Refrigeration and Air conditioning
Lesson Plan Vapour compression refrigeration cycle Components of a refrigeration system Pressure enthalpy chart superheating & sub-cooling Heat exchanger Coefficient of performance ( COP ) System Capacity Direct and Indirect Expansion System Back Pressure Regulating valve Types of compressor Oil Separator Filter/Drier Throttling device Capacity control Method
Basic refrigeration cycle: Heat energy flows from a hot region to a cooler region. Vapour Compression Refrigeration System uses a circulating refrigerant as a medium which 1) absorbs & removes heat from space to be cooled 2) rejects the heat elsewhere (cooler) Cold room cooler Cooling water Heat energy Refrigerant flow
Vapour Compression System Liquid receiver 4 numbers principle components : Evaporator Compressor Condenser Expansion Valve Heat out Liquid Condenser High Pressure Side Hot Gas Compressor Expansion valve Low Pressure Side Evaporator Gas Heat in
Vapour Compression System Liquid receiver EVAPORATOR: The evaporator coils are located in the compartment to be cooled. The low pressure liquid refrigerant ,after passing through the expansion valve, expands. Takes in heat from the surrounding and evaporates. The gas is then sucked up by the compressor. Heat out Liquid Condenser High Pressure Side Hot Gas Compressor Expansion valve Low Pressure Side Evaporator Gas Heat in
Vapour Compression System Liquid receiver COMPRESSOR : Compresses the refrigerant (gaseous state). Raising its Temperature & Pressure. Discharges refrigerant to Condenser. Heat out Liquid Condenser High Pressure Side Hot Gas Compressor Expansion valve Low Pressure Side Evaporator Gas Heat in
Vapour Compression System Liquid receiver LIQUEFACTION: Hot refrigerant gas cooled in the condenser. Condensed liquid refrigerant flows into a receiver. Then liquid refrigerant flows to the expansion valve. Heat out Liquid Condenser High Pressure Side Hot Gas Compressor Expansion valve Low Pressure Side Evaporator Gas Heat in
Vapour Compression System Liquid receiver EXPANSION: The expansion valve acting as a regulating valve, limits the amount of refrigerant flowing through. Resulting in reduction of pressure of the liquid and expansion takes place. Heat out Liquid Condenser High Pressure Side Hot Gas Compressor Expansion valve Low Pressure Side Evaporator Gas Heat in
P-H chart ( Pressure – Enthalpy chart ) Pressure – Absolute pressure Unit : bar , psi Enthalpy – Total amount of energy per unit weight of substance. Unit : BTU / Lb or kJ / kg The lines ,saturated liquid & vapour respectively are plots of pressure vs enthalpy for the saturated state of a given refrigerant. This chart is used to understand the property changes that takes place in each phase of the cycle. Saturated vapour line Saturated liquid line Sub-cooled region Sub cooled liquid Liquid – vapour mixture Superheated region
Refrigeration Cycle : Pressure-Enthalpy graph Enthalpy – Total amount of energy per unit weight of substance. Unit : BTU / Lb or kJ / kg Entropy – Measure of heat dispersion in a system divided by temperature. Unit : BTU / Lb / deg change or kJ / kg / deg change for a substance.
Ideal Refrigeration Cycle : Pressure-Enthalpy chart Liquid vapour mixture Sub cooled liquid Superheated vapour 4 3 Pressure (absolute) P2 P1 1 2 Enthalpy ( BTU / lbs or KJ / kg )
Refrigeration Cycle : Pressure-Enthalpy chart Non ideal Refrigeration Cycle : Pressure – Enthalpy chart , showing superheating & sub cooling Vapour to Liquid transformation in CONDENSER Superheated Liquid vapour mixture Sub cooled liquid Superheated vapour 4 subcooling 3 Pressure (absolute) Throttling at expansion valve Liquid vapour mixture Work done in the compressor 2 1 Liquid to Vapour Transformation in EVAPORATOR superheated Enthalpy ( BTU / lbs or KJ / kg )
Enthalpy ( BTU / lbs or KJ / kg ) Non ideal Refrigeration Cycle : Pressure – Enthalpy chart , showing superheating & sub cooling Vapour to Liquid transformation in CONDENSER Superheated vapour Sub cooled liquid 4 3 Throttling at expansion valve Pressure (absolute) Liquid vapour mixture Work done in the compressor 1 Liquid to Vapour Transformation in EVAPORATOR 2 H1 H2 H3 Enthalpy ( BTU / lbs or KJ / kg ) The amount of heat that the refrigerant absorb must equal the cooling load. (1) Refrigerant cooling load ( F ) = cooling load / ( H2 – H1) (2) Work done by compressor = F x ( H3 – H2 ) (3) Heat rejected by condenser = F x ( H3 – H1 ) (4) Heat absorbed by evaporator = F x ( H2 – H1 ) Coefficient of Performance (COP) = heat absorbed by refrigerant / Energy required driving compressor = ( H2 – H1) / ( H3 – H2)
Pressure-Enthalpy chart 1-2 : EVAPORATOR – extraction of heat from room 2-3 : COMPRESSOR – compression work 3-4 : CONDENSER – energy thrown to sea 4-1 : EXPANSION VALVE – throttling at the expansion valve For each kg of refrigerant flow , Energy extracted from meat room : 304 - 150 = 154 KJ / kg Work spent on compressor = 365 – 304 = 61 KJ / Kg Coefficient of Performance ( COP ) = Energy extracted from room / Energy spent = 154 / 61 or 2.52 Pressure ( bar ) Vapour to Liquid transformation in CONDENSER at 42 deg C 4 3 16 Throttling at expansion valve Work done in the compressor 3.2 Liquid to Vapour Transformation in EVAPORATOR at -13 deg C 2 1 150 304 365 Enthalpy ( KJ / kg of refrigerant )
Pressure – Enthalpy chart , of a practical cycle (refer to page 8) Effects of pressure loss resulting from friction.
Superheating & Sub-cooling evaporator refrigerant control (expansion valve) Saturated suction vapour Saturated liquid Heat exchanger Sub cooled liquid Superheated suction vapour receiver compressor Page 7 condenser Improvement in cycle efficiency with a heat exchanger – as compared to another cycle where vapour is superheated without producing any useful cooling
Refrigeration system capacity Rate at which system removes heat from. Rate depends : (1) mass of refrigerant circulated per unit time (2) refrigerating effect per unit mass circulated (undercooling increases the refrigerating effect)
Two systems employed: Direct Expansion System Indirect expansion system aka Brine System
Direct Expansion System : Provisional Refrigeration System Thermostat Purging line To FISH ROOM Condenser expansion valve Solenoid stop valve Drier receiver Cooling water in / out T1 Sight glass Oil separator Capillary tube Fan / blower Evaporator To VEGETABLE ROOM Oil return to compressor sump HP pressure switch Bulb HP pressure gauge T2 MEAT ROOM Oil pressure gauge Refrigerant compressor Oil pressure switch Temperature sensor LP pressure gauge Back pressure regulating valve From FISH ROOM LP pressure switch From VEGETABLE ROOM : Refrigerant flow
Indirect Expansion (Brine System) Thermostat Brine header tank Condenser / Receiver Solenoid stop valve expansion valve Drier pump Cooling water in / out T1 Sight glass Oil separator Capillary tube Evaporator Oil return to compressor sump Bulb HP pressure switch T2 Refrigerant compressor Oil pressure switch Temperature sensor Secondary refrigerant to various compartment LP pressure switch : Refrigerant flow
Back pressure regulating valve Normally fitted to higher temperature rooms, ie the vegetable room not for the fish room or meat room. Purpose : Act as system balancing diverters – a) When all solenoid valves are opened, the valve restrict liquid flowing into the vegetable room & therefore deliver the bulk to the colder rooms. b) Limits the pressure drops across the expansion valve by giving a set minimum pressure in the evaporator coil. Prevents cold air blowing directly onto delicate vegetables.
Refrigerant Compressor types: Reciprocating Rotary Centrifugal Screw
Oil Separator Page 12 Gas from compressor Gas to condenser Internal baffles Oil to compressor crankcase Oil Page 12 Float
Liquid-line Filter / Drier Course filter to remove large particles Drying agent : silica gel or activated alumina Desiccant (dehydrating material) Refrigerant in Clean,dry refrigerant Felt pad Fine filter to remove small particles Page 13
Condenser: Air cooled type – up to 5 hp Large capacity – shell & tube type , SW cool Tubes – aluminium brass (option ext. fins) Water velocity < 2.5 m/s minimise erosion Anodes – avoid corrosion non ferrous metals
Throttling device: Metering of refrigerant – rate suitable to maintain designed operating pressures at different load. Maintain pressure differential between HP & LP side. The pressure of the refrigerant is reduced as it passes through the small orifice of the throttling device. With the reduction in pressure, the corresponding boiling point of the liquid is reduced. Types of throttling devices: Hand expansion valves Automatic constant pressure expansion valve Thermostatic expansion valve Externally equalized expansion valve Pressure balancing expansion valve Expansion valves with centrifugal type distributors Flow control device for flooded evaporators
Expansion valve automatic expansion valve thermostatic expansion valve externally equalised thermostatic expansion valve
Automatic expansion valve Page 18
Thermostatic expansion valve (TEV) Page 19
External equalised thermostatic expansion valve Page 20
Capacity control methods To maintain constant temperature, a constant pressure must be present in the EVAPORATOR. Ideally, the compressor should remove from the EVAPORATOR exactly the volume of refrigerant that boils off in it. Change in loading : change in quantity of boiling off the refrigerant. Manual start/stop Speed variation Cylinder unloading reciprocating compressor Suction side throttling centrifugal compressor Inlet guide vane centrifugal compressor Hot gas bypass Compressor in parallel Slide valve Screw compressor - control effective working length of rotor.
Unloading device
Screw compressor NORMAL LOADING Page 12 DRIVE SHAFT INLET LOBES Max Min DISCHARGE PORT UNLOADING PISTON BYPASS GAS OUTLET CYLINDER SLIDE VALVE NORMAL LOADING Page 12
Screw compressor REDUCE LOADING DRIVE SHAFT INLET LOBES Max Min DISCHARGE PORT UNLOADING PISTON BYPASS GAS OUTLET CYLINDER SLIDE VALVE REDUCE LOADING