Fire performance of structures

Slides:



Advertisements
Similar presentations
Design of Steel and Composite-Structures for Seismic Loading – Safety Requirements, Concepts and Methods – Prof. Dr.-Ing. Ekkehard Fehling, University.
Advertisements

Introduction to Lateral Force Resisting Systems
2.2 STRUCTURAL ELEMENT BEAM
Chp12- Footings.
Reinforced Concrete Design-8
Lecture 9 - Flexure June 20, 2003 CVEN 444.
Workshop at Indian Institute of Science 9-13 August, 2010 Bangalore India Fire Safety Engineering & Structures in Fire Organisers:CS Manohar and Ananth.
Lecture 33 - Design of Two-Way Floor Slab System
Sample Problem 4.2 SOLUTION:
Modeling for Analysis CE Design of Multi-Story Structures
Lecture Goals Slab design reinforcement.
Eurocode 1: Actions on structures – Part 1–2: General actions – Actions on structures exposed to fire Part of the One Stop Shop program.
Fire Behaviour Elements of Structure and Fire Development.
Beams Extremely common structural element
ONE-WAY SLAB. ONE-WAY SLAB Introduction A slab is structural element whose thickness is small compared to its own length and width. Slabs are usually.
Task 3.4. Validation of horizontal solutions Fire and mechanical characterization.
Enclosure Fire Dynamics
Eurocode 1: Actions on structures –
CM 197 Mechanics of Materials Chap 14: Stresses in Beams
Sample Problem 4.2 SOLUTION:
Introduction to composite construction of buildings
COLUMNS. COLUMNS Introduction According to ACI Code 2.1, a structural element with a ratio of height-to least lateral dimension exceeding three used.
Composite Beams and Columns
Design of steel structures under the aspect of fire protection measures TU BRAUNSCHWEIG iBMB Dr.-Ing. E. Richter Institute for Building Materials, Concrete.
SHEAR IN BEAMS. SHEAR IN BEAMS Introduction Loads applied to beams produce bending moments, shearing forces, as shown, and in some cases torques. Beams.
Heat Transfer in Structures
Static Pushover Analysis
Reinforced Concrete Design
BEAMS AND COLUMNS PRESENTED BY K.ROSHIN RUKSHANA.
Concrete 2003 Brisbane July 2003 Design Of Pre-cast Buried Structures For Internal Impact Loading.
FOOTINGS. FOOTINGS Introduction Footings are structural elements that transmit column or wall loads to the underlying soil below the structure. Footings.
Distribution of temperature in steel and composite beams and joints under natural fire F. Hanus (B.E.S.T. design office) & J.-M. Franssen (Univ. of Liege)
Workshop at Indian Institute of Science 9-13 August, 2010 Bangalore India Fire Safety Engineering & Structures in Fire Organisers:CS Manohar and Ananth.
Eurocode 1: Actions on structures – Part 1–2: General actions – Actions on structures exposed to fire Part of the One Stop Shop program Annex F (informative)
Eurocode 1: Actions on structures – Part 1–2: General actions – Actions on structures exposed to fire Part of the One Stop Shop program Annex A (informative)
©Teaching Resource in Design of Steel Structures IIT Madras, SERC Madras, Anna Univ., INSDAG 1 COMPOSITE FLOORS - II.
05/04/05 FEM Analysis of PA 44 Engine Mount PIPER SEMINOLE –PA-44 TWIN ENGINE AIRCRAFT.
02 November EN : Structural fire design EC2 Workshop Eurocodes Moscow 2010 J.C. Walraven Vermelding onderdeel organisatie.
Workshop at Indian Institute of Science 9-13 August, 2010 BangaloreIndia Fire Safety Engineering & Structures in Fire Organisers: CS Manohar and Ananth.
Design Fires A Structural Engineering Perspective Dr M Gillie.
Fordham Place Bronx, NY Aric Heffelfinger Structural Option Spring 2006.
Prof. Khalifa S. Al-Jabri
Preliminary Design & Steel Deck Alternative Presentation
Building Construction
Bassam A. Izzuddin* and Bassam A. Burgan†
Structural Slab Analysis
Introduction to composite construction of buildings
Sample Problem 4.2 SOLUTION:
M. Z. Bezas, Th. N. Nikolaidis, C. C. Baniotopoulos
Structural Fire Engineering, October 2015, Dubrovnik, Croatia
Behaviour of Reinforced Concrete Beams Under Bending
Heat and Mass Transfer Heat is ……… Heat Transfer ……
CE 808 : Structural Fire Engineering Ch 5. FIRE SEVERITY
Thermal analysis Friction brakes are required to transform large amounts of kinetic energy into heat over very short time periods and in the process they.
Building Construction
Chapter 3 BENDING MEMBERS.
Electrical Machine-I EE 2107 Dr. Md. Sherajul Islam
CE 808: Structural Fire Engineering SAFIR - Computer Program
New approach for evaluating Equivalent fire severity of Design fires
Nikhil Keshav Raut Michigan State University
Performance Based Design of a Steel Frame Hotel
AD16WM Workspace Management Lecturer: Daniel Wong MBA, MSc, BBus
Effect of Earthquake on Fire Protection Systems
Sample Problem 4.2 SOLUTION:
Eurocode 1: Actions on structures –
Structure II Course Code: ARCH 209 Dr. Aeid A. Abdulrazeg
Fire Resistance of Steel Structures
Effect of Location of Axial Restraint on Beam-Columns behavior in Fire
CE808: Structural Fire Engineering – Research Project
Masonry Bearing Walls.
Presentation transcript:

Fire performance of structures John Hewitt

Structures and Fire Structural design Structural engineers, Fire engineers Concepts for structural assessment in Fire Fire severity Time equivalence Other approaches Comparisons

Structural Design

Structural Design Loads are relatively well understood and/or defined in standards Loads are subject to factors of safety Expected strengths and member capacities are reduced by factors All structural materials are tested Each structural member is specifically designed for forces upon it, taking into account its role in the overall structure Structural engineers understand ‘load paths’ and how every force can be resisted and transferred to the ground

Structural design … but there are many uncertainties Dead loads, live loads, wind loads Seismic and fire – analogy – extreme cases Both push the structural performance beyond normal limits, allowing yield, and damage to occur In seismic design, very important to understand the structural performance, dynamics, non-linear behaviour etc Need similar understanding in a structural fire case to check that performance will be achieved

Structural Performance in fire – ideal performance: For buildings that would require Type A construction: No collapse of main structure, with full burn out No breach of compartmentation Usually no active systems or intervention assumed

Do structural engineers understand fire? Fire is not usually part of a structural engineers training (we are working on this!) FRL, fire severity, not understood fully or not at all BCA is rarely looked at But on being told a required FRL, structural designers will apply code rules for concrete dimensions, cover etc Loading standards specify a ‘Fire Load case’, ie a reduced vertical load to be supported in the case of a fire. For steel, can work out a ‘critical temperature’, for single elements. Fire performance of whole structure needs specialised knowledge

Do fire engineers understand structures? ?? Conclusion: In assessing fire performance of structures, there are gaps in the usual understanding of the main players

Concepts for structural fire performance

Structural Performance in fire – ideal performance: For buildings that would require Type A construction: No collapse of main structure, with full burn out No breach of compartmentation Usually no active systems or intervention assumed

Fire Protection for single steel elements How hot can the steel be allowed to reach, and still carry prescribed loads? How long must it remain below this temperature ie what is the required FRL? What protection is required to do this?

Steel - Reduction in strength and stiffness

Load Cases – AS 1170.0 Normal Load case 1.2 Dead + 1.5 Live Fire Load case 1.0 Dead + 0.4 or 0.7Live Load factors reduced eg If dead = Live If 90% utilization for NLC r = 0.9x FLC/NLC = 0.9 x 1.4/2.7 = 0.47 Tcrit = 905-690r Critical temperature = 583ºC

Critical Temperature 550 C often used as a criterion for fire protection materials But Critical temperature could be less – eg if mostly dead load Or could be more, eg if structure has spare strength under normal loads So need to check it

How quickly does steel heat up? Depends on: Gas temperature Exposed area Thermal Inertia Insulation

Ksm Concept High Ksm Low Ksm heats quickly heats slowly Exposed surface area to mass ratio m2/tonne Some codes use Heated Perimeter/Area Hp/A (deals with the same thing) High Ksm Low Ksm heats quickly heats slowly

Composite construction – interaction of elements For composite construction: Some secondary beams left unprotected Columns and their connections should be protected Floor slab is key to increased strength in fire conditions Detailed numerical models ·         Secondary beams can be left unprotected. ·         Unprotected beams can survive even if sprinklers do not operate. ·         Perimeter beams are relatively unheated in compartment fires and this should be considered when providing fire protection. ·         Columns should be protected to their full height and should include the connection. ·         The importance of composite floor slabs in maintaining structural stability will be emphasised. It is felt that this issue is the key to the strength observed in overall frame behaviour in fire. In particular, the development of tensile membrane action in the composite slab and its significance in maintaining the strength and stability of the structure even where large displacements occur. MENTION SCI GUIDE FOR 60 MINUTE ASSEMBLIES ETC ETC COLIN BAILEY TO ALLOW SECONDARY BEAMS TO BE UNPROTECTED

Importance of the slab Anchoring tensile membrane action around the perimeter edge of the slab Composite edge beams Anchoring reinforcing mesh

Heron Tower Compartment floor Typical Village Atrium floors

Design fire protection layout

One Shelley Street

One Shelley Street

Material Response - Timber Calculate the strength based on what’s left Charring and heat affected zone, deeper with time, insulates inner timber Eg 0.7mm/min +7.5 mm

Material Response - Concrete Heat transfer to other side – fire separation Heat transfer to steel Concrete degrades, may spall

Fire Severity

Time-Equivalent Analysis The more ventilation the lower the temperature so a lower rating possible Arup Fire conducted a study of time equivalence on a modern building with extensive glazed façade and compared that to the time equivalence of a traditional early 19th century office with a façade typical of the style when the fire resistance test was developed and prescriptive fire resistance guidance was written. The time equivalence calculation for the traditional office agreed with the prescriptive guidance for an office building of that height. The modern building only required half that value because the fire is so much less severe when there is so much ventilation. Ventilation - 60 v’s 120 minutes

Fire severity – time equivalence calculation

Fire severity – time equivalence calculation

Time equivalence – Eurocode formula

Time equivalence calculations – pros and cons Recognises effect of fuel load, ventilation, compartment dimensions and boundary conditions Simple to calculate, simple to use the result Cons Black box calculation Does not convey understanding of the nature of the fire Cannot separate short/hot fires from longer cooler fires Does not understand different structures, different critical temperatures, different structural performance Developed for protected steelwork, not concrete, timber, insulation issues etc

A more rigorous approach

Time temperature model Parametric fire CFD calc Test measurements Heat transfer model Radiation, convection, conduction 1-dimensional – lumped mass 2-d or 3-d heat transfer – finite elements Thermal properties constant or vary with time/temp Structural model Single element strength v temperature Interaction with whole building

‘Slimflor’ system

Finite Element Model

Temperature and strength at 60 minutes Upper flange, 100⁰ Strength 100% Lower flange, 600⁰ Strength 40% approx Overall plastic moment capacity, x 80% approx

1 dimensional assessment Protected steelwork – specific sections Time in a standard fire to cause same reduction in strength as predicted actual fire Critical temperature FIRE!

The effect of ventilation

Comparison case – 60 minutes equivalent FRL

Test case 60 FRL – compare using parametric fire, simple 1d heat transfer 410 x 60kg/m Universal beam, with fire protection for 60 FRL, 19mm insulation, critical temperature 550C

Parametric fire curve generated from same room/fuel data 410UB with protection FRL60, max temp = 493ºC < Tcrit

How about a much smaller steel section? 150 UB14 FRL60, 27mm insulation, max temperature 502C

Hot and fast or longer slower fire?

Long slow fire 410UB, long slow fire with T equiv = 60 min, max temp = 532ºC

400 dia concrete column Parametric fire ISO fire Based on Tequiv 60min Outer surface Inner core

Thomas, Buchanan & Fleischmann

Thomas, Buchanan & Fleischmann

Thomas, Buchanan & Fleischmann

Thomas, Buchanan & Fleischmann

Fire Severity - Summary Time equivalence calcs can be useful, but care needed to apply only when valid T equiv not useful for detailed structural fire assessment beyond applying FRL Concerns in a number of cases, eg short fires, cases other than protected steel structure More rigorous approach is possible, even with the same input data, that can provide better insight into performance and uses specific properties of the structure