Psychrometric analysis Revision of principles - Central plant for UBCLQT-40-3: Building & Engineering Systems Performance and UBLLSM-20-3: Mechanical Services
Psychrometric quantities temperature dry bulb, t [oC d.b.] wet bulb, t’ [oC w.b.] relative humidity, [%rh] = avp / svp percentage saturation, μ [% sat.] = ms/mss moisture content, x [kg.kg-1dry air] specific volume, v [m3.kg-1 dry air] = 1/ specific enthalpy, h [kJ.kg-1 dry air] dew point temperature, td [oC]
Psychrometric chart Lines of constant d.b. temp. Dry bulb temperature, t
Psychrometric chart Lines of constant moisture content Moisture content, x
Psychrometric chart percentage saturation , Lines of constant relative humidity, (percentage saturation)
Psychrometric chart Wet bulb temperature, t’ Lines of constant w.b. temp. Wet bulb temperature, t’ 5oC wb 5oC db
Psychrometric chart Lines of constant specific volume specific volume, v
Psychrometric chart Specific enthalpy, h ‘Lines’ of constant
Psychrometric chart Dew point temperature, td oC
State point Any two psychrometric quantities can be used to define a state point. All other properties can be read from the chart 50 %rh 26.5 kJ.kg-1 0.82 m3.kg-1 8.9oC db 0.00495 kg.kg-1 14oC db
Exercise - complete Table 1
Exercise – Solutions
Ideal processes Isothermal humidification Adiabatic humidification Sensible heating Sensible cooling Adiabatic dehumidification Isothermal dehumidification
Real processes - Sensible Heating Heating load, QH = ma (h2 - h1) h2 - h1 1 2 Heater Battery
Heating load, QH = ma (h2 - h1) Real processes - Sensible Heating Plant Loads Example 1: Air flows at a rate of 3.42 kg.s-1 into a heater battery. If the initial condition of the air is state 5 (see Table 1) and the air leaves the heater battery at a temperature of 31 oC d.b., determine the load on the heater battery in kW. Heating load, QH = ma (h2 - h1)
Real processes - Sensible cooling Cooling load, QC = ma (h1 - h2) (Nominal) h1 - h2 2 1 Cooler Battery
Real processes - Cooling & Dehum. 1 2 Cooler Battery
Real processes - Cooling & Dehum. Cooling load, QC = ma (h1 - h2) (Nominal) h1 - h2 1 2 Cooler Battery
Real processes - Cooling & Dehum. Cooling load, QC = ma (h1 - h2) (Nominal) h1 - h2 1 2 Cooler Battery
Contact Factor Cooling load, QC = ma (h1 - h2) h1 - h2 1 2 s ADP t
Real processes – Cooling with dehum Plant Loads Example 2: A cooler battery takes a flow of 1.5 kg/s of air at 25oC d.b. with a moisture content of 11.3 g/kg and dehumidifies to obtain a moisture content of air leaving the battery of 8 g/kg. If the cooler contact factor is 85%, determine the apparatus dew point and the nominal cooling load in kW. Cooler Contact Factor,
Real processes - adiabatic humidifier Adiabatic process - where no energy transfer occurs i.e. h1 = h2 Load = 0 2 1 Air Washer
Real processes - steam injection h 2 1 Steam humidifier
Humidifier saturation efficiency ADP 2 1
Humidifier saturation efficiency, Real processes – Humidification Plant Loads Example 3: Air enters an air washer at 31oC d.b., 14.4oC w.b. and leaves with a moisture content of 0.008 kg/kg d.a. Determine the saturatiion efficiency of the air washer. What factors influence the saturation efficiency of humidifiers generally? Humidifier saturation efficiency,
Room heat loads Summer room loads:- Sensible heat gain + Latent heat gain Sensible Heat Ratio 1 Room ratio line R S tR - tS
Room heat loads Winter room loads:- Sensible heat loss + Latent heat gain Sensible Heat Ratio 1 Room ratio line R S tS - tR
Room heat loads Example 4: The room is to be kept at state 4 using a flow of 1.50 kg.s-1 of air at state 6. Determine the room sensible and latent loads in kW. The specific heat capacity of moist air is 1.02 kJ.kg-1K-1
Central plant AHU - 100% fresh air Summer cycle 2 4 6
Central plant AHU - 100% fresh air Summer cycle 2 Cooler battery 8 4 6
Central plant AHU - 100% fresh air Summer cycle 2 Cooler battery + Re-heater battery 8 4 6
Central plant AHU - 100% fresh air Summer cycle O Cooler battery + Re-heater battery C R S Room ratio line (RRL)
Central plant AHU - 100% fresh air Winter cycle 3 7 5
Central plant AHU - 100% fresh air Winter cycle Pre-heater battery 3 7 5 10
Central plant AHU - 100% fresh air Winter cycle Pre-heater battery + steam humidifier 3 9 7 5 10
Central plant AHU - 100% fresh air Winter cycle Pre-heater battery + steam humidifier 3 + re-heater battery 9 7 5 10
Central plant AHU - 100% fresh air Winter cycle Pre-heater battery Room ratio line (RRL) + steam humidifier R + re-heater battery B S O A
Central plant AHU - 100% fresh air Winter cycle Pre-heater battery Room ratio line (RRL) + adiabatic humidifier R + re-heater battery B S O A
Mixing AM A xA BM M xM B xB tB tM tA
Real processes - Mixing Example 5: Air in state 3 is mixed with air in state 4 to obtain mixed air, state M, with a dry bulb temperature of 25oC. If the mass flow rate of mixed air is 1.45 kg/s, determine the flow rates of consituent air flows.
Central plant AHU - recirculation air 2 6 4 C C’ M Summer cycle
Central plant AHU - recirculation air S M Room ratio line (RRL) Winter cycle