Reduce Arcing Time – Bus Differential

Slides:



Advertisements
Similar presentations
Copyright 2008 ABB - 1 All Rights Reserved Optical Arc Flash Protection and Installation Experience Boris A. Vega Regional Sales Manager, ABB Inc. MEMSA.
Advertisements

CURRENT TRANSFORMERS AND VOLTAGE TRANSFORMERS
GENERATOR PROTECTION.
1 Arc Flash Hazard Mitigation Analyse, Maintain, Mitigate. E3 Calgary – September 16, 2014 Dean Wiersema.
PROTECTION scheme for bus bar / feeder
Power System Analysis/ Power System 1 EEE 4113/ EEE 3131
GE Consumer & Industrial Multilin  Single & Three phase models  Specific mount CT’s  Rectangular & Toroidial models  Plastic case & cast models  Multi.
EE4503 Electrical Systems Design
Generator Protection. Amount of Protection Rated power of the generator Ratio of its capacity to the total capacity of the system Configuration of the.
Advanced Protective Relaying Based on Rogowski Coil Current Sensors
Unit Transformer Unit transformer are step up transformer which is connected to generating house & step up voltage from 15kV voltage to 132 voltage level.
Objective of the Lecture Describe a basic electric circuit, which may be drawn as a circuit schematic or constructed with actual components.
Bonding, Grounding and the NEC  Presented by The National Association of Certified Home Inspectors
Connections of a CT and a PT to supply, load and relay.
Electrical Resistance and Ohm’s Law Electric circuits are used to convert electrical energy into some other form of energy we need.
By J DAVID MANOHAR (08A31A0232). NECESSITY OF SUPERCONDUSTOR  Damage from short circuit is constant threat in power systems  All the power systems components.
Protection of Microgrids Using Differential Relays
Protection and switchgear
Transformer Protection Over-current protection in the form of fuses may be the only protection provided to a small 100 kVA, 11 kV/440 V distribution transformer.
Neptune Power Versions compared 1 All rights reserved © 2003, Neptune Power sub-system Versions 1 and 2 Key features V2 is functionally equivalent to V1.
A SEMINAR ON 400 KV GSS(RRVPNL) BIKANER.
MAHATMA GANDI INST. OF TECHNICAL EDUCATION & RESEARCH CENTRE, NAVSARI.
DC Machine & Transformer
 The figure below shows a protection system for a transmission line, consisting of a CT, PT, a relay and its associated circuit breaker.
Protection of Power Systems
SEMINAR PRESENTATIon ON C IRCUIT B REAKER DEPT. OF ELECTRICAL ENGG. JALPAIGURI GOVT. ENGG. COLLEGE PRESENTED BY Madhusudan Mahato Malay Ghosh.
By: 47.M.B.J.Varma 48.Mallikarjuna Abhilash 49.Maraka Kulateja 50.Prajakta Mategadikar 51.Medepalli Nikhil Raj.
Power System Protection 1. Contents Contents Introduction Functions of Equipment Protection Functions of Protective Relays Required Information for Protective.
ELECTRICAL PLANT DIMENSIONING
ANALOGUE ELECTRONICS CIRCUITS 1
Announcements Design Project has firm due date of Dec 4
SERIES, PARALLEL, AND SERIES-PARALLEL CIRCUITS
Sub Station.
Protection of Power Systems
Quality and Security Assessment of Protection Systems
Announcements Please read Chapters 9, 10 and 11
CHAPTER 6 SPECIAL TRANSFORMERS Electrical Machines.
Circuit Protection Unit 9.
2011+ NEC Article Arc Energy Reduction. Where the highest continuous current trip setting for which the actual overcurrent device installed.
Power Generation and Distribution
Protection of Power Systems
ACTIVE LEARNING ASSINGNMENT
Smitty’s Two Minute Drill Overcurrent Protection
GROUND-FAULT GROUND-CHECK MONITOR
Mersen’s Fused Coordination Panelboard
Principles & Applications Residential Wiring Concepts
Basics of electrical engineering
ELECTRICAL INSTALLATION AND MAINTENANCE (EIM) 5 INSTALL ELECTRICAL PROTECTIVE DEVICES FOR DISTRIBUTION, POWER, LIGHTING, AUXILIARY, LIGHTNING PROTECTION.
Chapter 7 System Protection
This webinar brought to you by the Relion® product family
This webinar brought to you by the Relion® product family
Background Information on Hurricane Matthew Event No.1 Event No.2
A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Power Plants By: Stephanie Mercer.
The Electric Circuit.
Reduced Safety/Reliability: Arc Flash Hazard Example
Click to Continue to Calculator window
GEORGIA TECH PROTECTION CONFERENCE 2018
Presented to: IEEE-IAS (Atlanta) Presented by: Michael D. Seal, P.E.
POWER SYSTEM ENGINEERING
EET 323 – Electrical System Design Lecture 9: Grounding
Power System Protective Relaying-Part One
EET 503 Power System Protection (Instrument transformer )
What Is to Be Covered? Electrical Shock - Why Have GFCIs?
POWER SYSTEM COMMISSIONING AND MAINTENANCE PRACTICE
POWER SYSTEM COMMISSIONING AND MAINTENANCE PRACTICE
Substation Equipment's
Long Island Interconnection Working Group Meeting August 22, 2019
Fuses vs Circuit Breakers for Low Voltage Applications
Presentation transcript:

Reduce Arcing Time – Bus Differential Bus Differential (87B) MV or HV IM1 = IF1 + IF2 + IF3 IM1 = IF1 + IF2 + IF3 + IF4 87B IM1 IF2 IF3 IF1 IM1  IF1 + IF2 + IF3 X IF4 Instantaneous trip! CT issues CT balancing CT accuracy / linearity CT “burden” capacity Load impedance - saturation Zone Selective Interlocking is a way of communicating between circuit breakers to let upstream breakers know when they should delay tripping and when they should trip instantaneously. Normally, the upstream breaker must delay since you want only the downstream breaker to clear the fault and the upstream breaker to remain closed on the fault. But if the fault occurs upstream from the downstream breaker, the downstream breaker can’t clear the fault. The Zone Selective Interlocking works is that a restraining signal is transmitted from any downstream breaker that sees a fault up to the upstream breaker feeding that downstream breaker. The upstream breaker sees the fault current, but also sees the restraining signal and delays tripping, allowing the downstream breaker to clear the fault. On the other hand, if the downstream breaker doesn’t see the fault, it won’t send the restraining signal and that is a green flag for the upstream breaker to trip instantaneously, as it is closest breaker that clear the fault. The result is that the fault is cleared in 80 milliseconds instead of 1/2 second and the incident energy released at the point of the fault drops from 43.7 calories (which exceeds the 40 calorie limit of PPE 4), down to only 7 calories, safely below the 8 calorie PPE 2 limit which is only a fire resistant shirt and pants.

CT Error 𝐼 𝑒 = 𝐸′ 𝑋 𝑒 𝐸′=𝐼′∙ 𝑍 ′ + 𝑍 𝐵 𝐶𝑇 𝑒𝑟𝑟 = 𝐼 𝑒 𝐼′+ 𝐼 𝑒 Primary Current Secondary Current CT excitation current 𝐼 𝑒 = 𝐸′ 𝑋 𝑒 𝐸′=𝐼′∙ 𝑍 ′ + 𝑍 𝐵 𝐶𝑇 𝑒𝑟𝑟 = 𝐼 𝑒 𝐼′+ 𝐼 𝑒

CT Saturation #14 AWG (0.002525 /ft) 100’ total wiring (50’ x 2) 22.5V ISEC or I’ I PRI 600:5 Z’/2 (conductor impedance) Z’/2 + - E’ ZB (relay burden) Emax ~5V 𝐸′=𝐼′∙ 2 𝑍 ′ /2 + 𝑍 𝐵 E’ < EMax 𝐸′=𝐼′∙ 𝑍 𝑇𝑜𝑡𝑎𝑙 #14 AWG (0.002525 /ft) 100’ total wiring (50’ x 2) ZB = 0.2  load Z’ = 100 * 0.002525 = 0.25  ISEC = I’ = 5A * 10 = 50A (10x fault) E’ = I’*ZTotal = 50*(0.25+0.2) = 22.5V 22.5V 0.04A 0.5% (or better) accuracy?

 CT Error 𝐶𝑇 𝑒𝑟𝑟 = 𝐼 𝑒 𝐼′+ 𝐼 𝑒 𝐶𝑇 𝑒𝑟𝑟 = 0.04 50+0.04 =0.08% I’ = 50 A I’ Secondary Current I Primary Current 𝐶𝑇 𝑒𝑟𝑟 = 𝐼 𝑒 𝐼′+ 𝐼 𝑒 I’ = 50 A Ie = 0.04 𝐶𝑇 𝑒𝑟𝑟 = 0.04 50+0.04 =0.08%  Better than 0.5%