Introduction to Distribution Systems

Slides:



Advertisements
Similar presentations
“Power Factor” In Transmission System
Advertisements

ENERGY CONVERSION ONE (Course 25741) CHAPTER SIX ……SYNCHRONOUS MOTORS.
Sinusoidal Steady-State Power Calculations
CH5 AC circuit power analysis 5.1 Instantaneous Power 5.2 Average Power 5.3 Effectives values of Current & Voltage 5.4 Apparent Power and Power Factor.
Power Factor Correction Most domestic loads (such as washing machines, air conditioners, and refrigerator) and industrial loads (such as induction motors)
Copyright © 2013 The McGraw-Hill Companies, Inc. Permission required for reproduction or display. 1 Chapter 11 AC Circuit Power Analysis.
Power Engineering Society Chicago Chapter Reactive Power: Sources and Solutions 12 February 2003 David E. Mertz, PE Burns & McDonnell Engineers, Inc.
Measurements &Testing (1)a CSE 323a 1. Grading Scheme 50Semester work 50Lab exam 50Final exam 150Total Course webpage
Power Factor and Power Factor Correction
AC POWER ANALYSIS Tunku Muhammad Nizar Bin Tunku Mansur
Problem Solving Part 2 Resonance.
Lesson 26 AC Power and Power Factor
LOGO LINEAR CIRCUIT ANALYSISSAJID HUSSAIN QAZI MEHRAN U.E.T, KHAIRPUR CAMPUS A.C POWERS AND POWER FACTOR.
ECE 2300 Circuit Analysis Dr. Dave Shattuck Associate Professor, ECE Dept. Lecture Set #24 Real and Reactive Power W326-D3.
Circuits II EE221 Unit 4 Instructor: Kevin D. Donohue Complex Power, Power Conservation, Power Factor Correction, and Applications.
AC POWER ANALYSIS Tunku Muhammad Nizar Bin Tunku Mansur
Fundamentals of Electric Circuits Chapter 11
Voltage Voltage is the potential energy source in an electrical circuit that makes things happen. It is sometimes called Electromotive Force or EMF. Voltage.
EE369 POWER SYSTEM ANALYSIS
POWER FACTOR CORRECTION
Lecture 28Electro Mechanical System1  Consider a circuit with a source, a load, & appropriate meters.  P and Q are positive, so the load absorbs both.
Fundamentals of Electric Circuits Chapter 11
Power in AC Circuits ELEC 308 Elements of Electrical Engineering
ELECTRICAL ENGINEERING: PRINCIPLES AND APPLICATIONS, Fourth Edition, by Allan R. Hambley, ©2008 Pearson Education, Inc. Lecture 16 Phasor Circuits, AC.
1 Chapter 11 AC Power Analysis 電路學 ( 二 ). 2 AC Power Analysis Chapter Instantaneous and Average Power 11.2Maximum Average Power Transfer 11.3Effective.
AC POWER ANALYSIS Instantaneous & Average Power
Chapter 7 AC Power Analysis
Circuits II EE221 Unit 11 Instructor: Kevin D. Donohue Complex Power, Power Conservation, Power Factor Correction, and Applications.
Chapter 11 AC Power Analysis
Power Factor Improvement Lecture 9. Normally, the power factor of the whole load on a large generating station is in the region of 0·8 to 0·9. However,
Lecture19 Examples Presented by Robert Trajkovski.
Chapter 17 Power in AC Circuits.
1 11/17/2015 Power Quality Correction. 2 11/17/2015 Power Quality Correction.
Three Phase Motors Maths
AC POWER ANALYSIS. 2 Content Average Power Maximum Average Power Transfer Complex Power Power Factor Correction.
REACTIVE POWER COMPENSATION
Lecture 32Electro Mechanical System1 Assignment 10 Page 396 Problems 17-9, 17-14, and Due Date: Thursday 28 th April, 2011 Quiz No.5 Next Week Quiz.
FUNDAMENTAL OF ELECTRICAL POWER SYSTEMS (EE 270)
NEUTRAL CURRENT IS NOT ZERO
1 Chapter 3 AC Power Analysis. 2 AC Power Analysis Chapter 3 3.1Instantaneous and Average Power 3.2Maximum Average Power Transfer 3.3Effective or RMS.
1 March 2001 EPCOS FK PM PFC Basics of Power Factor Correction BASICS OF POWER FACTOR CORRECTION.
Dr inż. Agnieszka Wardzińska Room: 105 Polanka cygnus.et.put.poznan.pl/~award Advisor hours: Monday: Wednesday:
Lesson 3: Ac Power in Single Phase Circuits
Power Generation and Distribution
Power Factor Correction The Definitive power solution
Lesson 22: AC Power Factor and Power Factor Correction
Lecture 07 AC POWER & POWER FACTOR.
POWER FACTOR CORRECTION
Lesson 5: Power In Balanced Three-Phase Systems
AC POWER & POWER FACTOR.
Real and Reactive Power
ECE 2202 Circuit Analysis II
Per-Unit System.
SWAMI VIVEKANAND COLLEGE OF ENGINEERING,INDORE(M.P)
Introduction To Reactive Power
ECE 333 Green Electric Energy
Electromechanical Systems
Some practice problems
Why does power factor matter Make-up of distribution capacitor banks
POLYPHASE CIRCUITS LEARNING GOALS Three Phase Circuits
BASIC ELECTRICAL ENGINEERING
Sr. Lecturer in Electrical Engg. Govt. Polytechnic,Manesar
ELL100: INTRODUCTION TO ELECTRICAL ENGG.
ECE 333 Green Energy Systems
The instantaneous power
Alternating Current Circuits
Power system operation and control
Comments on Final Exam Exam logistics: What is on the exam:
Engineering Circuit Analysis
ECE 2202 Circuit Analysis II
Presentation transcript:

Introduction to Distribution Systems Module D1-c Introduction to Distribution Systems (Continued) General comments Please perform ISU course evaluation. You should have received email on how to do this. Topics today: Final exam Power factor correction Taking EIT/PE exams. Induction motors Power electronics

Comments on Final Exam Exam logistics: What is on the exam: Monday May 6, 2019, 12:00-2:00pm Open book, open notes (must be hardcopies) No computer. No device that communicates. Expect to be in the room for 2 hours. What is on the exam: Between 4-7 problems to work. Additionally (possibly) short-answer or true false. Expect problems that integrate several topics. Points during semester when I said “This would be good final exam question.” Exam coverage: Comprehensive over coverage of entire semester. Energy system overview; Three-phase and per-unit analysis; Component model, operation, analysis for transformers, lines, synch gens Systems analysis: power flow problem. Systems analysis: economic dispatch Distribution systems and two-ports Power factor correction Induction machines Power electronics(?)

Power Factor Correction Recall: Assume |V| is constant. Given that we desire to supply a load that consumes a specified power P, do we want: pf close to 1 pf close to 0 Why?

We want pf close to 1.0 because then Answer: We want pf close to 1.0 because then I is minimum for the given P. Observe: So both currents I1 and I2 provide the same real power, but V I1 I2

Power Factor Correction: Basic Idea Note: We use absolute value signs around QC because, with a consuming load defined as positive, Qc is a negative number. The arrow indicates the actual direction of reactive flow. Iold VLN Inew VLN C VLN VLN Inew Iold

Power Factor Correction: Approach Iold VLN Inew VLN C Known (given or can be obtained): PL, pfold, pfnew Compute: 1. θold=acos(pfold), θnew=acos(pfnew) 2. QL=PLtanθold, Qnew=PLtanθnew, 3. QC=Qnew-QL 4. XC,Y=(VLN)2/QC,1ϕ =(VLL)2/QCXC,Δ=3XC,Y. 5. Use the appropriate XC to compute: BC=1/XC, C=1/ωXC

SHOULD YOU TRY TO OBTAIN YOUR PROFESSIONAL ENGINEERING LICENSE? www.nspe.org/resources/licensure/what-pe

SHOULD YOU TRY TO OBTAIN YOUR PROFESSIONAL ENGINEERING LICENSE? www.nspe.org/resources/licensure/what-pe

SHOULD YOU TRY TO OBTAIN YOUR PROFESSIONAL ENGINEERING LICENSE? www.nspe.org/resources/licensure/what-pe

SHOULD YOU TRY TO OBTAIN YOUR PROFESSIONAL ENGINEERING LICENSE? www.nspe.org/resources/licensure/what-pe Answer is “yes” if you want to practice engineering. The next problem was taken from a PE exam. This problem is a good practical problem of what you will see in the industry. I expect, for the final exam, that you can begin to “put things together” from the course, think, and solve problems like this.

A paper mill is supplied by a 13.8 kV, 3 , 60 Hz system SITUATION A paper mill is supplied by a 13.8 kV, 3 , 60 Hz system with appropriate transformers. The total load is as follows: Induction motors: 600 hp Eff = 85% pf = .8 lag Heating and lighting: 100 kW pf = unity Synchronous motors: 200 hp Eff = 90% 33

The synchronous motors are being operated at rated kVA and are over excited to correct the plant power factor to .95 lagging (so the synchronous motors are operating leading). It is desired to increase the mill output by 20% A plant survey indicated that the installed induction motor capacity could provide 20% more power than it is presently providing, but the synchronous machines are at rated kVA and cannot provide any more horsepower output. 34

It is suggested that it might be possible to increase the HP output of the synchronous motors by correcting the power factor of the synchronous motors to unity with a static bank of capacitors. The idea is to relieve the motors of their electrical reactive output in order to increase their real mechanical output. 35

(a) Determine if it is possible to increase the REQUIREMENT (a) Determine if it is possible to increase the output of the synchronous motors by 20% by reducing their excitation without exceeding the kVA ratings. (b) Determine the reactive power required, to correct the power factor to .95 lagging. 36

operating condition 1: as described (600 hp ind. mot., Define: operating condition 1: as described (600 hp ind. mot., 200 hp sync. mot, 100 kW lighting, plant power factor at 0.95, with high vars supplied by synchronous motors. operating condition 2: 20% more mechanical output from motors, plant power factor at 0.95 using power factor correction capacitors. 36

a) Synchronous motor presently consumes P1, Q1, where The question is, if we force reactive power to zero so that P2 = Srated, will ? 37

So we need to obtain Srated, since P2=Srated, and we can do this if we get P1 and Q1 via analysis of operating condition 1. P1 is easy: 38

To get Q1, we begin from knowing that under operating condition 1, the synchronous motor supplies enough Q to correct plant pf to 0.95. This means the power triangle for the entire plant appears as Stotal Qtotal Ptotal Other: induction motor & lighting loads. Values are positive for load consuming power.

Use a power triangle to show the relationship between all terms in the above equation. 39

Qtotal =Qother+Q1 =QIM + Q1  Ptotal =Pother+P1 =PH&L+PIM+P1 39

So our job is to find Pother and Qother, which are the total real and reactive powers, respectively, consumed by all other components in the plant: - induction motor load - heating and lighting load 40

Induction Motor 41

Heating and Lightning Load PHL = 100,000 w QHL = 0 42

So from boxed equation, Negative value indicates motors are supplying power. 43

43

So the % increase in power which is possible is: So we can increase beyond 20%. 44

Now at this point, we have only shown that we can increase mechanical output of synchronous motors by up to 28.7 % if we reduce its reactive demand. Now we want to compute exactly what reactive supply is needed from the capacitors at the 13.8 kV bus in order to maintain the plant 0.95 pf (lagging) and also provide for the 20% increase in plant output. 44

Synchronous motor increases output Assumption Synchronous motor increases output by 20% and is maintained at rated kVA. Note that since we are not increasing to the full 28.7%, there will still be some capability to supply reactive power. We do want to get as much reactive support from the synchronous motors as possible since it will reduce the amount of capacitance that we need to buy. 45

Based on this assumption, we can compute the real and reactive power into the synchronous motors. Since we know that it is supplying vars (leading), Q1<0 46

We need reactive of induction motor. Note PIM is greater than before because it is 20% more. Induction motor pf stays the same at 0.8 lag; because PIM increase, QIM must also increase (relative to what it was before). 46

So Ptotal = PIM+PHL+PSM = 930,839 watts Qtotal = QIM+QHL+QSM = 396914 = 631906+100000+198933 = 930,839 watts Qtotal = QIM+QHL+QSM = 473930+0-77016 = 396914 47

A pf of 0.95 lagging requires: What is Bc and C necessary to supply this reactive power? We need to know ……. 48

The voltage! Assume that it is 13.8 kV L-L. Recall that it will be delta connected. 48

Final comment on power factor correction Resonance occurs when an RLC circuit is excited by a frequency ω such that the impedance seen by the source is purely resistive. For example, consider the below RLC circuit: The impedance seen by the source is given by Z=R//jωL//-j/ωC, which is: 48

Final comment on power factor correction For this impedance to be entirely real, we have that Which implies that the resonant frequency is Note also that So resonance occurs when in the above circuit XL=XC, i.e., when the reactive consumption of the inductor is exactly compensated by the reactive supply of the capacitor. This is 100% compensation, or, 1.0 power factor condition. 48

Final comment on power factor correction Conclusion: Resonance is the condition under which the frequency causes the circuit to exhibit 1.0 power factor. Or…unity power factor condition is the condition for which resonance occurs in an RLC circuit. 48