POWER SYSTEM COMMISSIONING AND MAINTENANCE PRACTICE

Slides:



Advertisements
Similar presentations
Introduction to Switchgear
Advertisements

Submitted by: Name:Rajendra Kumar Choudhury Branch:Electrical Engg.
SYMMETRICAL COMPONENETS OF POWER SYSTEM
GENERATOR PROTECTION.
PROTECTION scheme for bus bar / feeder
CIGRE 7-10 September 2009, Moscow
Universal Relay Family
Power System Analysis/ Power System 1 EEE 4113/ EEE 3131
Material used:  Tin  Lead  Zinc  Silver  Antimony  Copper  Aluminum.
MEASUREMENT DEVICES OUTLINE Multimeters Analog Multimeters
Generator Protection. Amount of Protection Rated power of the generator Ratio of its capacity to the total capacity of the system Configuration of the.
Problem Solving Part 2 Resonance.
Chapter 7 SYSTEM PROTECTION
POWER SYSTEM PROTECTION
OVER CURRENT RELAY The relay has two settings. These are the time setting and the plug setting. The time setting decides the operating time of the relay.
Connections of a CT and a PT to supply, load and relay.
Electrical Distribution Training
TESTING AND COMMISIONING
Need for protection Power system must be kept in operation continuously without major breakdowns This can be achieved in two ways: 1.Implement a system.
Queensland University of Technology CRICOS No J Protection of distributed generation connected networks with coordination of overcurrent relays.
Transformer Protection Over-current protection in the form of fuses may be the only protection provided to a small 100 kVA, 11 kV/440 V distribution transformer.
Announcements Read Chapters 10 and 11
Introduction to switchgears
Protection of Power Systems
Stepper Motor – Types, Advantages And Applications
Protection of Power Systems
DC Machine & Transformer
 The figure below shows a protection system for a transmission line, consisting of a CT, PT, a relay and its associated circuit breaker.
Power System Protective Relaying-Part One
Protection of Power Systems
Part Three – Relay Input Sources
III ALTERNATING CURRENT Electricity is generated, transmitted, and used in the form of three-phase alternating current (AC). The current strength of AC.
Power System Protection 1. Contents Contents Introduction Functions of Equipment Protection Functions of Protective Relays Required Information for Protective.
 Energised by two quantities(voltage and current)  Φ1 and Φ2 set by voltage and current  Eddy currents induced in the disc due to two fluxes  Interaction.
Static Relays contains electronic circuitry (Diodes, transistors, zener diodes, thyristors,logic gates …etc) ICs are widely being used in place of transistors.
SCHOOL OF ENGINEERING Introduction to Electrical and Electronic Engineering Part 2 Pr. Nazim Mir-Nasiri and Pr. Alexander Ruderman.
Protection and Relay Schemes
Introduction High Voltage!!.
TRANSFORMERS.
Sub Station.
Announcements Please read Chapters 9, 10 and 11 HW 8 quiz today
Protection of Power Systems
Grounding And Safety Techniques Ms. Tahoora Qureshi, Asst. Professor
Fundamentals of Electric Circuits Chapter 5
AUTOMATIC STREET LIGHT CONTROL USING LDR
Percentage Differential Protection Prepared by Viren B Pandya
Protection of Power Systems
Smitty’s Two Minute Drill Overcurrent Protection
Series Capacitor Compensation
ELECTRICAL INSTALLATION AND MAINTENANCE (EIM) 5 INSTALL ELECTRICAL PROTECTIVE DEVICES FOR DISTRIBUTION, POWER, LIGHTING, AUXILIARY, LIGHTNING PROTECTION.
PLC Hardware Components.
Chapter 7 System Protection
Electrical Installation Practice 2
Electric braking Powerpoint presentation by:- Poonam sharma
Protective Relaying Conference
UNIT II APPARATUS PROTECTION.
A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Power Plants By: Stephanie Mercer.
ELECTRICAL POWER-II Electrical engineering sixth semester
Presented to: IEEE-IAS (Atlanta) Presented by: Michael D. Seal, P.E.
Distance Protection: Why Have We Started With a Circle, Does It Matter, and What Else Is Out There? Edmund O. Schweitzer, III and Bogdan Kasztenny Schweitzer.
Agenda Introduction of Protective Relays
POWER SYSTEM ENGINEERING
EET 323 – Electrical System Design Lecture 9: Grounding
Power System Protective Relaying-Part One
POWER SYSTEM COMMISSIONING AND MAINTENANCE PRACTICE
Chapter 4. Time Response I may not have gone where I intended to go, but I think I have ended up where I needed to be. Pusan National University Intelligent.
Substation Equipment's
Braking of Three Phase IM
Principles of Lifting Machines
Presentation transcript:

POWER SYSTEM COMMISSIONING AND MAINTENANCE PRACTICE DET310/3 CHAPTER 10 PROTECTIVE RELAY

INTRODUCTION Power systems and their components need protection from natural hazards as well as human error. Lightning, wind, ice, switching surges, resonance, trees, animals and humans are some of the causes of faults. These faults produce overcurrents and/or overvoltages at various locations in a power system and must be cleared before they cause before they damage any machines, transformers, lines etc. This is generally accomplished by isolating the faulted portion (as small a portion as possible) of the system so that the remainder of the system can serve without interruption.

-continue: In low-voltage distribution systems, lightning (surge) arresters are used for over-voltage protection and fuses and slow-acting circuit breakers are employed for over-current protection. In high-voltage transmission systems reliable sensors, fast-acting relays and circuit breakers are needed to clear the fault quickly so that the stability of the remaining system is secured. In short, the protection, stability and security of a power system are affected by the ability of the protection devices to detect and respond to system abnormalities like over-voltages and over-currents

Protection Components Protection systems have three basic components: Sensors (transducers, detectors) to detect system abnormalities Relays (activators) to provide signals to activate the protection devices. Circuit breakers (interrupters) to open (disconnect) the circuits.

Figure 5.0

What is a Relay? A relay is a logical element which process the inputs (mostly voltages and currents) from the system and issues a trip decision if a fault within its jurisdiction is detected. Inputs to a relay are: - Current from a current transformer. - Voltage from a voltage transformer

CLASSIFICATIONS OF RELAYS Relays may be classified according to the technology used: a. electromechanical b. static c. digital d. numerical

Protection Techiques The most common protection techniques can be classified into 3 categories: a) Over-current/earth fault b) Differential protection c) Distance protection

Overcurrent and earth-fault protection A protective relay which operates when the load current exceeds a preset value is called an overcurrent relay. The value of preset current above which the relay operates is known as pick up value. An overcurrent relay is used for protection of distribution lines, large motors and power equipment. An overcurrent scheme may include one or more overcurrent relays. A wide variety of time-current characteristics is available for overcurrent relays

Non-Directional Overcurrent Protection When the current in a system exceeds a predetermined value, it indicates the presence of a fault. Relaying decision is based solely on the magnitude of current. Used in radial distribution systems. Overcurrent relaying and fuse protection uses this principle.

Directional Overcurrent Protection Uses both magnitude of current and phase angle information for decision making. Used in radial distribution systems with source at both ends.

Type of Overcurrent Relay can be categorized as below: Definite time overcurrent relays This type of relay operates after a predetermined time when the current exceeds its pick-up value. The operating time is constant, irrespective of the magnitude of the current above the pick-up value. Operating time is independent of current Relay closest to fault has shortest operating time. Problem Longest operating time is at the source where fault level is highest

Instantaneous Overcurrent Relay This type of relay operates in definite time when the current exceeds its pick up value. The operating time is constant, irrespective of the magnitude of current. Current settings chosen so that relay closest to fault operates. Problem relies on there being a difference in fault level between the two relay locations. Cannot discriminate if IF1= IF2

Generally, it can be divided into three (3) categories IDMT overcurrent relay Generally, it can be divided into three (3) categories Standard Inverse (SI) Very Inverse-time Overcurrent (VI) Extremely Inverse-time Overcurrent relay (EI) Characteristics of IDMT relay Current setting via plug bridge or PMS Time multiplier setting via disc movement or TMS Electromechanical relay only have single characteristics curve while numerical and electronics have multiple type of curve.

IDMT Electromechanical relay

Ir = (I/Is), where Is = relay setting current TMS = Time multiplier Setting TD = Time Dial setting

The tripping characteristics for different TMS settings using the SI curve

RELAY CURRENT SETTING An overcurrent relay has a minimum operating current, known as the current setting of the relay. The current setting must be chosen so that the relay does not operate for the maximum load current in the circuit being protected, but does operate for a current equal or greater to the minimum expected fault current.

Plug Setting Multiplier It is the ratio of fault current in the relay coil to the pick – up current.

Time Multiplier Setting A relay is generally provided with control to adjust the time of operation. This adjustment is known as time setting multiplier the time setting dial is calibrated from 0 to 1 in steps 0.1. These figures are multipliers to be used to convert the time derived from time/p.s.m curve into the actual operating time. The actual time of operation is calculated by multiplying the time setting multiplier with the time obtained from time/ p.s.m curve of the relay.

Relay Operating Time In order to calculate the actual relay operating time, the following things must be known: (a) Time/ p.s.m curve (b) Current setting (c) Time setting (d) Fault current (e) Current transformer ratio

Example: Problem 1: – Determine the time of operation of a 5-ampere, 3-second over current relay having a current setting of 125% and a time setting, multiplier of 0.6 connected to supply circuit through a 400/5 current transformer when the circuit carries a fault current of 4000A. The time of operation is 3.5 for a P.S.M value of 8. Solution Rated secondary current of CT = 5 A Pickup current = 5 x 1.25 = 6.25 A Fault current in relay coil = 4000 x 5/400 = 50 A Plug-setting multiplier (P.S.M.) = 50/6.25 = 8 Given when P.S.M is 8 time operation is 3.5 Sec. Actual relay operating time = 3.5 x Time-setting = 3.5 x 0.6 = 2.1 seconds

Testing and Commissioning of IDMTL Typical secondary injection commissioning tests for this type of relay consists of the following: A check should be made of the minimum operating current with the plug inserted into the nominal setting (i.e 100% plug setting) and the TMS is set to 1. The injected current is incrementally increased, and the disc must not creeping at current less than 100%.

Testing and Commissioning of IDMTL Full travel of disc must occur, and relay flag must have dropped with an injected current less than 130% of setting. The current should be then incrementally reduced to enable the disc to reset, which occur at a current less than 70% of the pick-up current

Testing and Commissioning of IDMTL(continue)- A timing tests is required with the PMS at 130% setting and TMS equal to 1. This is usually carried out with a stop watch. The tests is carried out with setting of 200% and 300% of PMS. The data obtained is then compared to calculation using corresponding mathematical formulation. An error of 10% is usually acceptable.

Example: Determine the magnitude of fault current, secondary current and tripping time at 130%, 200% and 300% for a standard inverse relay having a parameters as shown below: PSM = 100%, CT ratio 500/5; TMS= 0.1 Solutions: Fault current: 100% = 500 A; 130 % = 1.3 x 500 A = 650 A 200 % = 2 x 500 A = 1000 A 300 % = 3 x 500 A = 1500 A Secondary Current: 130% = 1.3 x 5 = 6.5 A 200% = 2.0 x 5 = 10 A 300 % = 3.0 x 5 = 15 A

Example (continue)- Tripping time: For Standard Inverse = time, t = At 130 % , t = At 200 %, t = At 300 %, t =

10.4.2 Differential Relay 10.4.2.1 Introduction The graded overcurrent systems previously described though attractively simple in principle, do not meet all the protection requirements of a power system. Application difficulties are encountered for two reasons: 1) satisfactory grading cannot always be arranged for a complex network, 2) the settings may lead to maximum tripping times at points in the system that are too long to prevent excessive disturbances occurring.

10.4.2.1 Introduction (continue)- These problems led to the concept of 'Unit Protection', where by sections of the power system are protected individually as a complete unit without reference to other sections. One form of ‘Unit Protection’ is also known as ‘Differential Protection’, as the principle is to sense the difference in currents between the incoming and outgoing terminals of the unit being protected.

Principle of Operation Differential protection, as its name implies, compares the currents entering and leaving the protected zone and operates when the differential between these currents exceeds pre-determined magnitude. The difference between the currents may be in magnitude or in phase angle or in both. For healthy operation, magnitude and angle differences must be zero. If there is a difference and that difference exceeds some value (setting valued, the relay will operate and associated circuit breaker will trip .

During external Fault, SPILL CURRENT = I1 – I2 = 0

During Internal Fault: Radial line: I2s = 0; SPILL CURRENT = I1S TWO Source feeding: SPILL CURRENT = I1S+I2S

In reality, CTs will subjected to ratio and phase angle error. This will results in spill current when through fault increases.

Spill Current = Where:

BIASED/PERCENTAGE DIFFERENTIAL RELAY Large external fault may cause false operation of simple differential relay. To make the differential relay more stable to external faults and improve relay quality, its respectively to operation was increased by inserting restraining coils. Two restraining (Biasing) coils and one operating are used as shown in figure below. Restraining coils will opposite the operation of operating coil. The relay will operate only when the operating force is higher than restraining force.

PERCENTAGE/BIAS DIFFERENTIAL RELAY Relay trips if operating torque is greater them restraining torque

The relay will be on verge of operation when the operating torque just balances out restraining torque, when: operating torque = restraining torque Or can be written : Where K=Nr/No Thus, the operating characteristics of the relay will be a straight line with a slope of Nr/No (K). SPILL current must be greater than a definite percentage of the through fault current for the relay to operate.

The slope of the relay is customarily expressed as a percentage The slope of the relay is customarily expressed as a percentage. Thus a slope of 0.4 is expressed as 40% slope

PERCENTAGE DIFFERENTIAL RELAY APPLICATION - TRANSFORMER Several consideration Transformer vector group the effects of the variety of earthing and winding arrangements (filtering of zero sequence currents) correction for possible unbalance of signals from current transformers on either side of the windings (ratio correction) the effect of magnetising inrush during initial energisation. the possible occurrence of overfluxing

Transformer vector Group

Transformer vector Group

Example:

Example: Transformer , S=30MVA, 33/11 kV delta star transformer. Calculate the spill current on differential relay during normal operation. Calculate the spill current when interposing CT is included. Determine the stability of relay if percentage restrained torque is set at 30%