Two Minute Drill Number 29- Conductors and Raceways

Slides:



Advertisements
Similar presentations
Denver Fire Alarm Test Preparation Speed Drill © Ted Smitty Smith 2013.
Advertisements

FIRE PUMP ELECTRICAL CONFIGURATIONS UNDER 600 VOLTS.
Master Examination Practice Drill # O 1. Given: Two (2) rigid metal conduits (RMC) are to support a weatherproof 18 cu. In. device box, with threaded.
Master Examination Practice Drill # Ted “Smitty” Smith.
DAY 4 CHAPTER 3 CONDUCTOR SIZES,TYPES, ETC.. Continuous Load. A load where the maximum current is expected to continue for 3 hours or more. Continuous.
Master Examination Practice Drill # O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at.
2014 CHANGES TWO MINUTE DRILL COPYRIGHT TED “SMITTY” SMITH ©2014.
 E4 Electrical Installation #2 Wire Sizing and Materials.
©Ted “Smitty” Smith This speed drill focuses on calculations that will be required for the journeyman and masters examination. The question slide.
Copyright 2005 Ted "Smitty" Smith Two Minute Drill Number Three Improving your skill in code Look Up Increasing Speed Drill.
Two Minute Drill Number 32- Journeyman Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 25- Residential Improving your skill in code Look Up Increasing Speed Drill.
©Ted “Smitty” Smith  This speed drill is designed to help you practice calculations. The slides will transition in three and one half minutes instead.
Two Minute Drill #8 Copyright 2005 Ted "Smitty" Smith Practice Code Look Up.
Two Minute Drill Number 26- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill #9 Copyright 2005 Ted "Smitty" Smith.
Equipment Use In Occupancies  A receptacle shall not be grouped or ganged in enclosures with other receptacles unless they are so arranged so that voltage.
Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith.
Two Minute Drill Number 27- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Calculation Speed Drill # NEC
Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1.
Copyright 2005 Ted "Smitty" Smith Practice Code Look Up Two Minute Drill #6.
Copyright 2008 Ted "Smitty" Smith.  Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide. 
©Ted “Smitty” Smith This speed drill focuses on subjects that will be required for the journeyman and masters examination arranged by chapter of.
Two Minute Drill Number 23- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill Number 31- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Two Minute Drill Number 22- Residential Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith.
Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 24- Residential.
Speed Drill 51 Wireways and Raceways.
2008 Code Drills (C) Copyright 2008 Ted "Smitty" Smith 1 Smitty’s Speed Drills.
Copyright 2008 Ted "Smitty" Smith Two Minute Drill Number 21- Residential Improving your skill in code Look Up Increasing Speed Drill.
2014 NEC C ODE C HANGES C LASS P ART III C ALCULATIONS Ted “Smitty” Smith 8/15/2014 E Light Electric Services, Inc.
2014 NEC C ODE C HANGES C LASS P ART II Ted “Smitty” Smith 8/15/2014 E Light Electric Services, Inc.
Smitty’s Two Minute Drill Grounding
Smitty’s Two Minute Drill Grounding
HOW TO SIZE ELECTRICAL CIRCUITS
Advanced Calculations Drill 1 for the 2011 NEC
License Examination Practice Drill
E4 Electrical Installation
2011 Changes Two Minute Drill
Smitty’s Two Minute Drills
E4 Electrical Installation
Smitty’s Two Minute Drill Overcurrent Protection
Smitty’s Two Minute Drill Mixed Content -05
Theory and Calculations
Smitty’s Two Minute Drill #9: Special Occupancies
Practice Code Look Up Two Minute Drill #7
Conductors and Cables 2017 NEC
Ampacity Calculations and Overcurrent Protection 1
Calculation Speed Drill #1
Calculations: Transformers and Service Conductor Calculations
Smitty’s Two Minute Drill #1: Feeders and Branch Circuits
Two Minute Drill: Raceways and Boxes 2017
Smitty’s Two Minute Drill Photovoltaic Systems
2014 Changes Two Minute Drill
Instructor: Radian Belu, PhD
EET 323 – Electrical System Design Lecture 6: Conductors and Over-Current Protection Radian Belu, PhD.
Smitty’s Two Minute Drill Grounding and Bonding
2008 Code Drills Health Care Facilities
Two Minute Drill – Residential 3
Smitty’s Two Minute Drill Services, Feeders, and Branch Circuits 1
Two Minute Drill – Residential 3
Smitty’s Two Minute Drill Varied Number 7
Smitty’s Two Minute Drill The BIG 5 Drill 1
Two Minute Drill – Residential 2
Calculations Review Drill
Calculation Speed Drill Varied-1
Varied Calculations Drill 2
Presentation transcript:

Two Minute Drill Number 29- Conductors and Raceways Improving your skill in code Look Up Increasing Speed Drill Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith Directions Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide. Each slide will transition to the correct answer automatically in 2:00 minutes. The correct answer will transition in 15 seconds. As you progress through the slide show, the time for each question will be reduced. This drill is primarily concerning conductor and raceway installations. Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 1. Type FMC conduit can be used in wet locations. True False Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 1. B 348.12(1) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 2. Conduits exposed to sunlight and installed on rooftops shall have the ambient temperature determined using table ___________ for the purposes of determining conductor ampacity derating. 310.16 310.15(B)(2)(c) Table 1 Table 8 Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 2. B 310.15(B)(2)(c) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 3. Running threads shall be used on conduit for connection at couplings in rigid metal conduit. True False Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 3. B 344.42(A) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 4. Reinforced thermosetting resin conduit shall be permitted for nonincendive field wiring in a class I, division 2 location. True False Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 4. A 355.12(A)(2) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 5. Concealed knob and tube wiring shall be permitted in which of the following locations. Dwelling units for extension of existing installations Commercial garages Movie theaters None, knob and tube is not allowed anymore Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 5. a 394.10(1) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 6. Open wiring on insulators shall be permitted for _____________ and industrial establishments on systems of 600 volts or less and both indoors and outdoors. Farms Fish containment systems Dairy cow milking facilities All of the above Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 7. A single conductor listed and marked for use in cable tray of size __________ or greater may be installed in a cable tray in an industrial establishment. 6 AWG 1 AWG 1/0 AWG 350 kCMIL Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 7. C 392.B(1) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 8. Under floor raceways shall contain no more than ________ percent of their interior cross sectional area in conductors. 10 20 30 40 Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 9. Type MC cable shall be supported at intervals not exceeding _______ feet. 3 4.5 6 8 Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 9. C 330.30(B) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 10. When type NM cable, 12-3 is installed in an unfinished basement and is run at angles across the joists it is permissible to staple the NM cable to the bottom of the joists. True False Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 10. a 334.15(C) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 11. Flexible metallic tubing is used to enclose conductors in a branch circuit located in a dry location, the tubing is not exposed to damage and the entire length is 18 feet. Is this an acceptable installation? Yes No Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 11. No 360.12(6) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 12. A rigid PVC conduit is installed in a junction box, the PVC is 16 inches long and is unsupported. It does not contain a coupling and the other end terminates in another junction box. Is this an acceptable installation? Yes No Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 12. a 352.30(C) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 13. 3000 series wiremold is installed so that it runs along a wall from one office to another. A partition wall that is 4 inches wide separates the two offices. The wire mold runs through the wall. All receptacle devices are installed at least 6 inches away from each side of the wall. Is this an acceptable installation. Yes No Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 13. No 380.2(B)(1) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 14. A branch circuit is 16 feet in length, it is supplied by three 12 AWG, THHN conductors installed in Flexible Metallic Conduit. The conduit is installed above the suspended ceiling. Is this an acceptable installation? Yes No Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 14. Yes 348.10 Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 15. A liquid tight metallic conduit is installed to feed a load. Liquid tight flex was selected because of the number of obstacles and rigid metallic conduit would be too difficult to install. The liquid tight is run so that there are two 90 degree bends and three offsets. Is this an acceptable installation? Yes No Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 15. No 350.24 This installation would exceed 360 degrees of bend. Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith End of Drill Click the left mouse button to advance back to the first question. Each question will now be repeated without the timer to give you a chance to review it and find the answer. Clicking the left mouse button will advance the slide to the answer and the code reference. Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 1. Type FMC conduit can be used in wet locations. True False Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 1. B 348.12(1) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 2. Conduits exposed to sunlight and installed on rooftops shall have the ambient temperature determined using table ___________ for the purposes of determining conductor ampacity derating. 310.16 310.15(B)(2)(c) Table 1 Table 8 Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 2. B 310.15(B)(2)(c) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 3. Running threads shall be used on conduit for connection at couplings in rigid metal conduit. True False Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 3. B 344.42(A) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 4. Reinforced thermosetting resin conduit shall be permitted for nonincendive field wiring in a class I, division 2 location. True False Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 4. A 355.12(A)(2) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 5. Concealed knob and tube wiring shall be permitted in which of the following locations. Dwelling units for extension of existing installations Commercial garages Movie theaters None, knob and tube is not allowed anymore Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 5. a 394.10(1) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 6. Open wiring on insulators shall be permitted for _____________ and industrial establishments on systems of 600 volts or less and both indoors and outdoors. Farms Fish containment systems Dairy cow milking facilities All of the above Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 7. A single conductor listed and marked for use in cable tray of size __________ or greater may be installed in a cable tray in an industrial establishment. 6 AWG 1 AWG 1/0 AWG 350 kCMIL Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 7. C 392.B(1) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 8. Under floor raceways shall contain no more than ________ percent of their interior cross sectional area in conductors. 10 20 30 40 Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 9. Type MC cable shall be supported at intervals not exceeding _______ feet. 3 4.5 6 8 Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 9. C 330.30(B) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 10. When type NM cable, 12-3 is installed in an unfinished basement and is run at angles across the joists it is permissible to staple the NM cable to the bottom of the joists. True False Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 10. a 334.15(C) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 11. Flexible metallic tubing is used to enclose conductors in a branch circuit located in a dry location, the tubing is not exposed to damage and the entire length is 18 feet. Is this an acceptable installation? Yes No Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 11. No 360.12(6) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 12. A rigid PVC conduit is installed in a junction box, the PVC is 16 inches long and is unsupported. It does not contain a coupling and the other end terminates in another junction box. Is this an acceptable installation? Yes No Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 12. a 352.30(C) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 13. 3000 series wiremold is installed so that it runs along a wall from one office to another. A partition wall that is 4 inches wide separates the two offices. The wire mold runs through the wall. All receptacle devices are installed at least 6 inches away from each side of the wall. Is this an acceptable installation. Yes No Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 13. No 380.2(B)(1) Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 14. A branch circuit is 16 feet in length, it is supplied by three 12 AWG, THHN conductors installed in Flexible Metallic Conduit. The conduit is installed above the suspended ceiling. Is this an acceptable installation? Yes No Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 14. Yes 348.10 Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 15. A liquid tight metallic conduit is installed to feed a load. Liquid tight flex was selected because of the number of obstacles and rigid metallic conduit would be too difficult to install. The liquid tight is run so that there are two 90 degree bends and three offsets. Is this an acceptable installation? Yes No Copyright 2008 Ted "Smitty" Smith

Copyright 2008 Ted "Smitty" Smith 15. No 350.24 This installation would exceed 360 degrees of bend. Copyright 2008 Ted "Smitty" Smith