Preferred Utilities Manufacturing Corp Oxygen Trim Overview Preferred Utilities Manufacturing Corporation 31-35 South St. • Danbury • CT www.preferred-mfg.com
Overview Introduction Combustion Experience ZP Oxygen Analyzer PCC-III Multiple Loop Controller Pricing Summary I think you will agree with me that…. the PCC-III is backed by a wealth of experience PCC-III has the best features on the market Has the best applications available Is the easiest controller Best Value
In-Situ Oxygen Probe Field replaceable probe Only one conduit to stack. No separate analyzer, one less item to mount
In-Situ Oxygen Probe Proven Reliable No Reference Air Sensing element has been proven reliable in 100s of installation over the last 10 years No Reference Air The probe uses ambient air as a reference. Competitors use instrument air and run the risk of element cracking due to water Automated, menu driven pushbutton calibration. Fully automatic calibration package available.
In-Situ Oxygen Probe Thick cell Ceramic heater Avoids premature cell failures Ceramic heater provides reliable long life Complete detailed diagnostics Automatic impedance checking Alarms when time to recalibrate Alarms when reaching end of cell life Optional fuel gas temperature element / T/C input
Jackshaft Control with Air Trim Coming Soon!
Air Trim
Fuel Trim
Combustion Experience 25 years of Combustion Control Experience… Third Generation Digital Controller 2400 PCC II/III Controllers Installed Exclusively in Combustion Control Applications 38 SCADA/Flex Projects 640 Rotary Cup Burner Projects
Combustion Experience JC Boiler Control & Monitoring Projects…. > 8000 Boilers Numbers from 1998.… 324 Smoke Opacity Monitors 243 Flue Gas Temperature Monitors 226 Draft Indicators 212 Draft Controllers 91 Lead Lag Controllers
Combustion Experience PCC II/III Combustion Control Projects.... 967 Boilers 624 Jackshaft Controlled Boilers 127 Parallel Positioning Controlled Boilers 103 Metering Controlled Boilers 351 Oxygen Trim Systems 13 EPA Compliant Opacity Monitors
PCC-III Combustion Experience Boiler Specific... Operator Friendly F(x) Characterizers with “Learn” Mode Built In Boiler Efficiency Constructed For Boiler Front Mounting 120 Vac Inputs for Direct BMS Interface Triac Outputs to Drive Electric Actuators Free Standard Combustion Blockware There are many digital controller manufacturers, but NONE have Preferred’s in-depth and ongoing combustion control experience.
Constructed For Boiler Front Mounting... PCC-III - Construction Constructed For Boiler Front Mounting... Weather Proof / Rain Proof Construction 7 3/4” Deep Case For Easy Mounting in Standard Burner Panels 32 to 120 deg F rating for Continuous Operation Built-in Surge Suppressor, and 99-135 Vac Input Power Rating for Industrial Applications
English Used For Operation & Configuration... PCC-III - Display English Used For Operation & Configuration... Large Displays & Pushbuttons 16 character process variable and alarm description messages 10 point first out alarm annunciator Intuitive Bargraphs User Configurable Pushbuttons
PCC-III - Input / Output Designed For Boilers... One PCC-III with integral I/O is capable of: A Dual Fuel, Fully Metered with Oxygen Trim Control Scheme! Standard 120 Vac Inputs, 8 Amp Relay Outputs for Easy BMS Interfacing 215 mA 24 Vdc Power Supply for Transmitters Triac Output Option Card for Electric Actuators Standard Optically Isolated RS485 Modbus
PCC-III - Input / Output 18 Input / Outputs Standard! With Option Cards, Up to: 15 Analog Inputs 6 Analog Outputs 13 120 Vac Discrete Inputs Partial List of Option Card Combinations:
PCC-III - Input / Output Option Slot 3 Board CPU Board PCC-III One (1) Pair Triac Outputs, 2A, REAR VIEW "S” Board 24 - 120Vac 120 VAC Power Input Option Slot 1 Option Slot 2 28 25 120 Vac “L” & “N” Commons Option Slot 1 and 2 Board (s) 49 50 51 41 40 42 43 44 45 46 47 48 1U 2U 3U 4U 5U 6U 7U 8U 1L 2L 3L 4L 5L 6L 7L 8L 29 Five (5) Analog Inputs, 4 - 20mAdc, 1 - 5 Vdc "A" Board 30 Five (5) Discrete Inputs, 31 32 120Vac, Opto-Isolated 33 Option Slot 3 Three (3) Isolated Analog Inputs, 4 - 20mAdc, 1 - 5 Vdc "B" Board Two (2) Relay Outputs, Three (3) Analog Inputs 4 - 20mAdc, 1 - 5 Vdc Two (2) Analog Outputs, 4 - 20mAdc, 750 Ohm "F" Board 2 1 3 4 5 6 7 8 9 10 11 12 14 15 16 13 17 18 19 20 21 22 23 24 26 27 41 40 42 43 44 45 46 47 48 120 Vac 8 Amps. Max Isolated RS 485; Two (2) Pair Triac Outputs, 2A, 24 - 120Vac Two (2) Analog Inputs Pot, 4 - 20mAdc, 1 - 5 Vdc "G" Board Four (4) Discrete Outputs, 24Vdc, 200mA; Two (2) Analog Outputs, Two (2) Relay Outputs, 120 Vac, 8 Amps. Max Four (4) Discrete Inputs, 120Vac, Opto-Isolated "J" Board 4 - 20mAdc, 750 Ohm; Five (5) Analog Inputs, 4 - 20mAdc, 1 - 5Vdc CPU Board
English Used For Operation & Configuration... PCC-III - Configuration English Used For Operation & Configuration... Intuitive, Easy to configure “Soft Wired” Blockware Flexible Configuration Methods No Cost - Front Panel Edit Menus Low Cost - PC3_Edit™ Spreadsheet Full Featured - PC3_Draw ™ CAD RS232 Up/Download to Laptops
English Used For Operation & Configuration… PCC-III - Front Panel Editing English Used For Operation & Configuration… Edit Displays Edit Display Indicators Edit keys
PCC-III - Front Panel Edit Menus HI PSI ALM SP LO PSI ALM SP HI LEVEL ALM SP LO LEVEL ALM SP PSI GAIN PSI REPEAT/MIN LEVEL GAIN LEVEL REPEAT/MIN QUICK Menu: COPY PRIMARY TO BACKUP COPY BACKUP TO PRIMARY ERASE PRIMARY COMPARE MEMORIES REMAINING MEMORY REPORT CONFIG. NAME EPROM VER. MEMORY Menu: MAIN Menu: QUICK MENU EXAMINE BLOCK FIND FUNCTION FIND USAGE FORCE BLOCK UN-FORCE A BLOCK UN-FORCE ALL BLOCKS DISPLAY SCAN TIME EDIT QUICK MENU BLOCK TIMING UTILITIES SUB-MENU ALL S/M or (EXIT S/M) A0 b0c1 AUTO or (S/M) A0 b0c2 AUTO or (S/M) SERVICE MANUAL Menu: (ENTER S/M) OR (EXIT S/M) ENTER PASSWORD SECURE CONTROLLER TIMEOUT CHANGE OPERATOR PASSWORD CHANGE TECHNICIAN PASSWORD PASSWORD Menu: PASSWORD MENU ENTER THE BLOCK NUMBER... Bxx FUNCTION TYPE Bxx IO1 DESCRIPTION Bxx IO2 DESCRIPTION . Bxx P01 DESCRIPTION Bxx P02 DESCRIPTION EDIT A BLOCK Menu: EDIT A BLOCK MEMORY MENU UTILITIES MENU CALIBRATE I/O BOARD O INPUTS (BOARD 1 INPUTS) (BOARD 2 INPUTS) BOARD O OUTPUTS (BOARD 1 OUTPUTS) (BOARD 2 OUTPUTS) CALIBRATION Menu: COM MENU COM PORT ADDRESS BAUD PARITY RTU/ASCII +/- DATA TIME OUT TEST CABLE COM PORT Menu:
PCC-III - Front Door Removed REMOVE ONE SCREW TO TAKE AWAY FRONT PANEL RS232 BLOCKWARE DOWNLOAD PORT BACKUP MEMORY WRITE PROTECT JUMPER FRONT PANEL CABLE CONNECTOR BACKUP MEMORY MODULE
PCC-III - PC3_Edit ™ Spreadsheet
PCC-III - PC3_Edit ™ Spreadsheet
Blockware CAD PCC-III Visio™ PC3_Draw Allows PCC-III to be configured using a library of block templates with simple “drag” & “drop” mouse operations
Oxygen Analyzer Logic
Efficiency Logic
Easy Commissioning with “Learn” Mode... Controllers “Learn” Fuel-Air ratios Fuel and Air controllers are placed in Manual Burner is adjusted for optimum “low fire” “Store” button is pressed Air Flow SP, Oxygen SP, FD and FGR damper curve points automatically calculated and entered. Process is repeated for up to 10 more load points No calculating or entering of numeric data “Edit” points by re-Learning or via Edit Menu Separate Sets of Curves for Gas and Oil
Tools for Commissioning Front Panel Edit Keys Allow Commissioning without laptops or handheld devices “Quick Menus” for rapid editing of tuning constants, alarm setpoints, and key parameters “Last Parameter” selection Optional Password Protection with Time-out Copy between Primary and Backup Memories “Examine”, “Block Force” and, “Service Manual” Troubleshooting Modes Laptop Commissioning with PC3_Edit ™ or PC3_Draw
Lowest Installed Cost Shallow case allows smaller enclosure Weather / Rain Proof case avoids glass doors No need for external isolation relays Built in 215mA transmitter power supply Largest quantity of I/O in a single enclosure “Examine”, “Block Force” and “Learn” modes for efficient commissioning Free project proven combustion solutions 30 years of combustion experience to ensure a smooth project
Summary CB Oxygen Trim From Preferred.. Simple commissioning Simplified approach to calibration Easy calibration Learn Mode Low Cost & Field Proven. 10 year old sensor Thousands of PCC Controllers installed.
Preferred Utilities Manufacturing Corp For further information, contact... Preferred Utilities Manufacturing Corporation 31-35 South St. • Danbury • CT T: (203) 743-6741 • F: (203) 798-7313 www.preferred-mfg.com