OCP Engineering Workshop 2017 Delta Electronics; INC PSBG IDC 2017 Sep.
Modular Dimensions in Standard Flexible Power Shelf Height Size
Modular Dimensions in Standard Enable multiple configurations racks. No real physical size change on rack.
Dim. A-G, “Lock” to “Stop” Modular Dimensions (1) G Table 1 42” Rack 30” Rack Dim. A-G, “Lock” to “Stop” 789.6 +/- 1.0 645.0 +/- 1.0
Modular Dimensions (2)
Modular Dimensions (3) For 12V OCP rack, Dim. G-H should be: Dim. G-H, “Stop” to “RTN” G H For 12V OCP rack, Dim. G-H should be: 793.4 – 789.6 = 3.8 mm For 48V OCP rack, 652.6 – 645.0 = 7.6 mm This dimension is depended on used clip type / size. Table 2 12V Rack 48V Rack Dim. G-H, “Stop” to “RTN” 3.8 mm 7.6 mm
Dim. A-G, “Lock” to “Stop” Multiple Configuration Racks Table 1 42” Rack 30” Rack Dim. A-G, “Lock” to “Stop” 789.6 +/- 1.0 645.0 +/- 1.0 Table 2 12V Rack 48V Rack Dim. G-H, “Stop” to “RTN” 3.8 mm 7.6 mm 42” / 12V OCP Rack 42” / 48V OCP Rack 30” / 12V OCP Rack 30” / 48V OCP Rack
Flexible Power Shelf Height Size Define power shelf installed bottom datum. Propose bus bar connection patterns to for multiple power shelf form factors 12V / 18 KW / 1OU Power shelf 48V / 36 KW / 2OU Power shelf
Clip mated on 12V Bus Bar 48V clip +12V Bus Bar 21.3 mm Return Bus Bar Dim. G-H, 3.8 mm 48V clip 21.3 mm +12V Bus Bar Return Bus Bar
Clip mated on 48V Bus Bar 48V clip +48V Bus Bar Return Bus Bar 13.4 mm Dim. G-H, 7.6 mm
Power shelf bottom datum Proposed Connection pattern for 12 VDC Power Shelf in 12V OCP Rack G Dim. G-H, 3.8 mm 22 26.0 48.0 Return Bus Bar 16 12 24.0 TYP. Power shelf bottom datum Proposed Connection pattern for 12 VDC
Power shelf bottom datum Proposed Connection pattern for 48 VDC Power Shelf in 48V OCP Rack Return Bus Bar Power shelf bottom datum 48.0 24.0 TYP. 48.0 48.0 12 Dim. G-H, 7.6 mm 14 20 20 G Proposed Connection pattern for 48 VDC
Smarter. Greener. Together. To learn more about Delta, please visit www.deltaww.com.