Lesson 8 Symmetrical Components

Slides:



Advertisements
Similar presentations
Lecture 11: Unsymmetrical Short Circuits
Advertisements

EE369 POWER SYSTEM ANALYSIS
Lecture 2 Complex Power, Reactive Compensation, Three Phase Dr. Youssef A. Mobarak Department of Electrical Engineering EE 351 POWER SYSTEM ANALYSIS.
Basic Electronics Ninth Edition Basic Electronics Ninth Edition ©2002 The McGraw-Hill Companies Grob Schultz.
Complex Numbers for AC Circuits Topics Covered in Chapter : Positive and Negative Numbers 24-2: The j Operator 24-3: Definition of a Complex Number.
Lecture #12 EGR 272 – Circuit Theory II
Lecture 1. Balanced Three-phase Systems From Network to Single-phase Equivalent Circuit Power plant TransformerSwitching station LineLoad Three-phase.
ECE Electric Drives Topic 6: Voltage-Fed Converters Spring 2004.
Announcements Be reading Chapters 8 and 9
Chapter 24 Three-Phase Systems.
Chapter 12 Three Phase Circuits
1 Three-phase Circuits Balanced 3-phase systems Unbalanced 3-phase systems Dr. Nik Rumzi Nik Idris SKEE 1043 Circuit Theory.
SYMMETRICAL COMPONENETS OF POWER SYSTEM
Chapter 12 Three-Phase Circuits
Chapter 19 Methods of AC Analysis. 2 Dependent Sources Voltages and currents of independent sources –Not dependent upon any voltage or current elsewhere.
BASIC ELECTRICAL TECHNOLOGY Chapter 3 - Three Phase System
1 Chapter 1. Three-Phase System. 1.1: Review of Single-Phase System The Sinusoidal voltage v 1 (t) = V m sin  t i v1v1 Load AC generator v2v2 2.
ECE 4411 Introduction to Three-Phase Power. ECE 4412 Typical Transformer Yard.
Balanced Three-Phase Circuits
Lesson 35 Per Phase Analysis
Lecture 101 EEE 302 Electrical Networks II Dr. Keith E. Holbert Summer 2001.
Announcements Be reading Chapter 3
Chapter 12 Three Phase Circuits
Chapter 12 Three-Phase Circuit Analysis
Chapter 7 Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
EET 103 Chapter 3 (Lecture 1) Three Phase System.
THREE PHASE CIRCUIT.
Balanced 3-phase systems Unbalanced 3-phase systems
Circuits II EE221 Unit 12 Instructor: Kevin D. Donohue
Three – Phase Power System. Three-Phase Power Definitions 4 wires –3 “active” phases, A, B, C –1 “ground”, or “neutral” Color Code –Phase ARed –Phase.
Sinusoidal Response of RC Circuits
Chapter 5 Steady-State Sinusoidal Analysis. 1. Identify the frequency, angular frequency, peak value, rms value, and phase of a sinusoidal signal. 2.
ECE 530 – Analysis Techniques for Large-Scale Electrical Systems
BALANCED THREE-PHASE CIRCUITS
Announcements Please read Chapter 4 HW 1 is due now
1 ELECTRICAL CIRCUIT ET 201  Become familiar with the operation of a three phase generator and the magnitude and phase relationship.  Be able to calculate.
Review 1. Review of Phasors Goal of phasor analysis is to simplify the analysis of constant frequency ac systems: v(t) = V max cos(  t +  v ), i(t)
Fundamentals of Electric Circuits Chapter 12
Announcements Please read Chapter 3; start on Chapter 6
Guided by: Sudhir pandey
Grossman/Melkonian Chapter 3 Resistive Network Analysis.
Three-Phase System 1 by Dr Rosemizi Abd Rahim Click here to watch the three phase animation video
Announcements Read Chapters 8 and 9 HW 9 quiz today
THREE PHASE POWER Generation Transportation Consumption.
Announcements Please read Chapters 1 and 2
ELECTRICAL TECHNOLOGY (EET 103) PN HAZIAH ABDUL HAMID.
Lecture II Objective: Representation of sequence components
Balanced poly phase circuits. Two and four phase systems  A two phase system is an electrical system in which the voltages of the phases are 90 degree.
EKT103 ELECTRICAL ENGINEERING
Transformer Current & Voltage Practice
FUNDAMENTALS OF ELECTRICAL ENGINEERING [ ENT 163 ]
Lecture 19 Fault Analysis, Grounding, Symmetrical Components Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM.
MUZAIDI BIN MARZUKI PPKSE.
NEUTRAL CURRENT IS NOT ZERO
0 Balanced 3 Phase (  ) Systems A balanced 3 phase (  ) system has three voltage sources with equal magnitude, but with an angle shift of 120  equal.
Power System Protective Relaying-Part Two
ET 332b Ac Motors, Generators and Power Systems 1 Lesson 11_et332b.pptx.
Three-Phase Systems Professor Mohamed A. El-Sharkawi
ECE 476 POWER SYSTEM ANALYSIS
Module B3 More on Three Phase Analysis
POLYPHASE CIRCUITS Three Phase Circuits
DKT213 ELECTRICAL TECHNOLOGY
Lesson 4: Three Phase Sources and Loads
POLYPHASE CIRCUITS Three Phase Circuits
Energy Conversion and Transport George G. Karady & Keith Holbert
Circuits II EE221 Unit 12 Instructor: Kevin D. Donohue
Three Phase Circuits Chapter Objectives:
C H A P T E R 23 Symmetrical Components.
Power System Analysis (EELE 4351)
POLYPHASE CIRCUITS LEARNING GOALS Three Phase Circuits
Presentation transcript:

Lesson 8 Symmetrical Components Notes on Power System Analysis

Symmetrical Components Due to C. L. Fortescue (1918): a set of n unbalanced phasors in an n-phase system can be resolved into n balanced phasors by a linear transformation The n sets are called symmetrical components One of the n sets is a single-phase set and the others are n-phase balanced sets Here n = 3 which gives the following case: 8 Symmetrical Components Notes on Power System Analysis

Symmetrical component definition Three-phase voltages Va, Vb, and Vc (not necessarily balanced, with phase sequence a-b-c) can be resolved into three sets of sequence components: Zero sequence Va0=Vb0=Vc0 Positive sequence Va1, Vb1, Vc1 balanced with phase sequence a-b-c Negative sequence Va2, Vb2, Vc2 balanced with phase sequence c-b-a 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Va = 1 V0 Vb a2 a V1 Vc V2 where a = 1/120° = (-1 + j 3)/2 a2 = 1/240° = 1/-120° a3 = 1/360° = 1/0 ° 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis 1 a2 a Vs = V0 V1 V2 Vp = Va Vb Vc Vp = A Vs Vs = A-1 Vp 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis (1/3) 1 a a2 We used voltages for example, but the result applies to current or any other phasor quantity Vp = A Vs Vs = A-1 Vp Ip = A Is Is = A-1 Ip 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Va = V0 + V1 + V2 Vb = V0 + a2V1 + aV2 Vc = V0 + aV1 + a2V2 V0 = (Va + Vb + Vc)/3 V1 = (Va + aVb + a2Vc)/3 V2 = (Va + a2Vb + aVc)/3 These are the phase a symmetrical (or sequence) components. The other phases follow since the sequences are balanced. 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Sequence networks A balanced Y-connected load has three impedances Zy connected line to neutral and one impedance Zn connected neutral to ground Zy g c b a Zn 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Sequence networks Vag = Zy+Zn Zn Ia Vbg Ib Vcg Ic or in more compact notation Vp = Zp Ip 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Zy Vp = Zp Ip Vp = AVs = Zp Ip = ZpAIs AVs = ZpAIs Vs = (A-1ZpA) Is Vs = Zs Is where Zs = A-1ZpA Zy g c b a Zn n 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Zs = Zy+3Zn Zy V0 = (Zy + 3Zn) I0 = Z0 I0 V1 = Zy I1 = Z1 I1 V2 = Zy I2 = Z2 I2 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Zy n a V2 I2 Negative- sequence network Zy n g a 3 Zn V0 I0 Zero- sequence network Zy n a V1 I1 Positive- sequence network Sequence networks for Y-connected load impedances 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis ZD/3 n a V2 I2 Negative- sequence network ZD/3 n g a V0 I0 Zero- sequence network ZD/3 n a V1 I1 Positive- sequence network Sequence networks for D-connected load impedances. Note that these are equivalent Y circuits. 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Remarks Positive-sequence impedance is equal to negative-sequence impedance for symmetrical impedance loads and lines Rotating machines can have different positive and negative sequence impedances Zero-sequence impedance is usually different than the other two sequence impedances Zero-sequence current can circulate in a delta but the line current (at the terminals of the delta) is zero in that sequence 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis General case unsymmetrical impedances Zp = Zaa Zab Zca Zbb Zbc Zcc Zs=A-1ZpA = Z0 Z01 Z02 Z10 Z1 Z12 Z20 Z21 Z2 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Z0 = (Zaa+Zbb+Zcc+2Zab+2Zbc+2Zca)/3 Z1 = Z2 = (Zaa+Zbb +Zcc–Zab–Zbc–Zca)/3 Z01 = Z20 = (Zaa+a2Zbb+aZcc–aZab–Zbc–a2Zca)/3 Z02 = Z10 = (Zaa+aZbb+a2Zcc–a2Zab–Zbc–aZca)/3 Z12 = (Zaa+a2Zbb+aZcc+2aZab+2Zbc+2a2Zca)/3 Z21 = (Zaa+aZbb+a2Zcc+2a2Zab+2Zbc+2aZca)/3 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Special case symmetrical impedances Zp = Zaa Zab Zs = Z0 Z1 Z2 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Z0 = Zaa + 2Zab Z1 = Z2 = Zaa – Zab Z01=Z20=Z02=Z10=Z12=Z21= 0 Vp = Zp Ip Vs = Zs Is This applies to impedance loads and to series impedances (the voltage is the drop across the series impedances) 8 Symmetrical Components Notes on Power System Analysis

Power in sequence networks Sp = Vag Ia* + Vbg Ib* + Vcg Ic* Sp = [Vag Vbg Vcg] [Ia* Ib* Ic*]T Sp = VpT Ip* = (AVs)T (AIs)* = VsT ATA* Is* 8 Symmetrical Components Notes on Power System Analysis

Power in sequence networks Sp = VpT Ip* = VsT ATA* Is* ATA* = 1 = 3 a2 a Sp = 3 VsT Is* 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Sp = 3 (V0 I0* + V1 I1* +V2 I2*) = 3 Ss In words, the sum of the power calculated in the three sequence networks must be multiplied by 3 to obtain the total power. This is an artifact of the constants in the transformation. Some authors divide A by 3 to produce a power-invariant transformation. Most of the industry uses the form that we do. 8 Symmetrical Components Notes on Power System Analysis

Sequence networks for power apparatus Slides that follow show sequence networks for generators, loads, and transformers Pay attention to zero-sequence networks, as all three phase currents are equal in magnitude and phase angle 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis V1 I1 Positive Z1 N V2 I2 Negative Zn Z2 G Y generator V0 3Zn Zero I0 Z0 N 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis V1 I1 Positive Z N V2 I2 Negative Ungrounded Y load Z G V0 Zero I0 Z N 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Zero-sequence networks for loads G V0 3Zn Y-connected load grounded through Zn I0 Z N G D-connected load ungrounded V0 Z 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Y-Y transformer H1 X1 A a Zeq+3(ZN+Zn) A a B VA0 I0 Va0 b g c C Zero-sequence network (per unit) N n ZN Zn 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Y-Y transformer Zeq H1 X1 A a A a VA1 I1 Va1 B b n c C Positive-sequence network (per unit) Negative sequence is same network N n ZN Zn 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis D-Y transformer H1 X1 A a Zeq+3Zn A a B VA0 I0 Va0 b g c C Zero-sequence network (per unit) n Zn 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis D-Y transformer H1 X1 A a Zeq A a B VA1 I1 Va1 b n c C Positive-sequence network (per unit) Delta side leads wye side by 30 degrees n Zn 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis D-Y transformer H1 X1 A a Zeq A a B VA2 I2 Va2 b n c C Negative-sequence network (per unit) Delta side lags wye side by 30 degrees n Zn 8 Symmetrical Components Notes on Power System Analysis

Three-winding (three-phase) transformers Y-Y-D H and X in grounded Y and T in delta Zero sequence Positive and negative Ground Neutral ZT X H ZH H ZH ZX ZX X ZT T T 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Three-winding transformer data: Windings Z Base MVA H-X 5.39% 150 H-T 6.44% 56.6 X-T 4.00% 56.6 Convert all Z's to the system base of 100 MVA: Zhx = 5.39% (100/150) = 3.59% ZhT = 6.44% (100/56.6) = 11.38% ZxT = 4.00% (100/56.6) = 7.07% 8 Symmetrical Components Notes on Power System Analysis

Notes on Power System Analysis Calculate the equivalent circuit parameters: Solving: ZHX = ZH + ZX ZHT = ZH + ZT ZXT = ZX +ZT Gives: ZH = (ZHX + ZHT - ZXT)/2 = 3.95% ZX = (ZHX + ZXT - ZHT)/2 = -0.359% ZT = (ZHT + ZXT - ZHX)/2 = 7.43% 8 Symmetrical Components Notes on Power System Analysis

Typical relative sizes of sequence impedance values Balanced three-phase lines: Z0 > Z1 = Z2 Balanced three-phase transformers (usually): Z1 = Z2 = Z0 Rotating machines: Z1  Z2 > Z0 8 Symmetrical Components Notes on Power System Analysis

Unbalanced Short Circuits Procedure: Set up all three sequence networks Interconnect networks at point of the fault to simulate a short circuit Calculate the sequence I and V Transform to ABC currents and voltages 8 Symmetrical Components Notes on Power System Analysis