IEEE Power Engineering Society Toronto Chapter Ontario Wind Turbines – Testing of Electrical Safety Kinectrics Seminar May, 2007 Eugene Peter Dick IEEE Senior Member 49 Lynngrove Ave Toronto, Ontario
1.5 MW GE Wind Turbine
Foundation - Elevation
Tower Height: 65 to 80+ m Base Flange: 5 m , circa 200 bolts (ext, interior) Sections: 3 joined by interior flanges, platforms Access: ladder with fall restraint Bus type: rigid or locomotive flexible cable Section: 500+ mm 2 ( mcm) Erection: 500 tonne crane
Bolt Ring – Duplicated Inside
500 Tonne Crane
Nacelle
Rotor Blades Diameter: 71 m Speed: 12 – 22 rpm Gearbox: 3-step planetary spur gear, ratio 72 Power vs wind speed:kWk/hr cut out90
Generator Rating: 1.5 MW, 1.72 MVA, 575 V, stator A Type: double fed, 3 , (induction?) synchronous Rotor via PWM drive rated 300 kW Poles: 6, - / + 20 % speed (864 to rpm) H (inertial const): 6.55 s (gen alone 0.8 s) Xd” (subtransient reactance): 0.27 pu Protection: V over / under / unbal, f over / under Control: pf or current compensated V
Typical Interconnect Requirements < 88 % V trip in 2 s, < 50 % V trip in 0.16 s > 110 % V trip in 1 s, > 120 % V trip in 0.16 s < 59.8 Hz trip in 300 s, < 57 Hz trip in 0.16 s V on synch: < 5 %, flicker IEEE Std 519, 1453 dc: < 0.5 % on I harmonics: < 4, 2, 1.5, 0.6 % (h<11, 17, 23, 35) islanding with load: trip in less than 2 s no impact on utility feeder protection
Stepup Transformer
Transformer / Collection System Xmer: 575 / 34.5 kV, Yg / , Z = j 5.70 % 35-kV, 67 mm 2 (AWG 2/0) concentric Neu cable several units daisy-chained to riser pole may run Neu / bond back to main substation overhead line may be 3 or 4-wire typically 4 collection lines to main station, CB each collection line may have gnding Xmer main Xmer: 34.5 / 230 kV, 100 MVA
Stepup Transformer Cabinet
Cable Run to Riser Pole
Collection Line to Main Substation
Main Substation
Grounding Transformers
230-kV System Tie
Erie Shores Setting
Erie Shores Layout
Erie Shores Ground Electrode
Sault Ste Marie (Prince) Wilderness
Prince Layout
Prince in Autumn
Prince in Late Autumn
Prince Ground Electrode
Prince 1 Collection Cable
Grounding - Objectives limit V between touchable objects provide low Z path so protection sees fault I direct fault I, lightning away from equipment minimize interference
Grounding - Definitions Remote earth: soil not rising in potential on faults Bonding: to connect two objects with low Z path Grounding: to provide bonding to remote earth G System: all conductors that facilitate grounding G Current: fault current that enters a G system G Electrode: conductors that dissipate I into soil G Potential Rise: V between G system, remote soil Step Potential: foot-to-foot V during system fault Touch Potential: hand-to-foot V on system fault
Grounding – Tested Quantities GPR: general hazard indicator, telco pairs Step V: coord to safe body withstand (180, V) Touch V: coord to safe body withstand (168, 663 V) Touch types: structure, mesh, fence, gate, exterior Current splits: on external connections: Neu, Ohg Soil resistivity: model all of above Surface stone resistivity: check for deterioration Conductor integrity: measured and modelled
GPR = Rg Ig Ig - Vg + Telco
Measure Rg with Fall of Potential C1 P1 C2 P2 x c
Locate Probe P at 62 % of Probe C
When Soil Has Two Layers C1 P1 C2 P2 x c h 11 22
Adjust Location for P to C Ratio
Interconnections Affect P to C Ratio C1 P1 C2 P2 x c
Soil Anomalies Affect P to C Ratio low C1 P1 C2 P2 x c high
Proximity Correction: Arbitrary P, C low C1 P1 C2 P2 x c high
Running Out Leads in Fair Weather
Testing When Snow Flies
Reading the AC Milliohm Meter
Six Towers Left Before Nightfall
Network Analyzer for Current Splits low C1 Split- Core CT c high C2 Network Analyzer
Rogawski Coil for Current Splits
Counterpoise Current Split
Network Analyzer, Scope, Megger
Network Analyzer for Impedance low C1 P1 P2 x c high C2 Network Analyzer
Equiv Cct for Proximity Corrections XcgXgp Xcp Ic - Ic Rcg + Ic + Ic Rgp - Ic Rcp + + Vp - Zd Rg
Proximity Correction Method Zg= Zm + Rgp + Rcg – Rcp = Zd / ( Zd + Rg ) =b + Rcg / ( Rcg + Zd ) measure Zm and read Zm at several locations for P find Zg for each, average these estimates calculate standard deviation as quality check
Measuring Step Potential
Measuring Touch Potential
Summary When sandy soil or rock raise Rg, tests useful Fall of Pot bad with soil anomalies, interconnections Proximity Correction method has P and C opposite Multiple estimates of Zg averaged for less noise Standard deviation of Zg checked for quality Measuring current splits good with interconnections