PIPE TESTING www.concrete-pipe.org.

Slides:



Advertisements
Similar presentations
PETE 411 Well Drilling Lesson 17 Casing Design.
Advertisements

Chp12- Footings.
Advanced Flexure Design COMPOSITE BEAM THEORY SLIDES
Tests to Verify Low Strength Concrete ACI Georgia Chapter Virgil D. Skipper Seminar June 2009 Robert Jenkins, P. E.
VOBUG Conference August 3 rd, 2010 Nashville, Tennessee Robert LeFevre, P.E. Adam Price, P.E. Tennessee Department of Transportation Structures Division.
Overview Waffle Slab.
PIPE CULVERT By CH. VENKATARAMAIAH.
Chapter 3.1 Storm Drainage Sizing. Building Drain & Sewer  Building Drain —That part of the lowest piping of a drainage system that receives the discharge.
Framing Agriculture Structures
Reinforced Concrete Flexural Members
Materials used for pipes: Sewers are made from: 1- Concrete 2- Reinforced concrete 3- Vitrified clay 4- Asbestos cement 5- Cast iron (lined with cement).
Shear and Diagonal Tension
Masonry Design. 2 MASONRY WALLS CONSTRUCTION TYPE Single Wythe Cavity Prefabricated Barrier Masonry Veneer Masonry Bonded Hollow Wall.
ONE-WAY SLAB. ONE-WAY SLAB Introduction A slab is structural element whose thickness is small compared to its own length and width. Slabs are usually.
Chp.12 Cont. – Examples to design Footings
Wall Form Design Example (Continued)
Structural Collapse Technician Training
CTC 422 Design of Steel Structures
Chapter 3.1 Storm Drainage Sizing. Building Drain & Sewer  Building Drain —That part of the lowest piping of a drainage system that receives the discharge.
Contour and Topo map Applications Profile View (Longitudinal Sections): Roads, Canals, Pipes,… Cross-Sectional View, Roads, Canals, Pipes, Building,…
Introduction: Standard Test Method for Density (unit weight), Yield, and Air Content (Gravimetric) of Concrete –Apparatus –Sample –Procedure ACI Certification.
BEARING OR CRUSHING Bearing Stresses (Compression Perpendicular to the Grain) Allowable stresses for compression perpendicular to the grain are available.
Quality Control Testing
Fluid Statics Lecture - 2.
Footings.
You Should Know Bulletin No. 135 © ACPA All Rights Reserved.
Fluid Statics.
Rock Chute Mike Cox State Conservation Engineer Contractor Certification Training March 2008.
Intro to Concrete 18.0 & 19.0 Class notes.
Folded self- mailer The rules for folded self mailers have not changed…..yet. They are in the Domestic Mail manual and the Quick Service Guide available.
FOOTINGS. FOOTINGS Introduction Footings are structural elements that transmit column or wall loads to the underlying soil below the structure. Footings.
Mailpiece Design Rose Flanagan Director of Mailing Services Transcontinental Direct.
Tulkarem Multipurpose Sport Hall Prepared by: Moatasem Ghanim Abdul-Rahman Alsaabneh Malek Salatneh Supervisor: Dr. Shaker Albitar.
Sampling and Testing Concrete Mixes MATERIAL TESTING LABORATORY
EXAMPLE 9.3 – Part V PCI Bridge Design Manual BULB “T” (BT-72) THREE SPANS, COMPOSITE DECK LRFD SPECIFICATIONS Materials copyrighted by Precast/Prestressed.
Student Book © 2004 Propane Education & Research CouncilPage Performing Gas Distribution System Leak Checks Requirements for vapor distribution.
Two loading Conditions
Reinforcement Information - Code
Practical Design of PT Buildings
PILE FOUNDATIONS UNIT IV.
Industry Standards and Load Ratings of Enclosures
SANKALCHAND PATEL COLLEGE OF ENGINEERING,
Sanitary Engineering Lecture 13
Sanitary Engineering Lecture 10 Revision
PRESSURE VESSEL. 1.Determine the bursting steam pressure of a steel shell with diameter of 10 inches and made of ¼ in thick steel plate. The joint efficiency.
Concrete Box Culverts (CBC)
Framing Agriculture Structures
Basics of Seed Conditioning
Studying Geothermal Heat Pump in Palestine
Coursework guidelines
Chapter : 01 Simple Stresses
Lecture 39 - Design of Two-Way Floor Slab System
Framing Agriculture Structures
Design Factors Collapse Corrected
Direct Design Olander vs. Heger
ACPA QCAST PLANT CERTIFICATION
Casing Design Workshop
Navigating FDOT Specifications and Standards
REPAIR and FINISHING.
American Concrete Pipe Association Short Course School 2014
Precast Concrete Pipe and Box Culvert Equipment Calibration
Pipe Post Installation Inspection Demonstrations
History of Design Methodology
Reinforced Concrete Pipe
ACPA Resources Marketing Tools.
Joints John Kallemeyn.
ACPA 2014 Pipe School – Houston, TX
Building Good Boxes ACPA Spring Short Course School
Chapter 13 Concrete Form Design.
Hurdles - Production
Presentation transcript:

PIPE TESTING www.concrete-pipe.org

Learning Objectives Provide an overview of pipe testing requirements and procedures for ACPA Certification

PIPE TESTING Plant certification manual provides specific detail of requirements

PIPE TESTS External load crushing strength test (Three-Edge Bearing test) Joint shear test Off-center joint test Storm sewer and culvert joint test Water tightness tests

calculated based on laying length of the pipe, not the testing board length

Standard Test Methods For Concrete Pipe, Manhole Sections, Or Tile ASTM C497 Standard Test Methods For Concrete Pipe, Manhole Sections, Or Tile

THREE-EDGE BEARING TESTING Understand what you are doing Understand why you are doing it

SELECTED READING: ASTM C497 - Section entitled External load crushing strength test by the three-edge bearing test method ASTM C76 Tables 1-5

WHY DO WE RUN THE THREE-EDGE BEARING TEST WHY DO WE RUN THE THREE-EDGE BEARING TEST? To determine the strength of our pipe using two different criteria: A. The load to produce a crack with a width of 0.01” B. The ultimate load

D-LOAD Pounds per foot of length per foot of diameter For example: ASTM C76 Class III design D-load to produce a 0.01” crack 1350 D-load to produce the ultimate load 2000

SAMPLE CALCULATIONS FOR 24” DIAMETER x 8’ CLASS III 0.01” load = 1350 (D-load) x 8 ft (length) x 2 ft (diameter) = 21,600 lbs. Ultimate load = 2000 (D-load) x 8’ ft. (length) x 2 ft (diameter) = 32,000 lbs.

Point out critical elements and that they should be straight and stiff to get a more favorable result To your advantage to use max spread of bottom edges 1” – 1 ½”

Load Rate ASTM C497 For Reinforced Concrete Pipe, any rate of load application up to a maximum of 7500 lbf/lineal foot of pipe per minute shall be used up to 75% of the specified design strength, at which time the rate of loading shall be reduced to a maximum uniform rate of 1/3 of the specified design strength of the pipe per minute. www.concrete-pipe.org

Load Rate Calculation Example Test Class III, 24 in. pipe, 8’ long ASTM C76 design strength (0.01”) – ? 21,600 lbs. 75% equals ? 16,200 lbs. 7500 lbf/lineal foot of pipe (8’) per minute equals? 60,000 lbs/min. Seconds? 1,000 lbs/sec to 16,200 lbs Minimum 16 seconds to reach 16,200 lbs. Then 1/3 design strength /min equals? 7,200 lbs/minute maximum rate. Total Time? next 5,400 lbs (5,400/7200/min) * 60 sec/min takes 45 seconds more. Total test at least one minute. Depends on pipe size and class. www.concrete-pipe.org

It’s 3-edges, not 3 points

Should be tested that pipe is set squarely in the machine

ACPA T. E. B. TEST FREQUENCIES PIPE SIZE. CLASS FREQUENCY 12”-15” ACPA T.E.B. TEST FREQUENCIES PIPE SIZE CLASS FREQUENCY 12”-15” Class 5 and below 1/1000 pcs. 18”-36” Class 4 and below 1/800 pcs. 18”-36” Class 5 1/400 pcs. 42”-60” Class 3 and below 1/400 pcs. 42”-60” Class 4 and 5 1/200 pcs. 66” and All classes As required larger by project specs.

ACPA T.E.B. TEST FREQUENCIES Pipe shall be tested to the D-load specified in the ASTM tables for the 0.01-inch crack. Pipe meeting these requirements shall be accepted for use. ACPA requires: one piece, per size and class produced, shall be tested to the ultimate D-load at least one per year.

JOINT SHEAR TEST SPECIFIED IN ASTM C497 SANITARY CERTIFICATION ONLY

SANITARY

JOINT SHEAR TEST REQUIREMENTS 4000 lbs/ft of pipe diameter including the weight of the pipe.

WHAT IS A PASSING TEST? Load Joint to 4000 lbs/ft Crack Width less than 0.01” after the load is released.

Example of 1 method

Block must be= 1” from edge of each side of the pipe Block must be= 1” from edge of each side of the pipe. Can use spacer to achieve this. Otherwise, the top instead of bottom will break

DOCUMENTATION A proof of design test for the lowest class of each pipe size and joint style should be retained on file as a permanent record. Expect to run a joint shear test during the audit (sanitary) unless done at another company plant (must be certified). Note the Appendix here that shows Auditor Requirements

OFF CENTER JOINT TEST REQUIREMENTS VACUUM or HYDROSTATIC or LOW PRESSURE AIR Proof of design test on file. All pipe sizes and joint designs.

SANITARY

OFF CENTER JOINT TEST Test must be run during the audit (sanitary)unless testing performed at another company plant that is certified.

STORM SEWER AND CULVERT JOINT TEST REQUIREMENTS VACUUM, HYDROSTATIC OR AIR PROOF OF DESIGN TESTS FOR ALL GASKETED PIPE SIZES AND JOINT DESIGNS

Defined in 443

WATER TIGHTNESS TESTS In-plant quality control tests 12”-36” pipe vacuum test 12”-24” pipe air test 12”-36” pipe hydrostatic test 42” and larger pipe and manhole hydrostatic or vacuum test

ACPA PIPE PLANT CERTIFICATION Requires 100% plant testing 12”-36” Sanitary Sewer Pipe 12”-36” Vacuum Test 12”-24” Air Test 12”-36” Hydrostatic Test

12” - 36” VACUUM TEST Found in Appendix A of QCAST Certification Manual Starting vacuum is 7” Hg

X-tech produces digital monometer

12” - 24” AIR TEST Found in Appendix A of Certification Manual Starting pressure 3.5 psi

12” - 24” AIR TEST Found in Appendix A of Certification Manual Starting pressure 3.5 psi – Drop of 0.054 psi (1-1/2” water or ½” manometer oil)

12” - 36” HYDROSTATIC (Water) 100% OF SANITARY PIPE (Option - air or vacuum) 13 psi FOR 2 1/2 MINUTES NO VISIBLE LEAKAGE

42” AND LARGER HYDROSTATIC or VACUUM TEST ACPA QCAST certification manual Hydrostatic test - 13 psi for 2-1/2 minutes with no visible leakage Vacuum test per table 1/100 minimum of two 36” must test 100% and 42” only 2, why? Because at some point the wall is thick enough, and ACPA has drawn the line at 42”