Good Morning everybody. A discussion of fire scenarios and models for steel framed enclosed multi-storey balconies. Gordon Cooke International Fire Safety.

Slides:



Advertisements
Similar presentations
Loft Conversions - The building regulations Chris Wigley MD London Building Control Ltd
Advertisements

Designing House Extensions - draft Supplementary Planning Document (SPD) for consultation Eleanor Parker, Development Management.
The Game of Algebra or The Other Side of Arithmetic The Game of Algebra or The Other Side of Arithmetic © 2007 Herbert I. Gross by Herbert I. Gross & Richard.
Integration of Structural Engineering into Fire Engineering Design LEUNG Siu-man Chief Structural Engineer Buildings Department.
Introduction to Lateral Force Resisting Systems
Fire-Resistive Construction (2nd part)
J. Amdahl,, NTNU Dept, Marine Technology Beregning av ulykkeslaster for offshore stålkonstruksjoner – NFS Accidental Fires Design criteria.
1 Making buildings better Building Tight Chris Knights.
>ENTER< [PLS PUT ON SAFETY HELMETS BEFORE ENTERING THIS SITE.]
Chapter 11 Creating Framed Layouts Principles of Web Design, 4 th Edition.
Timber Framed Structures
BRE: The Fire Performance of Building Envelopes
Chp12- Footings.
FIRE SAFETY WITH CONCRETE - Experiences from real fires and full scale tests Tauno Hietanen standardization manager Finnish Concrete Industry.
Overview Waffle Slab.
Walls Ron Gatepain constructionsite.
LAYOUT OF STEEL STRUCTURES
Local Application Total Flooding System: (NFPA 12) A system consisting of a supply of carbon dioxide arranged to discharge into, and fill to the proper.
Eurocode 1: Actions on structures – Part 1–2: General actions – Actions on structures exposed to fire Part of the One Stop Shop program.
WALL FRAMING Section 6 of AS 1684 relates to the regulations governing timber wall construction.
Eurocode 1: Actions on structures – Part 1–2: General actions – Actions on structures exposed to fire Part of the One Stop Shop program Annex B (informative)
1 ISAT Module III: Building Energy Efficiency Topic 6:Stead-State Building Loads z Fabric Loss z Ventilation Loss z Environmental Temperature z Steady-State.
IBC 2006 Chapter 5 Building Height and Areas After determining occupancies, the code analysis determines what height and areas are allowable for the occupancy.
Amendment to GPDO Householder Permitted Development.
Task 3.4. Validation of horizontal solutions Fire and mechanical characterization.
Enclosure Fire Dynamics
Eurocode 1: Actions on structures –
Enclosure Fire Dynamics
Reinforced Concrete Design II
COLUMNS.
COLUMNS. COLUMNS Introduction According to ACI Code 2.1, a structural element with a ratio of height-to least lateral dimension exceeding three used.
Fire, Thermal & Acoustic Insulation New European Resistance To Fire Standards.
Eurocode 1: Actions on structures – Part 1–2: General actions – Actions on structures exposed to fire Part of the One Stop Shop program Annex E (informative)
Design of steel structures under the aspect of fire protection measures TU BRAUNSCHWEIG iBMB Dr.-Ing. E. Richter Institute for Building Materials, Concrete.
FOOTINGS. FOOTINGS Introduction Footings are structural elements that transmit column or wall loads to the underlying soil below the structure. Footings.
Eurocode 1: Actions on structures – Part 1–2: General actions – Actions on structures exposed to fire Part of the One Stop Shop program Annex F (informative)
Eurocode 1: Actions on structures – Part 1–2: General actions – Actions on structures exposed to fire Part of the One Stop Shop program Annex A (informative)
Prof. Kyriakos Papaioannou ARISTOTLE UNIVERSITY GREECE 7th Intern. Sprinkler Conference-Copenhagen 24-25/6/
An-Najah National University Faculty of Engineering Civil Engineering Department.
02 November EN : Structural fire design EC2 Workshop Eurocodes Moscow 2010 J.C. Walraven Vermelding onderdeel organisatie.
Construction Type of Buildings
Engineering Analysis of NFPA 285 Tested Assemblies
Neil Cooper Fire Safety Residential Implementing the Changes.
Topic 11: Timber Subfloor - Advanced
Lecture 15 - Timber Wall Framing Example
WALLS.
Fire Resistance of the Load Bearing Structure of High Bay and Instrument Halls Fire and Egress Safety Analysis of the Instrument Halls Björn Yndemark WSP.
DIMENSIONAL ANALYSIS SECTION 5.
Sprinkler Loads on Trusses
Sprinkler Loads on Trusses Educational Presentation.
Unit 6: Building Technology in Construction Learning Outcome Understand the techniques used in the construction of superstructures for low-rise domestic.
Overdriven Nails in Structural Sheathings Overview.
Amendments to the Town and Country Planning (General Permitted Development) Order 2008.
Prof. Shrikant M. Harle Asst prof. Dept of Civil Engg PRMCEAM
Building Construction
CITY OF HARARE EMERGENCY SERVICES
BOMBA BRIEFING QUESTIONAIRE FOR 30 AUGUST 2017
Code of Practice for Fire Safety in New and Existing Community Dwelling Houses Eamon O’ Boyle.
M. Z. Bezas, Th. N. Nikolaidis, C. C. Baniotopoulos
Why Know Building Construction
Structural Fire Engineering, October 2015, Dubrovnik, Croatia
Prepared by John R. Henry, P.E. Senior Staff Engineer
Decree of the Ministry of Interior 3rd August 2015 The “so called” Italian Fire Prevention Code - IFC: S6 – Fire Control and Suppression provisions.
Performance Based Design of a Steel Frame Hotel
Design Ribbed and Flat Slabs
Eurocode 1: Actions on structures –
Eurocode 1: Actions on structures –
Fire Resistance of Steel Structures
Masonry Bearing Walls.
Fire performance of structures
Presentation transcript:

Good Morning everybody

A discussion of fire scenarios and models for steel framed enclosed multi-storey balconies. Gordon Cooke International Fire Safety Consultant ( Formerly Visiting Professor, School of Engineering and Mathematical Sciences, City University, London) Prepared for the Institution of Structural Engineers Steel in Fire Forum meeting, 24 September 2013, London

Proprietary balcony

Advantages of balconies These include Adding to the usable space in the dwelling Adding to the monetary value of the dwelling Providing a glazed space in which to enjoy the sun protected from wind and rain Improving the aesthetic of an old building

Single cantilever balcony

Vertical section through multi-storey balcony

Horizontal section through balcony

Effect of cross wind

Two balcony systems Multi-storey balconies can be added relatively easily, often with four unseen slender steel columns per balcony which extend from ground level to top of building so that the whole balcony system is self- supporting and adds minimal imposed dead loads to the parent building. Single storey balconies can be added to a building so that they are: a) supported from the external wall of the parent building with diagonal tension members, or b) supported by an existing cantilevered floor. In both cases the dead load is normally low as the balcony system can be lightweight.

Functional regulations in the UK affecting balconies Building products are governed by regulations, codes, and standards. The UK comprises England, Wales, Scotland and Northern Ireland The regulations applying to new buildings and buildings subject to alteration are: In England and Wales -The Building Regulations 2010

Functional regulation B3 (England and Wales) B3. (1) The building shall be designed and constructed so that, in the event of fire, its stability will be maintained for a reasonable period.

Fire resistance in flats (ADB) According to Table A2 of AD B, which applies in England and Wales, structural elements such as beams and columns within a non-sprinklered block of flats need the following amount of fire resistance (the numbers in the first row of the table below are the height of the top floor (not the top of the building) above ground level measured in metres) Not more than 5mNot more than 18mNot more than 30mMore than 30m 30 minutes60 minutes90 minutes120 minutes

Importance of choice of fire scenario Fire scenario affects amount of fire resistance of balcony structural elements If small balcony columns are to be employed the amount of fire protection is very dependent on FR required The section factor (A/V) needed for a bare steel I-section column needs to be less than 50m-1 to achieve 30 minutes FR for 4-sided exposure. E.g. a massive bare solid steel column 150mm square achieved only 38 min in a FR test. An RHS section 150mm square with wall thickness of 8mm has a section factor of 135m-1 requiring a large thickness of added fire protecting material. BS 5950-Part 8: 2003, the ASFP yellow book and fire protection manufacturers gives guidance on A/V values etc.

Section factor v fire resistance

Fire safety engineering (ADB) This can provide an alternative approach to fire safety. It may be the only practical way to achieve a satisfactory standard of fire safety in some large and complex buildings and in buildings containing different uses e.g. airport terminals. Fire safety engineering may also be suitable for solving a problem with an aspect of building design which otherwise follows the provisions of this (ADB) document.

Some questions What fire resistance is required for balconies? Should the fire ratings in the building regulations guidance Approved Document B be adopted without question? Could the fire severity be more (or less) than the regulatory (ADB) value? What standardised fire models might be encountered and be appropriate? What purpose-designed fire test rig might be suitable for approval purposes?

Possible fire models ADB Equivalent time of fire exposure based on fire load and ventilation factor Total engulfment by standard fire, BS EN : 2004 External fire model, BS EN Jetting flames model (Eurocode or Law/OBrien)

Test for external cladding

Typical fire test rig for external cladding

Some standard fire (temperature-time) exposures

BS EN :2004 This specifies a method for determining the fire resistance, in respect with loadbearing capacity and with no separating function, of: balconies exposed to the fire from either outside or inside the building; and walkways exposed to the fire from either outside or inside the building. This European standard is used in conjunction with BS EN i.e. involving exposure to the standard fire resistance test exposure (ISO 834).

Bare external structural steel Law M and OBrien T, Fire safety of bare external structural steel, pub Constrado (now SCI), 1981, 88 p

Bare external structural steel Section C Design Tables, states in C2.2 that a bare steel column opposite a window with no through draft should be at least two thirds of the window height away from the plane of the window if the limiting temperature of the steel is not to exceed 550 degC. This is conservative and detailed calculations might show that less gap is needed but these calculations are time consuming and tedious. In this location it is deemed to be outside the trajectory of the jetting flame. Hence for a window height of 2m the bare column should be 1.33m away. Assumes fire load density does not exceed 50 kg/m2 of floor area. Greater gap may be needed if through-draft present

External fire exposure curve. Clause 5.1 of EN In some cases elements may be exposed to conditions which are less severe than when the element or structure is exposed to a compartment fire. Examples of this are walls at the perimeter of the building which may be exposed to an external fire or flames coming out of windows… This exposure condition is only relevant to the evaluation of fire resistance of separating elements. Other evaluation techniques exist for the evaluation of beams and columns …

Flame temperature model PD : 2003 page 43 gives an equation (equation 41) for flame temperature and states that the temperature of the flames at the opening can exceed the temperature of the fire within the compartment. This can occur when the fire within the compartment is starved of oxygen and air is entrained outside the compartment leading to stoichiometric combustion.

Time equivalent - early equation by Law

Numerical example using Law equation

Current methods of deriving time equivalent PD : 2003 Application of fire safety engineering principles to the design of buildings, Part 3 Structural response and fire spread beyond the enclosure of origin, section Equivalent time of fire exposure Eurocode 1: Actions on structures Part 1-2: General actions – Actions on structures exposed to fire, Annex F equivalent time of fire exposure. However the National Annex to the Eurocode, BS EN : 2002, states that Annex F may not be used, and PD : 2002 should be used as a replacement.

Time equivalent using PD : 2003 t e = k b w v q(31) (valid for unprotected steel up to 40 minutes fire resistance) where: t e = duration of time equivalence (min) k b = 0.07 for typical boundary surfaces,eg masonry, gypsum plaster (m 2 /MJ) q = fire load density per unit area of enclosure surface or floor area (MJ/m 2 )

Time equivalent using PD , continued w v = 1.7 H -0.3 { (0.4 – A v /A f ) 4 } (1+b v A h /A f ) (32) H= height of enclosure (m) A v = area of ventilation in vertical plane (m 2 ) A f = floor area of enclosure (m 2 ) A h = area of ventilation in the horizontal plane (m 2 ) b v = 12.5{1 +10 (A v /A f ) – (A v / A f ) 2 } 10 (33)

Time equivalent using PD , continued For residential buildings, safety factor у 1 = 1.1 and 1.6 for height of enclosure above ground level of 20m and 30m respectively, and у 2 = 1.2 у 3 may be taken to be 0.6 Substituting values used in previous example gives a time equivalent of 53 min which appears sensible, but the PD states that it cannot be used when time equivalent is greater than 40 min.

Equations and numerical values taken from PD : 2007 t e,d =q f,d k b w f limited to 30 minutes for totally unprotected structural steel (B.1) where q f,d = fire load per unit floor area k b = conversion factor = 0.09 when q d is given in MJ/m 2 (B.4a) w f = ventilation factor A t = total area of enclosure (walls, ceiling and floor including openings) A f = floor area of compartment For small fire compartment (A f < 100m 2 ) without openings in the roof

Equations and numerical values taken from PD : 2007, continued w f = O -0.5 A f /A t (B.3) where O is opening factor according to Annex A (of EN ?), ie O =A v (h eq 0.5 )/A t where A v = total area of vertical openings on all walls h eq = weighted average of window heights on all walls A t = total area of enclosure

Calculated value using PD : 2007 Substituting values gives time equivalent of 82 min. This seems high and, again, the calculation result is not acceptable because time equivalent exceeds limit of application i.e. exceeds 30 min. Note. The limits of application in PD and PD are different (40 min v 30 min)

Tentative Conclusions The time equivalent calculation is easy to do and gives periods of fire resistance, but, for the above example compartment size and fire load density, gives results which are outside the limits of application. This applies to PD and BS The external fire exposure curve is inappropriate. The BS EN for balconies assumes the whole balcony is exposed to the BS EN standard fire – a very severe fire exposure. The flame temperature model in PD is difficult to apply to flames outside the opening partly because it requires the use of flame radiation configuration factors and does not result in a period of fire resistance. The jetting flames model (Law/Eurocode) involves tedious calculations and is difficult to use. The ADB tabular values of fire resistance are convenient to use and more likely to be accepted by the building control official.

Ancient references to simple time equivalent equation Law, Margaret. Prediction of fire resistance, Paper No2 of Fire resistance requirments for buildings – a new approach. Dept of Environment and Fire Offices Committee Joint Fire Research Organisation, Symposium No 5, London 1973 HMSO Cooke GME, Fire Protection, chapter of Volume 1 of Specification 85, Published by The Architectural Press, 1985, pp 69.Cooke GME, Fire Protection, chapter of Volume 1 of Specification 85, Published by The Architectural Press, 1985, pp 69. (available on website under Publications)

Are the FR requirements anomalous?

Thats it - thanks