A PPARATUS G AS G ROUPS, T EMPERATURE C LASS AND T YPES OF E XPLOSION P ROTECTION (Adapted from:D.T. Hall:Practical Marine Electrical Knowledge)

Slides:



Advertisements
Similar presentations
Regulations (Standards - 29 CFR) Flammable and Combustible liquids
Advertisements

(Adapted from:D.T. Hall:Practical Marine Electrical Knowledge)
Fired And Unfired Pressure Vessels
Murray State University
Electrical Installation
Inspection & Preventive maintenance of breakers
BS7671 Formula and Tips.
Submitted by: Name:Rajendra Kumar Choudhury Branch:Electrical Engg.
Heating Control Devices
» When you have completed this module you will know, what components do, what they physically look like and how they are represented in a circuit diagram.
(Adapted from:D.T. Hall:Practical Marine Electrical Knowledge)
MAIN ELECTRICAL SURVEY ITEMS, GENERATORS AND GOVERNORS,, CIRCUIT BREAKERS, SWITCHBOARDS AND FITTINGS (Adapted from:D.T. Hall:Practical Marine Electrical.
Intrinsic Safety Testing by Gail Nicola, Electrical Engineering Technician Ed Vensko, Electrical Engineering Technician.
1 Module 3 Ignition Control. 2 Terminal Objectives Upon the successful completion of this module, participants will be able to explain the work procedures.
NEW TECHNOLOGY IN MINE SURVEYING AND ITS IMPACT ON SAFETY IN THE UNDERGROUND WORKINGS OF A MINE.
Gas Transmission Pipelines
Week 3 Electrical Circuits and Components. It’s a Radio!
Hazardous Location Standards and the CEC
Internal resistance of battery
Lesson.5: Fuses and Safe Plugs
Why do wires get hot when a current passes through them?
Blabo® Automated Tank Cleaning ExxonMobil 2009 Article Electrical standards Designed for operation in hazardous areas. Constructed for zone 1, and some.
Copyright © Flammable & Combustible Liquids.
Patrick Thornton, SNS/FPE June 9, 2008
Protection against Electric Shock (Note: All the mentioned tables in this course refer to, unless otherwise specified, Low Voltage Electrical Installation.
Chapter One Electrical Design and Component Basics.
Flammable and Combustible Liquids
NFPA 31 Standard for the installation of Oil- Burning Equipment
Flammable and Combustible Liquids Presented by Martina Schmeling Adapted From OSHA.
© BA Electrical Machines - 1 M3000 Ex-motors August 2002 M3000 Low Voltage Motors for Hazardous Areas.
Technological World. Electrical Function An electrical function is the role that a component plays in the control or transformation of electric current.
Electrical Safety in Construction. Objectives In this course, we will discuss the following: Common electrical hazards Standards relating to those hazards.
P2: Electricity Booklet 1 Name: _______________________ Teacher: _______________________ You are reminded for the need to complete all work to the best.
MAINS ELECTRICITY. Specification Electricity Mains electricity understand and identify the hazards of electricity including frayed cables, long cables,
Basic Awareness Training for all Staff
Flammable and Combustible Liquids. Introduction !The two primary hazards associated with flammable and combustible liquids are explosion and fire !Safe.
Need for protection Power system must be kept in operation continuously without major breakdowns This can be achieved in two ways: 1.Implement a system.
IP Circuit symbols © Oxford University Press 2011 Circuit symbols.
Automation and Drives A&D SD SM1, Hr. Mölter /62 Explosionsschutz_En_02_2004.ppt Standard Drives 3.2Classification of gases and vapors in explosion.
The work of CEN/TC 305 Potentially explosive atmospheres-
2 IMPACT - THE FIRE PERMIT = Hot Work Permit 3 Welcome ! This course is linked to the use of IMPACT, so it is assumed that: You know how to use IMPACT.
What is Welding? As Identified by the American Welding Society, a weld is a formed when separate pieces of material are Fused together through the application.
Flammable Liquids Directorate of Training and Education
ELECTRICAL INSTRUMENTS ( service and utilization )
Chapter 3 PHYSICAL INJURY AND CONTROLS 3.2 Electrical Safety
1 ATEX classification air motors, Dagmar Dübbelde ATEX CLASSIFICATION AIR MOTORS.
END BASIC ELECTRICAL THEORY Basic Electricity. 1 THE ATOM AND ITS STRUCTURE.
Hazardous Area Classification 1. Hazard & Its Causes/ Types 2. Hazardous Area Definitions 3. Material Classification 4. Area Classification 5. Prevention.
Electrical Safety.
Hazardous Area Timefiller Pt 2
NONINCENDIVE INSTALLATIONS FOR CLASS I DIV 2 AREAS
PROTECTION AGAINST INDIRECT CONTACT
Hazardous Area Environments
THUM Adapter Impact on Hazardous Area Classification
Practical electricity
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE
CONSTRUCTION BS (BS 4533) K.F. Chan (Mr.) MEBS 6002.
The Electric Circuit.
Electrical Safety Standards
EET 323 – Electrical System Design Lecture 9: Grounding
Flammable & Combustible Liquids
AGENDA INTRODUCTION CELLS AND COMPONENTS PV PERFORMANCE
MAINS ELECTRICITY.
Electrical components and systems
Biosco: MV/LV prefabricated substations IEC Presentation of the standard Safety is a choice.
Risk Management Student Powerpoint
Presentation transcript:

A PPARATUS G AS G ROUPS, T EMPERATURE C LASS AND T YPES OF E XPLOSION P ROTECTION (Adapted from:D.T. Hall:Practical Marine Electrical Knowledge)

A PPARATUS G AS G ROUPS The flammable gases in which explosion protected electrical equipment may have to operate are grouped according to the amount of electrical energy, in the form of an arc, which is needed to ignite the gas.

T EMPERATURE C LASS This defines the maximum surface temperature of the components in the electrical equipment under normal and fault conditions. This maximum surface temperature must not exceed the gas ignition temperature. The temperature class is stated with reference to a maximum ambient temperature of 40° C, should any other reference temperature be adopted, regulations require that this temperature be shown on the equipment.

It is important to note that the apparatus gas grouping and temperature class are not related. For instance, hydrogen requires very little spark energy to ignite, but the surface temperature necessary for ignition is very high (560 °C). The following table relates the temperature class to the maximum surface temperature under fault conditions.

Temperature Class / Maximum surface temperature T1450 °C T2300 °C T3200 °C T4135 °C T5100° C T685° C For example, an electric motor may have a maximum surface temperature of 120 °C and would be classed as T4.

T YPES OF E XPLOSION P ROTECTION There are a number of different constructional techniques employed in preventing electrical equipment causing explosions in hazardous areas. Some techniques, such as flameproof enclosures, have long been established but others, such as intrinsic safety and increased safety, are the result of developments in material and electrical/electronic circuit design. It has been internationally agreed that explosion protected equipment be identified by the symbol "Ex" followed by a letter indicating the type of protection employed.

The following table lists the types of protection: SymbolType of Protection Exdflameproof enclosure Exiintrinsic safety Exeincreased safety Exnnon-sparking Exq powder filled (not applicable to ships) Exo oil immersed (not applicable to ships) Exppressurisation Exsspecial protection

Some equipment may use more than one of these types of protection in its construction. In this case, the primary type of protection is quoted first. For example, an increased safety motor with a flameproof terminal box would be marked Exe d. Equipment may also be marked with a prefix "E" which denotes compliance with European Standards e.g. EExe d.

E XD F LAMEPROOF E NCLOSURE Type 'd' protection, code EExd, uses a flameproof enclosure to contain the electrical apparatus. The internal apparatus may include parts which arc and surfaces which become hot. Gas may be inside the enclosure so it must fulfill three conditions: 1)The enclosure must prevent the flame and hot gases from being transmitted to the external flammable atmosphere. 2)The external surface temperature of the enclosure must remain below the ignition temperature of the surrounding gas under all operating conditions.

3)The transmission of flame and hot gases from a flameproof enclosure is prevented because all joints, such as flanges, shafts and bearings are closely machined to achieve a small gap which is less than a defined maximum. The pressure of an internal explosion is then released through the small gap between machined faces which cools the gas sufficiently to prevent it from igniting any external flammable atmosphere. The maximum permitted gap depends upon three factors: 1)The type of gas with which the apparatus is safe for use. This is indicated by Apparatus Group. 2)The width of the joint (L). 3)The volume of the enclosure (V).

E XI I NTRINSIC S AFETY These are circuits in which no spark nor any thermal effect produced under prescribed test conditions (which include normal operation and specified fault conditions) is capable of causing igni­tion of a given explosive atmosphere. Generally, this means limiting the circuit conditions to less than 30 V and 50 mA. Naturally, this restricts the use of Exi ' protection to low power instrumentation, alarm and communication circuits. The design of the circuit will depend on the type of gas present (gas grouping). In the UK, two grades of intrinsic safety are recognised based on the safety factor of the equipment involved: # Exia the highest category based on a safety factor of 1.5 with two faults on the circuit. # Exib based on a safety factor of 1.5 with one fault on the circuit.

In addition to apparatus in the hazardous area being rated as intrinsically safe, an electrical safety barrier may also be fitted to the circuit. The purpose of such a barrier is to limit voltages and currents in the hazardous area when faults occur on the circuit. A separate barrier is required for each Exi circuit and they must be fitted outside the hazardous area.

A safety (or zener) barrier comprises: 1)A fuse to limit the maximum current through the shunt (zener) diodes. 2)A set of resistors to limit the maximum current into the hazardous area. 3)A set of shunt connected zener diodes to limit the maximum voltage appearing on the circuit within the hazardous area. 4)All components are sealed into a compact package with clearly marked terminals at each end of the barrier.

In the event of a short-circuit on the hazardous area wiring or equipment, the in-line resistors within the barrier will limit the size of fault current while the fuse blows. Two or three zener-resistor combinations are used within a barrier to provide back-up voltage anchors while the fuse is blowing. After clearing a fault, the complete zener barrier must be replaced with an identical unit. No alterations to the original is allowed remember this is a certified Ex safety device.

Cables for intrinsically safe circuits aboard ships should be separated from power cables and the crossing over of such cables should be at 90°. This is to minimise electromagnetic interference from the power cables affecting the intrinsically safe circuits. The metallic cable screens of intrinsically safe circuits should be earthed at the power supply end only to prevent circulating currents within the sheath. Power and intrinsically safe cable runs should be separately identified, i.e. by labels or by using cables with a distinctive colour (typically blue for Exi). (Adapted from:D.T. Hall:Practical Marine Electrical Knowledge)