Breaker Failure Protection PSRC – K2 WG. Last Publication on Breaker Failure Protection by PSRC An IEEE PSRC Report, Summary Update of Practices on Breaker.

Slides:



Advertisements
Similar presentations
CONDITIONS FOR SUCCESSFUL INTERRUPTION:
Advertisements


Announcements Be reading Chapters 9 and 10 HW 8 is due now.
New Energy Horizons Opportunities and Challenges Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25,
Submitted by: Name:Rajendra Kumar Choudhury Branch:Electrical Engg.
Transmission Operator Protection System Misoperations 2014 ERCOT Transmission Protections System Misoperations Data – 138kV and 345kV Combined (Not including.
MOLDED CASE CIRCUIT BREAKER BASICS
SYMMETRICAL COMPONENETS OF POWER SYSTEM
NERC Lessons Learned Summary December NERC lessons learned published in December 2014 Three NERC lessons learned (LL) were published in December.
Protection and Relay Schemes. Agenda  Introduction of Protective Relays  Electrical System Protection with Protective Relays  Conclusion.
GENERATOR PROTECTION.
Generator Management Relay
Protective Relaying Refresher
Selective Stator Ground Protection Expo Presentation.
Generator Protection. Amount of Protection Rated power of the generator Ratio of its capacity to the total capacity of the system Configuration of the.
1 PCA2 On-load Protection Condition Analyser. 2 PCA2 online testing concept Concept introduction: PCA2 is a new system test approach intended to save.
Chapter 7 SYSTEM PROTECTION
UMKC Senior SUBSTATION DESIGN TEAM
Interconnect Protection of Dispersed Generators
THE ELECTRIC SUB STATION
Lesson 9: Electrical Components
Scheduled Versus Event Driven Testing of Distribution Protection IEDs Dr. Alexander Apostolov, Benton Vandiver, Will Knapek, OMICRON electronics.
Applying the Distribution System in Grid Restoration/NERC CIP-014 Risk Assessment Srijib Mukherjee, Ph.D., P.E. UC Synergetic.
Adaptive Protection of Distribution Feeders Alexander Apostolov, Benton Vandiver.
PSRC Line Protection Subcommittee Working Group D4
SWER New Zealand & Australian Experience
Sommerville Power Engineering Ltd. System Studies Capabilities Company Number , registered in England & Wales. SPE.
Copyright © SEL 2008 Updated Transmission Line Protection Communications Roy Moxley, Ken Fodero, and Héctor J. Altuve Schweitzer Engineering Laboratories,
Electrical Distribution Training
CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION.
Summary Rich Bauer, Senior Reliability Engineer Event Analysis Subcommittee – LL Update March 04, 2014.
EE 445 Course Presentation Power System Protection
Protection of Microgrids Using Differential Relays
Lecture 22 Unbalanced Faults and Power System Protection Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Protection & Switchgear
Lecture 22 Unbalanced Faults and Power System Protection Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS.
Announcements Read Chapters 10 and 11
1 Distributed Generation and Power Quality-Continued.
Cheng-Ting Hsu Presenter: Cheng-Ting Hsu Cogeneration System Design for a High-Tech Science-Based Industrial Park Department of Electrical Engineering.
1 Institute of Electrical and Electronics Engineers Revised January 4, 2011.
NERC Lessons Learned Summary LLs Published in September 2015.
A common 400 Hz AC Power Supply Distribution System for CMS FEE. Authors C. Rivetta– Fermilab. F. Arteche, F. Szoncso, - CERN.
Jeffy Mathew ECEN 679 Spring  Adaptive Relaying permits and seeks to make adjustments automatically in various protections in order to make them.
ABOC/ATC days Electrical Network: Selectivity and Protection Plan José Carlos GASCON TS–EL Group 22 January 2007.
Sub-Synchronous Frequency Detection Using SEL OGIC ® Control Equations SSF Relay ERCOT Workshop NPRR562 Subsynchronous Resonance Larry Gross.
VACUUM CIRCUIT BREAKER. WHAT IS A CIRCUIT BREAKER A circuit breaker is an equipment that breaks a circuit either manually or automatically under all conditions.
Presentation Topic: Circuit Breakers Represented to: Dr. M. Riaz Khan Represented by: M. Mujahid.
Protection of Power Systems
Protection of Power Systems
April 7, 2015 Washington, D.C. Area Low-Voltage Event Operations Training Seminar 2016 Erik Johnson System Operations Training (ERCOT)
SYNERGY INSTITUTE OF ENGINEERING AND TECHNOLOGY
Equipment 1.Circuit Breaker. 3.Fuses. 4.Protecti- ve relay.2.Bus bar. TYPES OF SWITCH GEAR EQUIPMENT:-
 The figure below shows a protection system for a transmission line, consisting of a CT, PT, a relay and its associated circuit breaker.
Power System Protective Relaying-Part One
STUDY OF ELEMENTS OF A 220/132/33KV SUBSTATION
Protection and Relay Schemes
Automatic Transfer Switches
Announcements Please read Chapters 9, 10 and 11 HW 8 quiz today
Protection of Power Systems
NERC Published Lessons Learned Summary
NERC Published Lessons Learned Summary
FEEDER PROTECTION UNIT
Chapter 7 System Protection
High Voltage Power Circuit Breakers
IEEE Guide for Protective Relay Applications to Transmission Lines
Protective Relaying Conference
Background Information on Hurricane Matthew Event No.1 Event No.2
Summary of Revision C IEEE C Guide for Breaker Failure Protection of Power Circuit Breakers. Good morning. I have the privilege.
Agenda Introduction of Protective Relays
Interconnection of AES With The Grid
Presentation transcript:

Breaker Failure Protection PSRC – K2 WG

Last Publication on Breaker Failure Protection by PSRC An IEEE PSRC Report, Summary Update of Practices on Breaker Failure Protection, IEEE Transaction Power Apparatus and Systems, Vol. PAS-101, No. 3, pp , March 1982

Why a Guide ? Things have changed in 20 years. New Engineers need guidance. Breaker Failure Function being incorporated in multifunction relays.

PSRC – K2 Established Working Group members

K2 Members Roger Hedding, Chair S.Anderson Alex Apostlov John Appleyard Roy Ball George Bartok Ron Beazer Ken Behrendt Robert Beresh Martin Best Gustav Brunello Art Buanno Zeeky Bukhala Arvind Chaudhary, Vice Chair Simon Chano Terry Crawley Randy Crellin Randy Cunico Albert N. Darlington Paul Drum Walt Elmore David Emigh Jon Ferraro Kelly Gardner Tony Giuliante George Gresko

K2 Members Irwin Hassenwinkle Stan Horowitz Randy Horton Mohamed Ibrahim Bob Jackson Gerald Johnson Peter Kemp Tim Kern Shoukat Khan Mike Kloiber Gary Kobet Tom Lanigan Larry Lawhead Bill Lowe Vahid Madani Walter McCannon Mike McDonald Dean Miller Pratap Mysore Mukesh Nagpal George Nail Russell Patterson Frank Plumptre Elmo Price Dan Reckerd Don Sevcik Charles Sufana Joe Uchiyama Sahib Usman Don Ware James Whatley Roger Whittaker Skip Williams Ray Young Rich Young

Assignment This working group will investigate issues pertaining to breaker failure protection which will include : breaker failure mechanisms, fault detectors, breaker failure circuits, effect of bus configurations, effect of multifunction microprocessor relays, and the effect of modern breaker control schemes. Prepare a guide covering the application of breaker failure protection to power circuit breakers.

Why Breaker Failure Protection ?

Basic Breaker Failure Scheme

Timing Chart

Two Components Current Detector Breaker Failure Timer

Current Detector Detects current flow Pick up for minimum fault If phase current set above load current If ground current set above unbalance Drop out not delayed by dc offset Use 52a only if no current

Timer Longer than it takes the breaker to clear a fault Shorter than the Critical Clearing Time plus some margin. Could be longer for Line to Ground Faults than for Three Phase Faults

Critical clearing Time Dictated by Transient Stability limit Somewhere between 7 and 30 cycles Results from Stability Study

Total Clearing Time The sum of : BFI pick up + Breaker Failure Timer + Auxiliary trip relay time + Local back up breaker time + (Transfer trip time if remote)

Transient Stability time Severity of Fault Loading on System Mass of Generators Type of Fault

Circuit Breaker Failure Modes Failure to Trip Failure to Clear

Failure to Trip Contacts do not open after trip circuit energized. Short or open in Trip coil Mechanical problem with breaker

Failure to Clear Contacts open but fault not extinguished. Current continues to flow Mechanical or Dielectric problem Why auxiliary switches not reliable

Breaker Failure ReTrip

Elimination of 50BF Reset Time

Addition of Control Timer

Breaker Failure Seal-In

Minimum Fault Current Use where current magnitude may not be enough to pick up current detector Transformers Generators Harmonic Filters

Minimum Fault Current

Ring Bus Application

Ring Bus Separate Ct inputs into relay Careful of current distribution after one breaker opens in setting current detectors. Another Working group (K5) to look into this issue.

Distributed Breaker Failure

Design Considerations Total Breaker Failure clearing time should be less than system stability limit. Independent of type of failure detected Should operate during loss of dc to breaker

Conclusions BFP should operate only when desired Timer setting should allow adequate margin between backup breaker clearing and system critical clearing time. Multiple timers can be used for different types of faults Use auxiliary contacts as last resort for BFI.

Conclusions Phase current detectors should be set above load to protect from scheme operating during testing. Seal in circuits should be used to insure breaker failure scheme does not drop out prematurely Care should be taken when applying breaker failure to ring bus and breaker and one half.

Questions ?