CHAPTER 6 Lightning, Protection & Insulation Coordination

Slides:



Advertisements
Similar presentations
OVERHEAD LINE INSULATORS
Advertisements

Lightning and Lightning Protection
LIGHTNING PHENOMENON 1. The height of the cloud base above the surrounding ground level may vary from 160 to 9,500 m. The charged centres which are responsible.
Protection against Lightning Overvoltages Overvoltages due to lightning strokes can be avoided or minimized in practice by (d) shielding the overhead lines.
Chapter 17 Current and Resistance. Electric Current Let us look at the charges flowing perpendicularly to a surface of area A The electric current is.
I. INTRODUCTION A. Types of lightning II. LIGHTNING DENSITY MAPS A. Ground Flash density.For example (world, us etc) III. LIGHTNING PROTECTION A. Classification.
The Physics of Lightning
Prof. D. Wilton ECE Dept. Notes 19 ECE 2317 Applied Electricity and Magnetism Notes prepared by the EM group, University of Houston.
Calculating Separation Distance and Surge Current
Chapter 24 Electric Current. The electric current I is the rate of flow of charge through some region of space The SI unit of current is Ampere (A): 1.
KINEMATICS OF PARTICLES PLANE CURVILINEAR MOTION
Lightning “Thunder is good, thunder is impressive; but it is lightning that does the work.” Mark Twain--
Lightning Lightning is a discharge of electrical energy. May occur: –Between cells in the same storm (Inter-cloud Lightning) –Within a cloud.
Chapter 15 Electric Forces and Electric Fields Conceptual Quiz Questions.
Rain and Lightning September 26, Frequency of Lightning Factors effecting where lightning will strike: –Size of cumulonimbus cloud base –Height.
FEEE Ensuring Enhanced Education 1 D O : Point of lightning stroke S 0 : Rate of rise at O, kV/µs I 0 : Lightning stroke current, kA X :Distance in which.
Chapter 27 Current and Resistance. Electric Current The electric current I is the rate of flow of charge through some region of space The SI unit of current.
Current and Resistance FCI.  Define the current.  Understand the microscopic description of current.  Discuss the rat at which the power.
Chapter 25 Capacitance.
Fall 2004 Dielectric breakdown ECE 2317: Applied Electricity and Magnetism Prof. Jeffery T. Williams Dept. of Electrical & Computer Engineering University.
Chapter # 8 Mechanical Design of Overhead Lines.
Presented by: Nguyen Phan Thanh Southern Taiwan University of Science and Technology.
Weather Patterns. Weather Changes Because of the movement of air and moisture in the atmosphere weather constantly changes.
Electric Potential 2 q A C B r A B r path independence a a Rr VQ 4   r Q 4   R.
SMJE 2103 Overvoltage, Electrical Insulation and Protection Devices.
Chapter 22 Electric Fields The Electric Field: The Electric Field is a vector field. The electric field, E, consists of a distribution of vectors,
1 Transmission of Electrical Energy Electrical energy is carries by conductors such as overhead transmission lines and underground cables. The conductors.
LIGHTENING PROTECTION USING LFA-M
EE 2353 HIGH VOLTAGE ENGINEERING Faculty Name :A.JAIBUNISHA Faculty Code : EE 58 Designation : LECTURER Department : EEE.
EE 2353 HIGH VOLTAGE ENGINEERING
Alexandre Piantini University of São Paulo Lightning Transients in Medium- Voltage Power Distribution Lines V Russian Conference on.
SYNERGY INSTITUTE OF ENGINEERING AND TECHNOLOGY
Equipotential Surfaces A useful way to visualize electric fields is through plots of equipotential surfaces 2-D surfaces where the electric potential is.
Electrical Power II Unit 4-Overvoltages Unit 5-HVDC Unit 6-FACTS.
STUDY OF ELEMENTS OF A 220/132/33KV SUBSTATION
The Course of Synoptic Meteorology
Electric Charge and Static Electricity
High Voltage Engineering
A SEMINAR ON LIGHTNING ARRESTER
Polyimide sheet (5 mils)) AZ-93 Thermal Paint (5 mils))
High Voltage Engineering
Capacitance & Dielectrics
High Voltage Engineering
Bell Ringer Cumulonimbus clouds have a tall structure and a flat base. What are they usually associated with?
Chapter 24 Electric Current.
HIGH VOLTAGE ENGINEERING (HVE)
WELCOME TO ALL.
Chapter 22 Electric Fields.
OVER VOLTAGE The voltage waves having magnitude more than its normal value. In other words, sudden rise to an excessive or abnormal value It remains for.
Advanced Power Systems
OBJECTIVES After studying Chapter 4, the reader should be able to:
FAULT ANALYSIS - BALANCED FAULT
Lightning Interactions b/w hail and smaller ice crystals transfer e- to hail. They are heavier and sink to base of cloud. Ice Crystals Light due to e-’s.
EET 323 – Electrical System Design Lecture 9: Grounding
NATS 101 Lecture 28 Lightning
External Lightning Protection System
LIGHTNING AND INSULATIONS COORDINATION
Question for the day Can the magnitude of the electric charge be calculated from the strength of the electric field it creates?
NATS 101 Lecture 28 Lightning
Protection against over voltages
Chapter 22 Electric Fields
Chapter 6 Dielectrics and Capacitance Capacitance Now let us consider two conductors embedded in a homogenous dielectric. Conductor M2 carries a total.
NATS 101 Lecture 20 Lightning
NOTICE The authors who don’t receive oral notifications before March 20th are required to present the paper using poster. The size of display board is.
Chapter 31 Faraday’s Law 31.1 Faraday’s Law of Induction
NOTICE The size of display board is 1m (width)×2.40m(height). A size 0.95m (width)×1.40m(height) of your poster is recommend. In the poster, please edit.
Circuit Components.
Chapter 22 Electric Fields
C H A P T E R 5 Capacitance. C H A P T E R 5 Capacitance.
HIGH VOLTAGE ENGINEERING Presented By P.Sindhu Asst.Prof EEE Dept
Presentation transcript:

CHAPTER 6 Lightning, Protection & Insulation Coordination LIGHTNING PHENOMENA STROKE FORMATION LIGHTNING PARAMETER EMPIRICAL DESIGN METHODS ELECTROGEOMETRIC MODEL (EGM) INSULATION LEVEL

Lightning Phenomena Lightning require the formation of certain type of clouds to be presence in their generation. This type of clouds is known as cumulonimbus clouds more specifically is the lightning generating type.

Lightning Phenomena Based on Ice Splinter Theory, moistures in the atmosphere combining with precipitating particles which are suspended in air are force higher up into the altitude by updraft. Every km going higher up in altitude there is decreased about 0.4oC. So the moistures experienced super cooling and formed crystalline ice with double layered ice structures. During the process of super cooling, H2O undergo ionization break up into anions (H+) and cations (OH-). The existences of temperature gradient in the super cooling moisture structure allowing the migration of H+ ions and OH- ions. However due to lighter weight of H+ ions they become more mobile allowing them to move towards the outer shell, leaving the heavier ions OH- in the inner shell of the ice structures

Lightning Phenomena Figure (a) show the physical relationship of moisture, precipitating particle with the updraft pushing the matters mentioned high in the latitude

Lightning Phenomena Figure (b) show the formation of ice crystal with two-layered structure of positively charged externally and negative charged internally

Lightning Phenomena Figure (c) : Splintering process of the ice crystal to form minute splinters pushing the positive charged splinters higher up in the altitude

Lightning Phenomena Figure d shows the lower part of a thundercloud is usually negatively charged. The upper portion area is usually positively charged. Lightning from the negatively charged area of the cloud generally carries a negative charge to Earth and is called a negative flash. A discharge from a positively-charged area to Earth produces a positive flash

Stroke Formation There are a number of different types of lightning strokes. These include strokes within clouds, strokes between separate clouds, strokes to tall structures, and strokes that terminate on the ground. The positive and negative strokes terminating on the ground are the types of most interest in designing shielding systems.

Stroke Formation Stepped Leaders The actual stroke development occurs in a two-step process. The first step is ionization of the air surrounding the charge center and the development of stepped leaders which propagate charge from the cloud into the air. Current magnitudes associated with stepped leaders are small (in the order of 100 A) in comparison with the final stroke current. The stepped leaders progress in a random direction in discrete steps from 10 to 80 m in length.

Stroke Formation

Stroke Formation Return Stroke The second step in the development of a lightning stroke is the return stroke. The return stroke is the extremely bright streamer that propagates upward from the earth to the cloud following the same path as the main channel of the downward stepped leader. This return stroke is the actual flow of stroke current that has a median value of about 24 000 A . The velocity of the return stroke propagation is about 10% the speed of light.

Stroke Formation

Lightning Parameters Strike distance Stroke current magnitude Keraunic Level Ground Flash Density

Correlations between Return stroke current magnitude and strike distance Return stroke current magnitude and strike distance (length of the last stepped leader) are interrelated. A number of equations have been proposed for determining the striking distance. S is the strike distance to ground in (m) I is the return stroke current in (kA) The equation stroke current,

Keraunic Level Keraunic level is defined as the average number of thunderstorm days or hours for a given locality. A daily keraunic level is called a thunderstorm-day and is the average number of days per year on which thunder will be heard during a 24 hours period. The average annual keraunic level for locations can be determined by referring to keraunic maps.

Annual frequency of thunderstorm days in the world

Ground Flash Density Ground flash density (GFD) is defined as the average number of strokes per unit area per unit time at a particular location. It is usually assumed that the GFD to earth, a substation, or a transmission or distribution line is roughly proportional to the keraunic level at the locality.

Ground Flash Density If thunderstorm days are to be used as a basis, it is suggested that the following equation be used:- Where Nk is the number of flashes to earth per square kilometer per year Nm is the number of flashes to earth per square mile per year Td is the average annual keraunic level, thunderstorm days

The mapping of the lightning ground flash density of Peninsula Malaysia(courtesy of TNBR)

EMPIRICAL DESIGN METHODS Two classical design methods have historically been employed to protect substations form direct lightning strokes:- Fixed angles Empirical curves The two methods have generally provided acceptable protection

Fixed Angles The fixed-angle design method uses vertical angles to determine:- the number position height of shielding wires or masts The angles used are determined by:- the degree of lightning exposure the importance of the substation being protected the physical area occupied by the substation The value of the angle alpha that is commonly used is 45°. Both 30° and 45° are widely used for angle beta.

Fixed angles for shielding wires

Fixed Angles Fixed angles for mast

Empirical curves From field studies of lightning and laboratory model tests, empirical curves have been developed to determine number, position, and height of shielding wires and masts (Wagner et al., 1941; Wagner, 1942; Wagner, McCann, Beck, 1941). The curves were developed for shielding failure rates of 0.1, 1.0, 5.0, 10, and 15%. A failure rate of 0.1% is commonly used in design. The empirical curve method has also been referred to as the Wagner method.

Figure (a) Figure (b) Figure (a) Single lightning mast protecting single ring of object — 0.1% exposure. Height of mast above protected object, y, as a function of horizontal separation, x , and height of protected object, d . Figure (b) Two lightning masts protecting single object, no overlap — 0.1% exposure. Height of mast above protected object, y , as a function of horizontal separation, s , and height of protected object, d.

Empirical curves Areas Protected by Lightning Masts If two masts are used to protect an area, the data derived from the empirical curves give shielding information only for the point B, midway between the two masts, and for points on the semicircles drawn about the masts, with radius x, as shown in Figure a. The locus drawn by the semicircles around the masts, with radius x, and connecting the point B, represents an approximate limit for a selected exposure rate. Any single point falling within the crosshatched area should have <0.1% exposure. Points outside the cross-hatched area will have >0.1% exposure. Figure b illustrates this phenomenon for four masts spaced at the distance s as in Figure a.

Figure a Figure b Areas protected by multiple masts for point exposures shown in Figure a with two lightning masts, Figure b with four lightning masts.

Empirical curves The protected area can be improved by moving the masts closer together, as illustrated in figure below. The protected areas are, at least, as good as the combined areas obtained by superimposing those of the previous figure . The distance s′ is one half the distance s in the previous figure. The size of the areas with an exposure greater than 0.1% has been significantly reduced.

Figure a Figure b Areas protected by multiple masts for point exposures shown in Figure a with two lightning masts, Figure b with four lightning masts with the distance s′ is one half the distance s in the previous figure.

ELECTROGEOMETRIC MODEL (EGM) Shielding systems developed using fixed angles and empirical curves of determining the necessary shielding for direct stroke protection of substations have historically provided a fair degree of protection. However, as voltage levels (and therefore structure and conductor heights) have increased over the years, the classical methods of shielding design have proven less adequate. This led to the development of the electrogeometric model.

ELECTROGEOMETRIC MODEL(EGM) Striking Distances To A Mast/Shield Wire Where Sm is the strike distance in meters Sf is the strike distance in feet I is the return stroke current in kiloamperes K is a coefficient to account for different striking distances to a mast, a shield wire, or the ground plane

ELECTROGEOMETRIC MODEL(EGM) Mousa (1988) gives a value of k = 1 for strokes to wires or the ground plane and a value of k = 1.2 for strokes to a lightning mast. The EGM theory shows that the protective area of a shield wire or mast depends on the amplitude of the stroke current.

ELECTROGEOMETRIC MODEL(EGM) Allowable Stroke Current Bus insulators are usually selected to withstand a basic lightning impulse level (BIL). Insulators may also be chosen according to other electrical characteristics, including negative polarity impulse critical flashover (CFO) voltage. Flashover occurs if the voltage produced by lightning stroke current flowing through the surge impedance of the station bus exceeds the withstand value.

ELECTROGEOMETRIC MODEL(EGM) Where IS is the allowable stroke current (kA) BIL is the Basic lightning Impulse Level (kV) CFO is critical flashover voltage of the insulation being considered (kV) ZS is the surge impedance of the conductor through which the surge is phasing (ohm) 1.1 is the factor to account for the reduction of stroke current terminating on a conductor as compared to zero impedance earth

ELECTROGEOMETRIC MODEL(EGM) Application Of The EGM By The Rolling Sphere Method Rolling sphere method employs the simplifying assumption that the striking distance to the ground, a mast or a wire are the same. Use of the rolling sphere method involves rolling an imaginary sphere of radius S over the surface of a substation. The sphere rolls up and over lightning masts, shield wires, substation fence, and other grounded metallic objects that can provide lightning shielding. A piece of equipment is said to be protected from a direct stroke if it remains below the curved surface of the sphere. Equipment that touches the sphere or penetrates its surface is not protected.

ELECTROGEOMETRIC MODEL(EGM) Principle of the rolling sphere method

Examples Determine the allowable stroke current (kA) through a substation equipment BIL of 850 kV, if given surge impedance is 350 ohm. A 69 kV substation is protected by a lightning mast and has a basic insulation level (BIL) of 350 kV. Calculate the strike distance (Sm) in meters (m) if the surge impedance of the conductor is 300 Ω.

Insulation Co-ordination Introduction Insulation coordination is the process of coordinating the insulation level of electrical equipment and its associated surge arresters with the expected overvoltage that occur on the power system. It is selection of suitable insulation levels of various components in any electrical system and their rational arrangement. Substation equipment require properly applied surge arresters for reliable operation.

Insulation Co-ordination It is required to ensure:- Insulation shall withstand all normal stresses and majority of abnormal ones Efficient discharge of over voltages due to internal or external causes B/D shall be only due to external causes B/D shall be at such places where least damage is caused Safety of operating personnel and public The purpose of insulation coordination is to reduce the risk of insulation failure of key electrical equipment. The insulation levels of substation equipment should be co- ordinate with the protective levels of the surge arresters and spark gaps.

Insulation Level Insulation Level is defined by the values of test voltages which the insulation of equipment under test must be able to withstand. Basic Lightning Impulse Insulation Level ( BIL) : The electrical strength of insulation expressed in terms of the crest value of a standard lightning impulse under standard atmospheric conditions. Basic Switching Impulse Insulation Level (BSL) : The electrical strength of insulation expressed in terms of the crest value of a standard switching impulse. BSL may be expressed as either statistical or conventional.

Insulation Level Lightning Impulse Voltage The BIL of substation apparatus and equipment is verified by applying a standard lightning impulse having a 1.2/50 μs waveshape. Additional test on some equipment consist of the application of a 1.2/50 μs wave chopped at either 2 or 3 μs. For example, a circuit breaker must withstand the application of a 1.2/50 μs impulse chopped at 3 μs, having a crest of 1.15 times the BIL and the application of a 1.2/50 μs impulse chopped at 2 μs, having a crest of 1.29 times the BIL.

Insulation Level Busings must withstand the application of 1.2/50 μs impulse, chopped at 3 μs, having a crest of 1.15 times the BIL. Test on transformers include a 3 μs chopped wave test at 1.10 times the BIL. Thus the lightning impulse strength of all insulations is defined by use of the standard lightning impulse waveshape.

Standard Lightning Impulse Voltage 1.2/50 us Lightning impulse voltage Theoretical Lightning impulse voltage Practical Standard Lightning Impulse Voltage 1.2/50 us

Insulation Level t1 is the equivalent time to crest based on the time taken to rise 10-90% of the crest. t2 is the time between the origin of 10 – 90 % virtual front and the point where drops to half value .

Insulation Level Insulation Level Of An Equipment Basic Insulation level is a term which includes the following characteristics of an equipment :- Power frequency voltage withstand level. Lightning impulse voltage withstand level. Switching impulse voltage withstand level. These withstand levels together characterize the insulation level of a substation equipment. Each substation equipment has its rated insulation levels.

Insulation Level These are specified in the respective standard of that equipment. The substation insulation co-ordination is governed by impulse withstand values, lightning voltage withstand levels for voltages up to 220 kV and switching impulse for voltage of 345 kV and above.

Insulation co-ordination of a substation Insulation co-ordination of a substation involves the following :- To determine the appropriate insulation of transformers and other equipments. To select the settings of co-ordinating gap. To select the correct surge arresters at various locations. Insulation co-ordination consists of steps taken to prevent damage to electrical equipment due to over voltage and to localize the flashovers to discharge over voltage at such points where they will cause minimum damage.

Insulation co-ordination of a substation This is achieved by correlating the insulation strengths of line, switchgear, transformer, machines etc. and the characteristics of the overvoltage protective devices such as rod gaps, surge arresters. The impulse withstand level of system components and the impulse protective level to protective devices are correlated. The insulation level of an equipment is expressed in term of curve of the specified impulse wave called impulse withstand level.

Insulation co-ordination of a substation Consider for example at 132 kV incoming line. Basic insulation level of 550 kV is chosen. The line insulation can withstand standard impulse wave of 860 kV crest value. The breakdown voltage of line lightning arrester is 500 kV. Transformer impulse voltage withstand is 550 kV. Therefore, a high voltage surge coming from transmission line will be discharge to earth by lightning arrester. The residual voltage less than breakdown voltage, the transformer insulation is protected.

Insulation co-ordination of a substation The insulation coordination between equipment and a surge arrester

Insulation co-ordination of a substation The following points should kept in mind while co- ordinating the insulation in the substation:- Surge arrester should have the lower protective level characteristics. The residual voltage should be less than transformer insulation strength. The voltage time curves of individual components must be taken into account. To withstand voltage characteristic of all the equipments should lie above the protective characteristic of the surge arrester with enough margin. The insulation co-ordination should be based on worst possible atmospheric condition as regards rain, humidity, pollution etc. The protective device such as surge arrester should give protection against wave of both polarities.

Insulation co-ordination of a substation Margin Protection The Margin of Protection (MP) is the difference between arrester discharge characteristics and equipment withstand level, at any given instant of time. Where:- BILequip : the BIL of the equipment Var : the discharge of voltage of arrester The margin of protection for the equipment protection and should not be less than 0.20 (20%)

Insulation co-ordination of a substation Insulation coordination Between equipment and surge arrester

Example A Substation transformer 66 kV/150 kV, have BIL of 275 kV/ 650 kV. A lightning arrester is installed on transformer terminal of 66 kV, has discharge voltage of 250 kV. Calculate the protection margin in percentage.