with a ground wire 1910.106(e)(6)(i) Both objects bonded and grounded permit charge to flow to ground.

Ventilation Always provide adequate ventilation to reduce the potential for ignition of flammable vapors. 1910.106(a)(31) Ventilation for the prevention of fire and explosion is considered adequate if it is sufficient to prevent accumulation of significant quantities of vapor-air mixtures in concentration over one-fourth of the lower flammable limit. For additional information on ventilation, see OSHA’s web site at: http://www.osha-slc.gov/SLTC/ventilation/index.html

Storage Fundamentals Identify incompatible chemicals – check the Material Safety Data Sheet Isolate and separate incompatible materials Isolate by storing in another area or room Degree of isolation depends on quantities, chemical properties and packaging Separate by storing in same area or room, but apart from each other

Storage of Flammable and Combustible Liquids Storage must not limit the use of exits, stairways, or areas normally used for the safe egress of people In office occupancies: Storage prohibited except that which is required for maintenance and operation of equipment Storage must be in: closed metal containers inside a storage cabinet, or safety cans, or an inside storage room Inside storage room 1910.106(d)(5)(i) and (iii) In office occupancies, the inside storage room must not have a door that opens into that portion of the building used by the public.

Safety Cans for Storage and Transfer Approved container of not more than 5 gallons capacity Spring-closing lid and spout cover Safely relieves internal pressure when exposed to fire 1910.106(a)(29)

Flame Arrester Screen Prevents fire flashback into can contents Double wire-mesh construction Large surface area provides rapid dissipation of heat from fire so that vapor temperature inside can remains below ignition point

Storage Cabinets Not more than 60 gal of Class I and/or Class II liquids, or not more than 120 gal of Class III liquids permitted in a cabinet Must be conspicuously labeled, “Flammable - Keep Fire Away” Doors on metal cabinets must have a three-point lock (top, side, and bottom), and the door sill must be raised at least 2 inches above the bottom of the cabinet 1910.106(d)(3)(i) and (ii) and (ii)(a) Three-point lock on metal cabinet doors prevents buckling, which would expose contents to fire. Raised door sill contains leaks.

Fire Control Suitable fire control devices, such as small hose or portable fire extinguishers must be available where flammable or combustible liquids are stored Open flames and smoking must not be permitted in these storage areas Materials which react with water must not be stored in the same room with flammable or combustible liquids 1910.106(d)(7)(i) and (iii) and (iv)

Transferring Flammable Liquids Since there is a sizeable risk whenever flammable liquids are handled, OSHA allows only four methods for transferring these materials: Through a closed piping system From safety cans By gravity through an approved self-closing safety faucet By means of a safety pump 1910.106(e)(2)(iv)(d) Transferring of flammable liquids by means of air pressure on the container or portable tanks is prohibited.

Self-Closing Safety Faucet Bonding wire between drum and container Grounding wire between drum and ground Safety vent in drum

Safety Pump Faster and safer than using a faucet Spills less likely No separate safety vents in drum required Installed directly in drum bung opening Some pump hoses have integral bonding wires

Waste and Residue Combustible waste and residue must be kept to a minimum, stored in covered metal receptacles and disposed of daily. 1910.106(e)(9)(iii) Waste drum with disposal funnel Safety disposal can Oily-waste can (self-closing lid)

Container and Portable Tank Storage This section applies only to the storage of flammable and combustible liquids in drums or other containers not exceeding 60 gallons individual capacity and portable tanks of less than 660 gallons individual capacity.

Container and Portable Tank Storage Only approved containers and portable tanks may be used to store flammable and combustible liquids Metal containers and portable tanks must meet DOT requirements

Design, Construction and Capacity of Storage Cabinets Not more than 60 gallons of Class I and/ or Class II liquids, or not more than 120 gallons of Class III liquids may be stored in an individual cabinet

Design, Construction and Capacity of Storage Cabinets The standard permits both metal and wooden storage cabinets Cabinets shall be designed and constructed to limit internal temperatures to not more than 325°F when subject to a standardized 10-minute fire test

Design, Construction and Capacity of Storage Cabinets The bottom, top, door, and sides of metal cabinets shall be at least 18 gauge sheet metal and double walled with a 1 ½ -inch air space The door shall be provided with a three point lock and the door sill shall be raised at least 2-inches above the bottom of the cabinet

Design and Construction of Inside Storage Rooms Construction is to comply with test specifications outlined in NFPA 251 Openings to other rooms or buildings shall be provided with non-combustible liquid-tight raised sills or ramps at least 4-inches in height, or the floor in the storage area shall be at least 4-inches below the surrounding floor

Design and Construction of Inside Storage Rooms Opening shall be provided with approved self-closing fire doors The room shall be liquid tight where the floor joins the floor Electrical wiring for Class I liquids will comply with Class I, Division 2 hazardous locations

Design and Construction of Inside Storage Rooms In each storage room, an aisle of at least 3 feet in width will be maintained Containers over 30 gallons capacity shall not be stacked Containers will be at least 3 feet from sprinkler heads

Fire Control At least one portable fire extinguisher having a rating of not less than 12-B units shall be located outside of, but not more than 10 feet from, the door opening into any room used for storage.

Maximum Quantities The quantity of liquid that may be located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building shall not exceed: 25 gallons of Class IA liquids in containers 120 gallons of Class IB, IC, II, or III liquids in containers 660 gallons of Class IB, IC, II, or III liquids in a single portable tank.

Service Stations No smoking or open flames in areas used for fueling, servicing fuel, etc. Conspicuous signs must be posted.

Liquid Transfer If gravity transfer is used, must be through an approved self-closing valve. Transferring by means of air pressure on the container or portable tanks shall be prohibited.

Handling Liquids Flammable liquids shall be kept in covered containers when not actually in use.

Housekeeping Combustible waste and residue shall be kept to a minimum, stored in covered metal receptacles, and disposed of daily

Safe Handling Fundamentals Carefully read the manufacturer’s label on the flammable liquid container before storing or using it Practice good housekeeping in flammable liquid storage areas Clean up spills immediately, then place the cleanup rags in a covered metal container Only use approved metal safety containers or original manufacturer’s container to store flammable liquids Keep the containers closed when not in use and store away from exits or passageways Use flammable liquids only where there is plenty of ventilation Keep flammable liquids away from ignition sources such as open flames, sparks, smoking, cutting, welding, etc. Spills or Leaks First, eliminate all sources of ignition, then Stop the leak, if possible Contain the material Isolate the area Avoid direct contact with the material Use appropriate fire control procedures

Summary The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and storage of flammable liquids requires the use of approved equipment and practices per OSHA standards An excellent reference on this topic is National Fire Protection Association Standard No. 30, Flammable and Combustible Liquids Code

Spray Finishing 1910.107

Definitions Aerated Solid Powders Aerated powders shall mean any powdered material used as a coating material which shall be fluidized within a container by passing air uniformly from below. It is common practice to fluidize such materials to form a fluidized powder bed and then dip the part to be coated into the bed in a manner similar to that used in liquid dipping. Such beds are also used as sources for powder spray operation

Definitions Spraying Area Any area in which dangerous quantities of flammable vapors or mists, or combustible residues, dusts, or deposits are present due to the operation of spraying processes.

Definitions Spray Booth A power-ventilated structure provided to enclose or accommodate a spraying operation to confine and limit the escape of spray, vapor, and residue, and to safely conduct or direct them to an exhaust system

Definitions Waterwash spray booth A spray booth equipped with a water washing system designed to minimize dusts or residues entering exhaust ducts and to permit the recovery of overspray finishing material

Definitions Dry spray booth A spray booth not equipped with a water washing system as described in subparagraph (4) of this paragraph.

Definitions Dry spray booth A dry spray booth may be equipped with distribution or baffle plates to promote an even flow of air through the booth or cause the deposit of overspray before it enters the exhaust duct; or overspray dry filters to minimize dusts or residues entering exhaust ducts; or where dry powders are being sprayed, with powder collection systems so arranged in the exhaust to capture oversprayed material.

Separation of Operations Each spray booth shall be separated from other operations by: not less than 3 feet or by a partition or wall to reduce danger 3 ft 8 feet 3 feet

Sources of Ignition There will be no open flame or spark producing equipment in any spray area nor within 20 feet Space heating appliances, steam pipes, or hot surfaces shall not be located in the spray area

Electrical Class I or Class II, Division 1 Locations The interior of spray booths or rooms The interior of exhaust ducts Any area in the direct path of spray operations

Electrical Class I or Class II, Division 2 Locations For open spraying, all space outside of but within 20 feet horizontally and 10 feet vertically Spray Area 20’

Closed Top/Open Face Booth

Enclosed Spray Booth or Room

Open Spraying Locations

Process Safety Management of Highly Hazardous Chemicals CFR 1910.119

1910.119(a) Purpose This section contains requirements for preventing or minimizing the consequences of catastrophic releases of: Toxic, Reactive, Flammable, or Explosive chemicals These releases may result in toxic, fire or explosion hazards

1910.119(a)(1)Application A process which involves a chemical at or above the specified threshold quantities listed in Appendix A A process which involves a flammable liquid or gas (as defined in 1910.1200(c) of this part) on site in one location, in a quantity of 10,000 pounds (4535.9 kg) or more

Review What is a flammable liquid? What is a combustible liquid? A Class 1A flammable liquid has a flash point of less than?

Review What is the maximum amount of a 1A liquid that can be stored outside of a flammable storage cabinet or room? A 12B fire extinguisher must be located within _______ feet of flammable liquid storage room.

Review Spray finishing can be a hazardous activity. True or False Each spray booth must be separated by ___ feet or a wall or partition from other operations. Spray booths require ___________ electrical installations.