Levine Lectronics and Lectric, Inc.

Slides:



Advertisements
Similar presentations
Chapter 4 Transformer Connections
Advertisements

CURRENT TRANSFORMERS AND VOLTAGE TRANSFORMERS
Chapter 12 Transformers. Chapter 12 Transformers.
Presentation : IMS – Tech Managers ConferenceAuthor : IMS StaffCreation date : 08 March 2012Classification : D3Conservation :Page : ‹#› 07 - TransformersAuthor.
Submitted by: Name:Rajendra Kumar Choudhury Branch:Electrical Engg.
 E4 Electrical Installation #1 Power Distribution.
ECE Electric Drives Topic 6: Voltage-Fed Converters Spring 2004.
ENERGY CONVERSION ONE (Course 25741)
Lesson 38 Shipboard Power
During fault behavior of circuit breaker
GENERATOR PROTECTION.
1 Distributed Generation and Power Quality. 2 Relaying considerations DG infeed may reduce the reach of overcurrent relays –DG feeds fault, so utility.
Review of 1- AC Circuit Fundamentals
Universal College of Engineering & Technology
Announcements Be reading Chapter 3
Transformers and Coupled Circuits
electronics fundamentals
Generator Protection. Amount of Protection Rated power of the generator Ratio of its capacity to the total capacity of the system Configuration of the.
Unit Transformer Unit transformer are step up transformer which is connected to generating house & step up voltage from 15kV voltage to 132 voltage level.
SHUNT CAPACITOR FUNDAMENTALS AND PROTECTION
Basic Electricity.
Chapter 8 Inverters AC Power • Inverters • Power Conditioning Units • Inverter Features and Specifications.
PRODUCTS TRANSFORMERS ENERGY SAVING TRANSFORMERS (EST) TRANSFORMER RECTIFIER UNITS 3 rd HARMONIC REJECTION TRANSFORMERS (HRT) ULTRA HIGH ISOLATION TRANSFORMERS.
Substations. Substations Chapter 4 Substations Major types of equipment found in most transmission and distribution substations with their purpose,
Coal Mine Connections Lessons from Experience. Why are we talking about Coal mine connections Because we had a situation where the customer wanted a service.
Interconnect Protection of Dispersed Generators
Chapter 2 Transformers.
Transient Overvoltages
Instrument Transformers
Transformer Taking the ratio of the two equations
Announcements Please read Chapter 3; start on Chapter 6
Announcements For lectures 9 and 10 please be reading Chapter 3
Transformer Protection Over-current protection in the form of fuses may be the only protection provided to a small 100 kVA, 11 kV/440 V distribution transformer.
Chapter 2 Transformers Edit by Chi-Shan Yu Electric Machinery.
Lecture 11Electro Mechanical System1 Delta-Delta Connection  Three single-phase transformers connected delta-delta  H 1 terminal of each transformer.
Grounding.
A Training Presentation On 132 KV GSS JAIPUR Submitted in partial fulfillment For the award of the degree of BACHELOR OF TECHNOLOGY Submitted To:- Submitted.
DISTRIBUTED GENERATION ISSUES Technical Issues Non-Technical Issues.
Protection of Power Systems
TECHNICAL PAPER ON SIMULTANEOUS AC-DC POWER TRANSMISSION
Protection of Power Systems
SYNERGY INSTITUTE OF ENGINEERING AND TECHNOLOGY
DC Machine & Transformer
Push Button Station and Relay
STUDY OF ELEMENTS OF A 220/132/33KV SUBSTATION
Transformers. Single Phase Transformers Principles of Operation – Single Phase.
ET 332b Ac Motors, Generators and Power Systems 1 Lesson 11_et332b.pptx.
Auto Transformer Current Flow. Principles of Auto Transformers H X H0/X0.
HNC/D Engineering Science
Sub Station.
Grounding.
Interconnect Protection of Dispersed Generators
DC MACHINE AND tRANSFORMER
3-Phase Transformer Construction, Principal, Working, Operation Advantages Over 1-Phase Transformer Introduction Advatages Construction Principal Working.
ELECTRONICS & COMMUNICATION 3-SEM SHANTILAL DHOLIYA ( )
THREE-PHASE GROUND-FAULT BASICS
Electrical Machine-I EE 2107 Dr. Md. Sherajul Islam
Φ 3. Transformer Models. Turns ratio 7200:240 (30 : 1)
electronics fundamentals
Three Phase Transformers
Lesson 11: Transformer Name Plate Data and Connections
3-Phase Transformer Construction, Principal, Working, Operation Advantages Over 1-Phase Transformer Introduction Advatages Construction Principal Working.
Lecture 10 - Transformers/Three-Phase Circuits
Electrical Machines LSEGG216A 9080V.
Chapter 33 Transformer: Three Phase. Chapter 33 Transformer: Three Phase.
Substation Equipment's
Presentation transcript:

Levine Lectronics and Lectric, Inc. Grounding Transformers Medford, Oregon Medford, Oregon John S. Levine, P.E. Levine Lectronics and Lectric, Inc. February, 2007 March 2011

What is a Grounding Transformer? It is used to provide a ground path on either an ungrounded Wye or a Delta connected system The relatively low impedance path to ground maintains the system neutral at ground potential

Why do I need to have a Grounding Transformer? On Ungrounded systems you can have overvoltages of 6 to 8 times normal with arcing faults

Arcing Ground Faults Intermittent or Re-strike Plot of transient over-voltage for an arcing ground fault 1

Arcing Ground Faults Intermittent or Re-strike Intermittent ground fault: A re-striking ground fault can create a high frequency oscillator (RLC circuit), independent of L and C values, causing high transient over-voltages. i.e. re-striking due to ac voltage waveform or loose wire caused by vibration 1

THE HIGH RESISTANCE GROUNDED POWER SYSTEM CONTROL OF TRANSIENT OVERVOLTAGE 1

What is a Grounding Transformer? It supports the voltage on a faulted phase If a single line-to-ground fault occurs on an ungrounded or isolated system, no return path exists and no current flows The system will continue to operate but the other two un-faulted lines will rise in in voltage by the square root of 3, possibly overstressing the transformer insulation, and other components, by 173%

UNGROUNDED SYSTEM NORMAL CONDITIONS 1

UNGROUNDED SYSTEM GROUND FAULT ON PHASE A 1

What is a Grounding Transformer? Provides a metering point to measure faults

Where are Grounding Transformers used? A typical example is a Wind Farm. They utilize grounding transformers for fault protection on ungrounded lines When a ground fault occurs on a collector cable causes the substation circuit breaker to open, the wind turbine string becomes isolated Turbines do not always detect the fault and the generators continue to energize the cable. Voltages between the un-faulted cable and the ground rise by the 173% The transformer, placed on the turbine string, provides the ground path

Typical Wind Farm System Design A typical example is a Wind Farm. When the feeder breaker Opens, the collector bus and the step up transformer delta connected MV windings rely on the Grounding Transformer for their ground path and voltage support.

Types of Grounding Transformers Two different constructions: ZIG ZAG (Zn) WYE CONNECTED

How do you create the Ground? What if no neutral exists (i.e. delta systems)? A grounding transformer is installed (either a zig-zag or a wye-delta) from all three phases to create an artificial neutral for grounding purposes only. A Ø B C A Ø B Ø C Ø A Ø B Ø C Ø HRG Zig-Zag Grounding Transformer HRG Wye-Delta Broken Delta Grounding Grounding Transformers Transformers HRG 1

ZIG ZAG The zigzag transformer contains six coils on three cores. The first coil on each core is connected contrariwise to the second coil on the next core. The second coils are then all tied together to form the neutral and the phases are connected to the primary coils. Each phase, therefore, couples with each other phase and the voltages cancel out

Vector diagram of balanced system A B C Typical Wye connection with Neutral end of windings connected Together A B C Symmetrical three phase source A B C

a A c C The Zig-Zag connection has 2 windings on each leg. B b

Each leg of the Zig-Zag Connection is connected to a winding from another which is out of phase B C A c b a C B A b c a

The resulting Zig-Zag connection Is phase shifted with respect to the incoming three phase source Az Cz Bz

ZIG ZAG Limits circulation of triplen harmonics ( 3 rd, 6th, 9th, etc) Can be used without a Delta connected or 5-legged core Elimination of secondary winding results in smaller footprint, lower cost (25-30%)

Wye Connected Includes a Delta or Wye connected secondary Utilizes 4 or 5 legged core when Wye connected secondary is specified Multi-functional, provides benefit of auxiliary power

How to Specify a Grounding Transformer Know the basic parameters Primary Voltage Phase to Phase continuous primary current (or Rated kVA) Continuous Neutral current Available Fault Current and Duration Impedance as a % or as an ohms/phase value Primary Winding connection Secondary connection Basic overall construction

Primary Voltage This is the system voltage to which the grounded winding is to be connected. Don’t forget to specify the BIL also. In some cases the BIL will be dictated by equipment considerations, such as 150 kV BIL on 34.5 kV wind farms because of the limitation of dead front connectors

Primary Current The Transformer must be sized to carry the rated continuous, phase-to-phase current without exceeding its temperature limit The higher the current, the larger and more costly the transformer Typical values can be as low as 5 amps to as high as a few hundred Include any auxiliary loading requirements

Continuous Neutral Current Is defined as 3X the Phase-to-Phase current (Zero Sequence Current) It is the value that is expected to flow in the neutral circuit without tripping protective circuits Used to design for thermal capacity of the transformer

Fault Current and Duration Used to determine the short time heating resulting from a fault on the system which returns through the transformer Typical ranges run from a few hundred to a few thousand amps Duration is expressed in seconds (i.e. 400 amps for 10 seconds)

Impedance Can be expressed as either a percentage or as an ohmic value Either should be chosen such that the un-faulted phase voltages are within the temporary over-voltage capability of: The Transformer Associated equipment (i.e. arresters, terminal connectors, etc.) Typical values can be as low as 8% and as much as 100% Must be determined by the system designer

Primary Winding Connection Zig Zag or Grounded Wye

Secondary Connection Specify the secondary voltage and connection for primary Wye connected transformers Specify size of auxiliary loading to be connected If two winding with no secondary load, advise if the delta winding can be “buried” (not brought out) or if only one bushing is to be brought out for grounding to the tank or testing

Construction Features Compartmental pad mount or unit substation design Indoor or outdoor Fluid type (Mineral Oil, Silicone, or Envirotemp FR3) Site Elevation or Environmental conditions Connectivity Dead Front or Live Front Spade terminals Cover-mounted or sidewall Exposed or enclosed Temperature Rise 65 degrees C 55 degrees C 55/65 deg. C Special Coating requirements

Pictures of Liquid Filled Transformer

Round Coils 360 degree cooling ducts Radial forces are equalized during short circuits & overloads

Cruciform stacked core construction

Padmount Transformer

Unit Substation and Substation Transformer

Other types of Transformers The following transformers are for reference only to let you be aware of different type transformers for different applications.

NEUTRAL GROUNDING RESISTOR with Transformer

What is a Scott – T Transformer? A Scott – T Transformer is a transformer that is designed for converting 2 phase current to 3 phase current or vice-versa.

What is an Autotransformer An autotransformer is a transformer that only have one winding with taps. No isolation is provided between the primary and secondary.

Buck-Boost A Buck-Boost transformer is one that is designed to lower (buck) or raise (boost) the voltage in the range of 5% to 25%. This is a great (low cost) way to get between 208 and 240 Volts, or between 480 and 575 Volts. Used on 1 and 3 Phase applications.

Drive Isolation Transformers A drive isolation transformer is one that is typically used on AC or DC Drive systems. It typically has the same primary and secondary voltages and is used for isolation. In addition you typically have a shield to attenuate line to ground noise.

Constant Voltage Transformer A constant voltage transformer is one in which the secondary stays constant with large swings on the primary voltage. This is accomplished by operating the primary in a saturated mode so even when the primary voltage dips you can still maintain a constant output. Typical input may be 80% to 110% with the output maintaining 1% voltage regulation.

A copy of this presentation can be found at: www.L-3.com

www. PacificCrestTrans.com For more information and specification sheets www. PacificCrestTrans.com