Lesson 24 Appendix F Outside Air Calculation

Slides:



Advertisements
Similar presentations
Heating, Ventilating, and Air-Conditioning
Advertisements

Commercial Mechanical Requirements
100% Outside Air and Dehumidification Management
Heating, Ventilating, and Air-Conditioning (HVAC)
The Role of Controls for Indoor Air Quality Kent W. Peterson, PE, Fellow ASHRAE P2S Engineering, Inc. Mid Columbia ASHRAE Chapter.
Mechanical Plan Review. Review Plan Package Use Group/Occupancy Correct Code Reference/Conformance Revisions Mechanical Plans/Spec Books Structural Plans.
Heating and Air Conditioning I
Introducing the Biggest Breakthrough in Ventilation Since… Fresh Air…
Local Exhaust Hoods. 2 Introduction:  Designed to capture and remove harmful emissions from various processes prior to their escape into the workplace.
Local Exhaust Fans. Biological Contaminates Moisture Combustion gases - If not burned properly can intro. CO. Gas cooktops Gas ovens Furnace Gas Hot.
The House as a System 1. Air Temperature and Water Vapor.
Brett Graham Habegger Corporation Midwest Regional Sustainability Summit May 1, 2015.
Active beams versus VAV with Reheat Analysis of May 2013 ASHRAE Journal article Ken Loudermilk Vice President, Technology & Developement.
Welcome to S&P USA & the 2012 International Residential and Mechanical Code for Ventilation.
Ventilation for Confined Spaces requires ventilation as follows: An employee may not enter the space until the forced air ventilation has eliminated.
Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By Klas C. Haglid, P.E., R.A., CEM 1.
AIR QUANTITY REQUIRED TO TRANSFER HEAT IN A FORCED AIR SYSTEM In all four mechanical systems considered, the transfer of heat, either by taking it out.
Important variables Water: Air: Conversion:
HVACR416 - Design IAQ / Ventilation / Pathways. Ventilation Most air handling units distribute a mix of outdoor air and re-circulated indoor air. Some.
Ray & Joan Kroc Corps Community Center Mathias Kehoe | Mechanical Option April 09, 2012.
HVACR416 - Design Heat Loss / Heat Gain Part 1. Why? The primary function of Air Conditioning is to maintain conditions that are… o Conductive to human.
1 Stanley A. Mumma, Ph.D., P.E. Prof. Emeritus, Architectural Engineering Penn State University, Univ. Park, PA Web:
Air quality made simple A Balanced Approach Whole House Ventilation and IAQ Airflow Control Make-up Air Solutions Application by Geographic Region.
Energy Cost Budget Highlights Jason Glazer, PE GARD Analytics Arlington Heights, Illinois Energy Cost.
Objectives Propose residential system related final project –Compare VAV systems with DOAS systems.
Day 1 Part 4 Technician’s Guide & Workbook for Home Evaluation and Performance Improvement.
Part 15 Technician’s Guide & Workbook for Duct Diagnostics and Repair.
HCB 3-Chap 19A: All-Air Systems_Single Zone 1 Chapter 19A: ALL-AIR SYSTEMS: SINGLE ZONE AND SINGLE DUCT Agami Reddy (July 2016) 1)Introduction and common.
Free Air Cooling for Data Centres
Maria’s Restaurant Chapter 1 Section 1
Maria’s Restaurant Chapter 2 Section 6
Maria’s Restaurant Chapter 2 Section 9
Maria’s Restaurant Lesson 20 Appendix B Zone 2 Manual N Loads
Maria’s Restaurant Lesson 18 Appendix A Zone 2 Equipment Loads
Revoir titre.
Maria’s Restaurant Lesson 21 Appendix C Duct Design
Maria’s Restaurant Lesson 17 Appendix A Zone 1 Equipment Loads
Maria’s Restaurant Appendix A Section 16 HVAC Building Loads
Maria’s Restaurant Chapter 1 Section 4
Maria’s Restaurant Chapter 1 Section 3
Maria’s Restaurant Chapter 3 Section 13
Maria’s Restaurant Chapter 4 Section 15
NAFA Guide To Air Filtration
Lesson 24 Appendix F Outside Air Calculation
RESIDENTIAL HVAC (HEAT LOSS & GAIN)
Maria’s Restaurant Chapter 1 Section 2
Lesson 23 Appendix C Exhaust Calculation
Maria’s Restaurant Chapter 2 Section 8
By Klas C. Haglid, P.E., R.A., CEM
Munters DOAS, Chilled Beams and VRV
Munters DOAS and Chilled Beams
Cheryl Hughes Regional Sales Manager October 6, 2015
HCB 3-Chap 19A: All-Air Systems_Single Zone
Maria’s Restaurant Chapter 4 Section 14
Variable Refrigerant Volume
Technician’s Guide and Workbook for Zoning Section 3: Single Zone Airflow Balancing and Thermostat Location.
Flip The Long House Let’s imagine the Long house example in Manual J has undergone a house flipping/energy savings update. The insulation was increased,
Zoning Load Calculations
Manual D Duct Sizes Room Cooling CFM % Total CFM Heating CFM Kitchen GR Dining Bed Bed 3.
Zoning Methods There are an unlimited number of ways to zone a home! Popular ways include: More than one single zone HVAC system. Zone damper systems.
Mandatory Design Requirements
FBE03: Building Construction & Science
Objective Revie the Cooling Cycle Learn about air distribution systems
Maria’s Restaurant Chapter 1 Section 3
Maria’s Restaurant Chapter 2 Section 9
Maria’s Restaurant Lesson 22 Appendix C Zone 2 Duct Design
Maria’s Restaurant Lesson 20 Appendix B Zone 2 Manual N Loads
Maria’s Restaurant Chapter 2 Section 8
Maria’s Restaurant Chapter 1 Section 2
Presentation transcript:

Lesson 24 Appendix F Outside Air Calculation

Maria’s Restaurant Maria’s

Maria’s Restaurant Design (Staff: Maria & 6 Employees each shift. Glass Store Front and front door) C1 R1 F1 Woman’s Restroom 1 handicap 1 standard Men’s Restroom 1 handicap 1 urinal S3 Shelv.. R3 DW Bar 12 X 10 Seating 12 Counter C6 Bar S2 B2 Ice R4 Shelving/Storage 25 ft. Shelv. B1 C7 C2 Fry S1 Restaurant 33 X 15, 11 X 4 & 11 X 6 Seating 58 CT/O C3 SP SK H1 R2 F2 WH S1 66 ft. Kitchen Area = 533 Sqft Bar Area = 180 Sqft Woman Rest Room = 110 Sqft Men Rest Room = 99 Sqft Bar Area = 180 Sqft Entry Area = 120 Sqft Dinning Area = 605 Sqft

Restaurant Exhaust and Outside Air For Maria’s Restaurant, the Restaurant and Bar it Was decided that Class 2 air from the restaurant area would be used to condition the bathroom areas. Thus, a larger than required exhaust system for the bathrooms was used.

Operational Outside Air Minimums Air Classification Definitions from ASHRAE 62.1 Class 1: Air with low contaminant concentration, low sensory-irritation intensity, and inoffensive odor. (May be Recirculated to any space.) Class 2: Air with moderate contaminant concentration, mild sensory-irritation intensity, or mildly offensive odors. Class 2 air also includes air that is not necessarily harmful or objectionable but that is inappropriate for transfer or recirculation to spaces used for different purposes. (Can be recirculated to any space except a class 1 space.)

Operational Outside Air Minimums Air Classification Definitions from ASHRAE 62 Class 3: Air with significant contaminant concentration, significant sensory-irritation intensity, or offensive odor. (Can only be recirculated in space of origin.) Class 4: Air with highly objectionable fumes or gases or with potentially dangerous particles, bioaerosols, or gases, at concentrations high enough to be considered harmful. (Can not be recirculated in space of origin or transferred.)

ASHRAE 62.1 Outside Air Minimums Class 2 Air For a Restaurant or Kitchen 7.5 CFM per person Air Rate RA CFM/Ft2: 0.12 for Kitchens 0.18 for Restaurants & Bars

ASHRAE 62.1 Outside Air Minimums 2015 IMC “403.2.2 Transfer air. Except where recirculation from such spaces is prohibited by Table 403.3.1.1, air Transferred from occupiable spaces is not prohibited from serving as makeup air for required exhaust systems in such spaces as kitchens, baths, toilet rooms, elevators and smoking lounges. The amount of transfer air and exhaust air shall be sufficient to provide the flow rates as specified in Section 403.3.1.1.” Class 2 Air For a Restaurant or Kitchen 7.5 CFM per person Air Rate RA CFM/Ft2: 0.12 for Kitchens 0.18 for Restaurants & Bars

2015 IMC Woman’s Room 110 ft2 X 1 CFM = 110 CFM IMC 403.3.1.1Table: 1 ft3 of air per square foot: Woman’s Room 110 ft2 X 1 CFM = 110 CFM Men’s Room 99 ft2 X 1 CFM = 99 CFM Note: As per design values, 200 CFM per bathroom for ventilation and comfort cooling/heating is transferred from the restaurant area through Jump Ducts.

10 ACH (Required by Some Codes) Woman’s Room 110 ft2 X 8 ft. X 10 = 8,800 CFH 8,800 ÷ 60 = 147 CFM Men’s Room 99 ft.2 X 8ft. X 10 = 7,920 CFH 7,920 ÷ 60 = 132 CFM Note: As per design values, 250 CFM per bathroom for ventilation and comfort cooling/heating is transferred from the restaurant area through Jump Ducts.

ASHRAE 62.1 Outside Air Minimums Local Code CFM Outside Air Requirement: Restaurant & Bar Areas Zone 1 Fresh Air Requirement 74 People x 7.5 = 555 CFM 1,117 ft2 Rest. x 0.12 = 134 CFM Total Fresh Air CFM Required = 689 CFM Kitchen Area Zone 2 533 ft2 kitchen x 0.18 = 96 CFM Fresh Air Requirement 3 People x 7.5 = 23 CFM Total Fresh Air CFM Required = 119 CFM

ASHRAE 62.1 Outside Air Minimums Local Code CFM Outside Air Requirement: Restaurant & Bar Areas Zone 1 Fresh Air Requirement 74 People x 7.5 = 555 CFM 1,117 ft2 Rest. x 0.12 = 134 CFM Total Fresh Air CFM Required = 689 CFM Kitchen Area Zone 2 533 ft2 kitchen x 0.18 = 96 CFM Fresh Air Requirement 3 People x 7.5 = 23 CFM Total Fresh Air CFM Required = 119 CFM

ASHRAE 62.1 Outside Air Minimums Local Code CFM Outside Air Requirement: Restaurant & Bar Areas Zone 1 Total Fresh Air CFM Required = 689 CFM Kitchen Area Zone 2 Total Fresh Air CFM Required = 119 CFM Outside air required for Zone 1 the restaurant side of the building is 689 CFM: Thus 689 CFM must be brought into Zone 1 at all times. Note: (119 CFM into Zone 2)

Operational Outside Air Minimums Outside air required for the restaurant side of the building is 689 CFM: Thus, 689 CFM will be brought In at all times. 500 CFM will be exhausted through the two restrooms. That will mean an extra 189 CFM of air in the restaurant area. This extra air will provide a slightly positive pressure so, all air leakage from the Dinning area is into the kitchen or bathroom areas. Since the restaurant area air is Class 2 this is allowable.

Operational Outside Air Minimums Air Classification Definitions from ASHRAE 62 Food & Beverage Service Air Classification Dining Rooms 2 Cafeteria, fast food Bars, cocktail lounges Kitchens (cooking)

Kitchen Exhaust Requirements Typical Type 1 Exhaust Hood With Perforated Perimeter Supply (11.5 ft. linear length 3,450 CFM hood with 1,150 CFM untempered ASHRAE 62 Class 1 makeup air)

Kitchen Exhaust Total Cooking Hood: 3,450 CFM Dish washer Hood: 600 CFM Total: 4,050 CFM

Operational Outside Air Minimums Outside air required for the kitchen side of the building by ASHRAE 62.1 is 119 CFM: Thus, 119 CFM must be brought in at all times. 4,050 CFM will be exhausted through the two kitchen exhaust hoods. That will leave a negative 3,931 CFM of air if only 119 CFM is brought in from the outside. Thus, an additional 3,931 CFM of air will need to be brought into the kitchen if it is to remain at a neutral pressure with respect to the outside. (slightly positive to the outside is preferable)

Kitchen Exhaust & OA Sketch AIR In 1,150 CFM AIR In 600 CFM AIR In Setting 1: 1,900 CFM Setting 2: 100 CFM EX. AIR #2 Package Heat Pump ERV EX AIR OUT 500 CFM EX. AIR AIR In 500 CFM EX 2 Supply Air 3,200 CFM Return Air Setting 1: 1,300 CFM Setting 2: 3,100 CFM 2 Bathrooms Airflow ½ each EX 1 EX 2 AIR 600 CFM EX AIR Speed/Setting 1: 3,450 CFM Speed/Setting 2: 1,650 CFM Kitchen Area (+0.001” IWC) Bar & Dining Area (+0.004” IWC)

Kitchen Exhaust Total The Total CFM Requiring heating and cooling is Lowered to: 4,050 – 1,400 = 2,650 Cooking Hood: 3,450 CFM Dish washer Hood: 600 CFM Total: 4,050 CFM Bring 1,500 CFM into the hood by a separate outside air fan. Bring 500 CFM into kitchen area from Bathroom ERV.

ERV Savings for Cooling An ERV will be used as the exhaust fan in the two bathrooms. The 500 CFM of outside air will be provided to open area over the rear entrance door. This will save about 2/3 ton of cooling requirement for the required ventilation air. Note: tonnage savings based on plugging the difference into Manual N calculations for comparison.

Dining & Bar Exhaust & OA Sketch AIR In 500 CFM AIR In 689 CFM # 1 Package Heat Pump ERV EXHAUST AIR 500 CFM EXHAUST AIR 500 CFM Supply Air 2,400 CFM 2 Bathrooms Airflow ½ each AIR In 500 CFM Return Air 1,711 CFM Kitchen Area (+0.001” IWC) Bar & Dining Area (+0.004” IWC)

ERV

500 CFM IN (BLUE) & 500 CFM OUT (Brown) Blower Wheel Fresh Air To Building Building Air To Outside Separated Air Paths Through Heat Transfer Media Building Air To Outside Outside Air To Building Blower Wheel Filter MERV 8 FILTER

ERV TRANSFER EFFECIENCY 500 CFM WINTER TOTAL = 70%

ERV TRANSFER EFFECIENCY 500 CFM SUMMER TOTAL = 60%

ERV TRANSFER EFFECIENCY 500 CFM SUMMER SENSIBLE = 75%

ERV LOAD IMPLICATIONS Winter 500 CFM × 0.70 = 350 CFM 500 – 350 = 150 CFM Thus, there is an additional 150 CFM of outside air being brought in resulting in slightly less than a 4% increase in total load or 4,290 BTUH

ERV LOAD IMPLICATIONS Summer Total Load 500 CFM × 0.60 = 300 CFM 500 – 300 = 200 CFM Thus, there is an additional 200 CFM of outside air being brought in resulting in slightly less than a 3% increase in total load or 3,268 BTUH

Makeup Air Fan For Type I Exhaust The Type I hood selected is designed to have a portion of the outside air come directly into the hood untempered under full operational load. The amount in the design is 1,150 CFM. This will save a little under 1.5 tons of cooling requirement for the required ventilation air.

Further Savings: Two Speed Type I Exhaust Hood The Type I hood selected is designed with an automated control that senses usage. When there is no cooking station usage, hood fan lowers it’s speed so only 1,650 CFM are being exhausted by the hood when the cooking equipment is not being used. The hood makeup fan’s 1,150 CFM plus the 500 CFM from the ERV then meets the total hood requirement of 1,650 CFM (1,150 + 500). This will allow the HVAC system to save over 2 tons of cooling load for the required ventilation air, during off peak operation.

Field Notes On many occasions those who know the current outside air code requirements will try to enforce them on existing buildings. Technicians need to find out what the code was when the building was built because the equipment was designed to meet that requirement. Often the equipment is sized so it can not be adjusted to meet a new code requirement. The good news is, if the original code requirement is known, that is what must be met. In simple old fashioned terms: one horse can not pull a two horse load up a hill.