Example 1 Load 1 Load 2 20 kVA 230 Vrms R 20 mH pf 0.8 lagging 50 Hz

Slides:



Advertisements
Similar presentations
Complex power. It is a standard practice to represent S, P, and Q in the form of a triangle, known as the power triangle, shown in Fig. (a). This.
Advertisements

CH5 AC circuit power analysis 5.1 Instantaneous Power 5.2 Average Power 5.3 Effectives values of Current & Voltage 5.4 Apparent Power and Power Factor.
Lecture 71 EEE 302 Electrical Networks II Dr. Keith E. Holbert Summer 2001.
Problem #2-8 A 480 – 120 V, 60 Hz transformer has its high voltage winding connected to a 460 V system, and its low voltage winding connected to a 24/32.8°Ω.
ECE 201 Circuit Theory I1 Complex Power Designate as S Magnitude of S = Apparent Power Units are Volt-Amperes The complex sum of Real Power (P) and Reactive.
Copyright © 2013 The McGraw-Hill Companies, Inc. Permission required for reproduction or display. 1 Chapter 11 AC Circuit Power Analysis.
AC POWER ANALYSIS Tunku Muhammad Nizar Bin Tunku Mansur
Lecture 31 Sinsuoidal steady state power Instantaneous and average (real) power Reactive power Complex power Power factor Related educational modules:
LOGO LINEAR CIRCUIT ANALYSISSAJID HUSSAIN QAZI MEHRAN U.E.T, KHAIRPUR CAMPUS A.C POWERS AND POWER FACTOR.
Example 10.6 Calculating Power in Parallel Loads
ENGR-43_Lec-09-2_Complex_Power.ppt 1 Bruce Mayer, PE Engineering-43: Engineering Circuit Analysis Bruce Mayer, PE Registered Electrical.
Power Triangle.
Circuits II EE221 Unit 4 Instructor: Kevin D. Donohue Complex Power, Power Conservation, Power Factor Correction, and Applications.
AC POWER ANALYSIS Tunku Muhammad Nizar Bin Tunku Mansur
Example 1 A 9375 kVA, 13,800 kV, 60 Hz, two pole, Y-connected synchronous generator is delivering rated current at rated voltage and unity PF. Find the.
ELEC Electrical Engineering 1 Friday Revision Lecture 11 Maximum Power Transfer theorems in a.c. Circuits And Power in a.c. Circuits Semester 2,
Chapter 11 AC Power Analysis
Lecture 28Electro Mechanical System1  Consider a circuit with a source, a load, & appropriate meters.  P and Q are positive, so the load absorbs both.
Chapter 11 AC Steady-State Power
Power in AC Circuits ELEC 308 Elements of Electrical Engineering
ELECTRICAL ENGINEERING: PRINCIPLES AND APPLICATIONS, Fourth Edition, by Allan R. Hambley, ©2008 Pearson Education, Inc. Lecture 16 Phasor Circuits, AC.
1 Chapter 11 AC Power Analysis 電路學 ( 二 ). 2 AC Power Analysis Chapter Instantaneous and Average Power 11.2Maximum Average Power Transfer 11.3Effective.
AC POWER ANALYSIS Instantaneous & Average Power
Chapter 7 AC Power Analysis
Circuits II EE221 Unit 11 Instructor: Kevin D. Donohue Complex Power, Power Conservation, Power Factor Correction, and Applications.
POLYPHASE CIRCUITS LEARNING GOALS Three Phase Circuits Advantages of polyphase circuits Three Phase Connections Basic configurations for three phase circuits.
Chapter 11 AC Power Analysis
1 FOUNDATION DEGREE Course FE 101 and SC1107 COMPLEX R,L and C LOADS and the POWER WAVEFORMS.
Lecture19 Examples Presented by Robert Trajkovski.
Lab 13 – Complex Power EE 188L. Instantaneous Power Time domain.
E E 2415 Lecture 9 Phasor Circuit Analysis, Effective Value and Complex Power: Watts, VAR’s and Volt-Amperes.
AC POWER ANALYSIS. 2 Content Average Power Maximum Average Power Transfer Complex Power Power Factor Correction.
ENGR-43_Prob_5-80_Dual-Src_Complex-Pwr_Solution_.pptx 1 Bruce Mayer, PE Engineering 43: Electrical Circuits & Devices Bruce Mayer,
POLYPHASE CIRCUITS LEARNING GOALS Three Phase Circuits
1 Complex Algebra and Load Power EE341 Ali Keyhani Circuit Theory Lecture #3.
FUNDAMENTAL OF ELECTRICAL POWER SYSTEMS (EE 270)
EET 325 Oct. 14, 2005 Lecture Power factor correction.
SKM Power*Tools for Windows Part 1 Demand Load. PTW Part 1 - Demand Load Agenda Review of one-lines and the database The purpose of a Demand Load Study.
NEUTRAL CURRENT IS NOT ZERO
1 Chapter 3 AC Power Analysis. 2 AC Power Analysis Chapter 3 3.1Instantaneous and Average Power 3.2Maximum Average Power Transfer 3.3Effective or RMS.
PHYS219 Fall semester 2014 Lecture 16: AC Circuits with Inductors and Capacitors Dimitrios Giannios Purdue University.
Lesson 3: Ac Power in Single Phase Circuits
Lesson 8: Ideal Transformer Theory and Operation
DELTA-CONNECTED LOAD Method 1: Solve directly
Electric Circuits (EELE 2312)
Lesson 21: AC Power and Power Triangle
Lecture 07 AC POWER & POWER FACTOR.
Lesson 5: Power In Balanced Three-Phase Systems
AC POWER & POWER FACTOR.
Sinsuoidal steady state power
Chapter 11 AC Power Analysis
EFFECTIVE OR RMS VALUES
DKT213 ELECTRICAL TECHNOLOGY
Reactance Reactance In Phase + _ + + _ _ Voltage Current Voltage
Lecture 31 Sinsuoidal steady state power Related educational modules:
site.iugaza.edu.ps/ajasser
Transformers.
Chapter 2: AC Circuit MOHD ASRI BIN JUSOH.
ELECTRIC CIRCUITS EIGHTH EDITION
Electromechanical Systems
POLYPHASE CIRCUITS LEARNING GOALS Three Phase Circuits
ELL100: INTRODUCTION TO ELECTRICAL ENGG.
ECE 333 Green Energy Systems
Chapter 11 – Power AC Circuits
Chapter 15.
The instantaneous power
E E 2415 Lecture 9 Phasor Circuit Analysis, Effective Value and Complex Power: Watts, VAR’s and Volt-Amperes.
Chapter 11 – Power AC Circuits
EEE 3230 POWER SYSTEM ANALYSIS
Engineering Circuit Analysis
Presentation transcript:

Example 1 Load 1 Load 2 20 kVA 230 Vrms R 20 mH pf 0.8 lagging 50 Hz If the combined power factor of the load 1 and load 2 is 0.75 lagging, determine the value of R.

Things You Should know: Power-Impedance Relationships Reactive power of L, QL, is positive Reactive power of C, QC, is negative Pre-requisite: Basic Trigonometry Complex number

Solution: Load 1: Load 2: P2 Q2 S2 q2 P1 Q1 S1 q1 Total Load: ST QT=Q1+Q2 qT PT=P1+P2 Note: The power triangles were drawn not to scale

P1 Q1 S1 q1  

P2 Q2 S2 q2 

PT QT ST qT  

PT QT ST qT  

Exercise 1 Load 1 pf 0.8 lagging 20 kVA C 5 W Load 2 230 Vrms 50 Hz If the combined power factor of the load 1 and load 2 is 0.95 lagging, determine the value of C.

If V1 = 2000 V rms, determine: Example 2: 4 kW pf 0.9 lagging 6 kVAR pf 0.5 leading Vs Is 0.1 W 0.3 W 0.2 W + - V1 Load 1 Load 2 If V1 = 2000 V rms, determine: (i) Vs and Is (ii) Complex power for all circuit elements (exclusive of the source) (iii) Complex power supplied by the source.

If I1 = 4545 A rms, determine: Exercise 2: 4 kW pf 0.9 lagging 6 kVAR pf 0.5 leading Vs Is 0.1 W 0.3 W 0.2 W Load 1 Load 2 I1 If I1 = 4545 A rms, determine: (i) Vs and Is (ii) Complex power for all circuit elements (exclusive of the source) (iii) Complex power supplied by the source.